20 21
3.6.4.1 Steps for DC connection
Tip
Tip
Tip
Tip
Fig.3-22
Fig.3-23
Steps for DC cable wiring
Installation
DC cable between the inverter and the assembly shall be the
special PV cable. The voltage drop from the terminal box to the
inverter is about 1-2%. It is recommended the inverter is
installed on the assembly support for generation to reduce the
cable cost and the DC loss.
High performance and high quality PV array shall be used. The
open circuit voltage in the serial array must be lower than the
maximum DC input voltage in the PV grid-tied inverter, and the
working voltage of the serial array must comply with the MPPT
voltage of the serial array must comply with the MPPT voltage
in the PV grid-tied inverter.
Protect the LCD panel during wiring;
Protect the LCD panel and other elements from scratch or
damage by cables or tools.
1) Using the striping tool to cut the PV cable, and makes the cooper wire
reveal as 0.7cm.
In order to balance each PV series, Cable shall be with the same
sectional area.
Different colors of cables shall be used for differentiating in
assembling. For example: the positive pole is connected by a red
cable and the negative by a blue cable.
When designing the PV array, make sure the maximum
open circuit voltage is not higher than 1000V at each
series of PV group. Otherwise the inverter will be
damaged irreversibly
2) Insert cable into DC”+” terminal
3) Process crimping.
Fig.3-24 Fig.3-25