AQUA PLUS indirect-fired water heaters — Product Manual
Boiler-side piping
(continued)
Zoning with circulators — primary/secondary system piping
Notes
• Place circulators at begin-
nings of zones. Placing
them at the ends of zones
could result in heating idle
zones.
• Size manifold piping for
total flow of all zone cir-
culators.
• Locate flow / check valves
as close as possible to water
heater boiler side connec-
tions — to reduce heat loss
between cycles.
Wiring
• WMCR zone control-
ler, optional priority —
Figure 18, page 21.
1. This drawing is conceptual
only. It shows representa-
tive piping components
and layout. Weil-McLain
does not represent that this
drawing meets any partic-
ular mechanical or build-
ing codes. The installer is
responsible for inclusion
of all required safety de-
vices, or other miscella-
neous piping hardware not
shown on drawing. The
installer is responsible for
proper sizing / selection of
all hardware shown on this
diagram.
2. See boiler manual for spe-
cific details on installing
the boiler.
Part number GL-E223-ADOC 0614
12
:
apply the drawings in this
manual. Refer only to the boiler
manual.
Recommended ow rate and minimum boiler-side pipe size
Heater
model
GPM
Pipe
size
Heater
model
GPM
Pipe
size
8 1”
14 1¼” *
8 1”
14 1¼” *
8 1”
Requires 1¼”x1” reducers at water heater