Service Manual / Multi-Split Type Air Conditioners MXM-A, MXT-A, MXTH-A Series SiUS122410EA
Multi-Split Type Air Conditioners
MXM-A, MXT-A, MXTH-A Series
[Applied Models]
Inverter Multi : Heat Pump
background
SiUS122410EA
i Table of Contents
Introduction .................................................................................... 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................7
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Part 1 General Information .......................................................... 12
1. Applicable Models .................................................................................13
2. Functions...............................................................................................14
2.1 Indoor Unit..............................................................................................14
2.2 Outdoor Unit ...........................................................................................15
Part 2 Specifications.................................................................... 16
1. Specifications ........................................................................................17
1.1 Indoor Unit..............................................................................................17
1.2 Outdoor Unit ...........................................................................................19
Part 3 Printed Circuit Board Connector Wiring Diagram............. 25
1. Indoor Unit.............................................................................................26
2. Outdoor Unit..........................................................................................28
2.1 2/3/4MXM, 2MXT ...................................................................................28
2.2 5MXM, 3/4/5MXT, 3/4/5MXTH ...............................................................31
Part 4 Functions and Control ....................................................... 33
1. Main Functions......................................................................................34
1.1 Temperature Control ..............................................................................34
1.2 Frequency Principle................................................................................34
1.3 Airflow Direction Control.........................................................................36
1.4 COMFORT AIRFLOW Operation ...........................................................37
1.5 Fan Speed Control for Indoor Unit .........................................................38
1.6 Program Dry Operation ..........................................................................39
1.7 Automatic Cooling/Heating Change-over ...............................................40
1.8 Thermostat Control.................................................................................41
1.9 NIGHT SET Mode ..................................................................................42
1.10 ECONO Operation ................................................................................42
1.11 POWERFUL Operation ..........................................................................43
1.12 Brightness Setting of Indoor Unit Display...............................................44
1.13 Wireless LAN Connection ......................................................................45
1.14 Other Functions......................................................................................49
2. Control Specification .............................................................................50
2.1 Thermistor Functions..............................................................................50
2.2 Mode Hierarchy ......................................................................................52
2.3 Compressor Speed Control....................................................................53
2.4 Controls at Mode Changing/Start-up......................................................55
2.5 Discharge Pipe Temperature Control.....................................................57
2.6 Input Current Control..............................................................................58
2.7 Freeze-up Protection Control .................................................................59
background
SiUS122410EA
Table of Contents ii
2.8 Heating Peak-cut Control .......................................................................60
2.9 High Pressure Protection Control...........................................................61
2.10 Outdoor Fan Control...............................................................................62
2.11 Liquid Compression Protection Function................................................62
2.12 Defrost Control .......................................................................................62
2.13 Low Compressor Speed High Pressure Limit ........................................69
2.14 Electronic Expansion Valve Control .......................................................70
2.15 Malfunctions ...........................................................................................75
Part 5 Remote Controller ............................................................. 76
1. Applicable Remote Controller ...............................................................77
2. ARC480A83 ..........................................................................................78
3. BRC073A6 ............................................................................................80
4. BRC944B2 ............................................................................................84
Part 6 Service Diagnosis .............................................................. 85
1. General Problem Symptoms and Check Items .....................................87
2. Troubleshooting with LED .....................................................................88
2.1 Indoor Unit..............................................................................................88
2.2 Outdoor Unit ...........................................................................................89
3. Service Diagnosis .................................................................................90
3.1 ARC480 Series.......................................................................................90
3.2 BRC073A6 .............................................................................................93
4. Code Indication on Remote Controller ..................................................95
4.1 Indoor Unit..............................................................................................95
4.2 Outdoor Unit ...........................................................................................96
5. Troubleshooting for Indoor Unit.............................................................97
5.1 Indoor Unit PCB Abnormality .................................................................97
