AQUA PLUS indirect-fired water heaters — Product Manual
Ratings with 180°F boiler supply water
For water heater to achieve the rated performance below: Boiler water must be supplied to the water heater at least
180°F, and the boiler water flow rate must be no less than given in the tables below.
Boiler
Heating
Capacity
MBH
First Hour Rating Capacity (GPH) — Boiler Water Supply at 180°F
DHW
temps
AQUA
PLUS
35
Boiler
Water
Min GPM &
Head Loss
AQUA
PLUS
45
Boiler
Water
Min GPM &
Head Loss
AQUA
PLUS
55
Boiler
Water
Min GPM &
Head Loss
AQUA
PLUS
85
Boiler
Water
Min GPM &
Head Loss
AQUA
PLUS
105
Boiler
Water
Min GPM &
Head Loss
DHW 50°F to 140°F
93
8 GPM
minimum
@
1.6 ft wc
103
8 GPM
minimum
@
1.6 ft wc
124
8 GPM
minimum
@
1.6 ft wc
138
14 GPM
minimum
@
5.4 ft wc
148
14 GPM
minimum
@
7.1 ft wc
120 130 151 165 175
147 157 178 192 202
174 184 205 219 229
181 200 232 246 256
181 200 252 273 283
181 200 252 300 310
181 200 252 310 337
181 200 252 310 363
181 200 252 310 400
181 200 252 310 400
181 200 252 310 400
181 200 252 310 400
181 200 252 310 400
181 200 252 310 400
DHW 50°F to 115°F
119
8 GPM
minimum
@
1.6 ft wc
129
8 GPM
minimum
@
1.6 ft wc
150
8 GPM
minimum
@
1.6 ft wc
164
14 GPM
minimum
@
5.4 ft wc
174
14 GPM
minimum
@
7.1 ft wc
156 166 187 201 211
193 203 224 238 248
231 240 262 275 285
268 277 299 313 322
284 307 336 350 360
284 307 373 387 397
284 307 378 424 434
284 307 378 461 471
284 307 378 470 545
284 307 378 470 608
284 307 378 470 608
284 307 378 470 608
284 307 378 470 608
284 307 378 470 608
Part number GL-E223-ADOC 0614