7. Electrical work
7.6. Address setting
Switch address setting
Unit
Address
Outdoor
Branch Box
Indoor
Address Connection Setting
Switch
Port A B C D E
ON
OFF 1 2 3 4 5 6
*
ON: Indoor connect
OFF: No connection
None
SWU2 SWU1 SW12 SW11 SW1 *SW1-6 not use
range 51 - 100 1 - 50
setting Branch address + 50
According to the set address (for example, 01), the ad-
dresses for the connected indoor units are set sequentially
(for example, 02, 03, 04, and 05).
Specify whether indoor units are connected to each
port (A, B, C, D, and E).
There are no ad-
dress settings for
the indoor units.
SW1 1 2 3 4 5
ON ON ON ON ON
Port A B C D E
Address 01 (SW11, 12)
02 03 04 05 (sequential numbers)
SW1 1 2 3 4 5 (6)
Port A B C D E (not use)
Indoor units are connected ON
Indoor units are not connected OFF
Note: 1. Branch box address
When setting the address, use a number within the range 1–50.
Ex. The set address is (47) and there are 5 indoor units (A, B, C, D, and E).
If A: (47), B: (48), C: (49), D: (50), and E: (51), E is incorrect because it exceeds 50.
Ex1. Outdoor + Branch <1> (Indoor A, B, C, D, E) + Branch <2> (Indoor A, B, C)
Outdoor
address
(51) *1
*1 Outdoor address
Branch Box <1> start address + 50 = 01 + 50 = 51
*2 Branch Box <1>
A-port address = Start address = 01
B-port address = Start address + 1 = 02
C-port address = Start address + 2 = 03
D-port address = Start address + 3 = 04
E-port address = Start address + 4 = 05
*3 Branch-Box <2>
Branch Box <2> start address
= Branch Box <1> oldest start address + 1
= 05 + 1 = 06
A-port address = Start address = 06
B-port address = Start address + 1 = 07
C-port address = Start address + 2 = 08
Ex2. Outdoor + Branch <1> (Indoor A, C, E) + Branch <2> (Indoor A, C, E)
Outdoor
address
(51) *1
*1 Outdoor address
Branch Box <1> start address + 50 = 01 + 50 = 51
*2 Branch-Box <1>
A-port address = Start address = 01
B-port address no connection
C-port address = Start address + 1 = 02
D-port address no connection
E-port address = Start address + 2 = 03
*3 Branch-Box <2>
Branch Box <2> start address
= Branch Box <1> oldest start address + 1
= 03 + 1 = 04
A-port address = Start address = 04
B-port address no connection
C-port address = Start address + 1 = 05
D-port address no connection
E-port address = Start address + 2 = 06
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
(01) = A-port
(02) = B-port
(03) = C-port
(04) = D-port
(05) = E-port
(06) = A-port
(07) = B-port
(08) = C-port
(01) = A-port
non B-port
(02) = C-port
non D-port
(03) = E-port
(04) = A-port
non B-port
(05) = C-port
non D-port
(06) = E-port
Branch-Box <1>
address (01) *2
SW1 1, 3, 5 ON
SW1 2, 4 OFF
Branch-Box <2>
address (04) *3
SW1 1, 3, 5 ON
SW1 2, 4 OFF
Branch-Box <2>
address (06) *3
SW1 1, 2, 3 ON
SW1 4, 5 OFF
Branch-Box <1>
address (01) *2
SW1 1, 2, 3, 4, 5 ON
RG79D595H06_EN.indd 15 9/7/2016 9:49:59 AM