Installation
24 25
Installation
.
1. Strip the outer jacket of AC output cable by 55 mm
2. Cut the core wires of the cables excluding the PGND cable by 2.5 mm
That is, the core wire of the PGND cable should be 2.5 mm longer than that of
other four cables.
3. Strip the insulation layer of each core wires by 12 mm
Fi gure 3-35 Connecting an AC output power cable (1) (unit: mm)
The preceding figure shows only how to strip cables for the
10KTL to 20KTL
.
Notice
Notice
Step 3 Insert AC output cable (L1, L2, L3, N, and PE) into the cable gland and the adapter,
as shown in Figure 3-36.
If the external cable diameter ranges from16mmto20mm,
removeaseal ring from the cable gland before inserting
the power cable into the cable gland and the adapter.
Figure 3-36 Connecting an AC output power cable (2)
Step 4 Loosen the screws inside the coupling nut holes using a flathead screwdriver,
insert the core wires into corresponding holes, and tighten the screws, as shown
in Figure 3-37.
Tighten the screws to a torque of 0.7 N m.
Figure 3-37 Connecting an AC output power cable (3)
Connect L1 to the hole numbered L1.
Connect L2 to the hole numbered L2.
L1
L2
L3
N
Connect L3 to the hole numbered L3.
Connect N to the hole numbered N.
Connect PE to the hole marked .
Step 5 Check that all core wires are properly connected