Loading ...
Loading ...
Loading ...
Part Number 000015236 Rev 00 11/17 19
Section 3
Operation
NOTE: Flake and nugget ice machines use an auger to
remove ice from the evaporator. Occasional noises (creaks,
groans, squeaks, or pops) are a normal part of the ice making
process.
Bin Thermostat and Evaporator Low Temperature
Safety Adjustment Chart
The bin thermostat sensing bulb is located in the ice chute
or bin and turns the ice machine on and off as the level
of ice in the ice chute or bin changes. The evaporator low
temperature safety protects the evaporator and compressor
from damage caused by water loss or gear motor failure.
Model
Bin Thermostat
Setting
Evaporator
Thermostat Setting
UNF0200 5 5
UFF0200 5 5
RFF0320 4 7
UFF0350 5 7
UNF0300 5 7
RNF0620 3 ---
RFF0620 3 ---
RNF1100 3 ---
RFF1300 3 ---
RFF2500 3 ---
1
2
3
4
5
6
7
1
2
3
4
5
6
7
BIN THERMOSTAT
SMALL NUMBERS = LESS ICE IN BIN
LARGE NUMBERS = MORE ICE IN BIN
EVAPORATOR LOW TEMPERATURE
SAFETY THERMOSTAT
INCORRECT SETTINGS WILL CAUSE ICE MACHINE
TO SHUT OFF
Thermostat Adjustment for Altitude
Installation at altitude will require an adjustment to allow the
ice machine to operate according to the thermostat setting
chart.
Refer to table and adjust bin thermostat to match the
installation location altitude.
After adjustment verify the ice machine operates according
to the bin thermostat adjustment chart.
NOTE: The screw located between the electrical terminals
sets the cut-in/cut-out differential and must never be
adjusted.
ALTITUDE ADJUSTMENT CHART
Altitude
Feet
Meters
Bin Thermostat
Turn Screw Clockwise to Adjust
2000
610
1/4 Turn
4000
1219
5/8 Turn
6000
1829
1 Turn
8000
2438
1 3/8 Turn
Adjustment Screw
Loading ...
Loading ...
Loading ...