AQUA PLUS indirect-fired water heatersProduct Manual
Recirculation
(continued)
Components

1. Little flow is required to maintain a temperature
in the piping.
2. Size of circulator depends on minimum flow re-
quirements of the tempering valve.
3. Minimum flow rates of the tempering valve must
be maintained.

1. Used to control the on-off position of the circula-
tor. Aquastat is set 5° to 10° lower than mixed water
outlet of the mixing valve (#7).
2. The circulator cannot run continuously as bypass
through the mixing valve will eventually allow the
temperature on the piping to climb to the water
heater temperature during draw periods.

1. Assure the flow of water in one direction.
2. Each check valve functions as follows:
a. #3 and #4 prevent bypass in the event of pres-
sure drop.
b. #5 prevents thermal siphoning of hot water to
the cold water supply.
c. #6 prevents flow of cold water to the tempered
water supply. A draw of tempered water will
not result in flow of cold water into the return
loop.
Operation
1. During period of normal use (fixtures on) — Cir-
culator is off. There is no flow through #6, there is
flow through #5 equal to the flow at the fixtures,
there is flow through #3 and/or #4 equal to flow
at fixture.
2. When all fixtures are off — Circulator is off. There is
no flow through #3, #4, #5 or #6. Water temperature
in piping is cooling.
3. When temperature at aquastat #2 falls 10° below
temperature to be maintained — Circulator is on.
There is flow through #6 equal to the minimum
required by the mixing valve, flow through #3 and
#4 equals the flow of the circulator. There is no
flow through #5.
4. Aquastat reaches temperature — Circulator is off.
There is no flow through #3, #4, #5 or #6.
 Recirculation piping
Potential problems
1. Missing check valves #3 or #4 — Extreme pressure drop can cause
reverse flow of water; hot to cold supply or cold to hot supply.
2. Missing check valve #5 — Hot water can migrate from the water heater
back through the cold water supply.
3. Missing check valve #6 — Cold water can be forced back through the
tempered water supply when a fixture is opened.
4. No aquastat #2 — Circulator runs continuously. Small amount of
water will pass through mixing valve. Eventually all hot water is flow-
ing through valve. Recirculated water through cold port, hot water
through hot port.
5. Circulator too small — Mixing valve performance erratic.
Part number GL-E223-ADOC 0614
10