5.2 Freeze-up Protection Control/Heating Peak-cut Control ........................98
5.3 Indoor Fan Motor (DC Motor) or Related Abnormality ...........................99
5.4 Indoor Heat Exchanger Thermistor or Related Abnormality.................101
5.5 Room Temperature Sensor Abnormality/Humidity Sensor
Abnormality ..........................................................................................102
5.6 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)....103
5.7 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) .............105
6. Troubleshooting for Outdoor Unit........................................................106
6.1 Refrigerant Shortage ............................................................................106
6.2 Low-voltage Detection or Over-voltage Detection................................109
6.3 Wiring Error Check Unexecuted...........................................................111
6.4 Unspecified Voltage (Between Indoor Unit and Outdoor Unit),
Anti-icing Control in Other Rooms........................................................112
6.5 Anti-icing Control for Indoor Unit ..........................................................113
6.6 Outdoor Unit PCB Abnormality.............................................................115
6.7 Actuation of High Pressure Switch .......................................................116
6.8 OL Activation (Compressor Overload) .................................................117
6.9 Compressor Lock .................................................................................119
6.10 DC Fan Lock ........................................................................................121
6.11 Input Overcurrent Detection .................................................................122
6.12 Electronic Expansion Valve Coil Abnormality.......................................124
6.13 Four Way Valve Abnormality................................................................125
background
SiUS122410EA
iii Table of Contents
6.14 Discharge Pipe Temperature Control...................................................127
6.15 High Pressure Control in Cooling .........................................................128
6.16 System Shutdown due to Temperature Abnormality in the
Compressor..........................................................................................130
6.17 Compressor Sensor System Abnormality ............................................131
6.18 High Pressure Switch System Abnormality ..........................................133
6.19 Position Sensor Abnormality ................................................................134
6.20 Thermistor or Related Abnormality (Outdoor Unit)...............................136
6.21 High Pressure Sensor Abnormality ......................................................138
6.22 Electrical Box Temperature Rise..........................................................139
6.23 Radiation Fin Temperature Rise ..........................................................141
6.24 Output Overcurrent Detection ..............................................................143
7. Check ..................................................................................................146
7.1 Thermistor Resistance Check ..............................................................146
7.2 Indoor Fan Motor Connector Check .....................................................147
7.3 Power Supply Waveform Check...........................................................147
7.4 Electronic Expansion Valve Check.......................................................148
7.5 Four Way Valve Performance Check ...................................................149
7.6 Inverter Unit Refrigerant System Check...............................................149
7.7 Inverter Analyzer Check .......................................................................150
7.8 Outdoor Fan Motor Check....................................................................151
7.9 Installation Condition Check.................................................................152
7.10 Discharge Pressure Check...................................................................152
7.11 Outdoor Fan System Check .................................................................153
7.12 Main Circuit Short Check......................................................................153
7.13 Capacitor Voltage Check......................................................................155
7.14 Power Module Check ...........................................................................156
7.15 High Pressure Sensor Check ...............................................................158
Part 7 Trial Operation and Field Settings .................................. 159
1. Pump Down Operation........................................................................160
2. Forced Cooling Operation ...................................................................161
3. Wiring Error Check Function ...............................................................162
4. Trial Operation ....................................................................................164
5. Field Settings ......................................................................................166
5.1 Indoor Unit............................................................................................166
5.2 Outdoor Unit .........................................................................................172
6. Silicone Grease on Power Transistor/Diode Bridge............................175
Part 8 Appendix .......................................................................... 176
1. Piping Diagrams..................................................................................177
1.1 Indoor Unit............................................................................................177
1.2 Outdoor Unit .........................................................................................178
2. Wiring Diagrams..................................................................................182
2.1 Indoor Unit............................................................................................182
2.2 Outdoor Unit .........................................................................................184
3. Operation Limit....................................................................................194
background
SiUS122410EA
Introduction 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................7
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Introduction
background
Safety Cautions SiUS122410EA
2 Introduction
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown in the illustration or near the symbol.
1.1 Warnings and Cautions Regarding Safety of Workers
This manual is for the
person in charge of
maintenance and
inspection.
This appliance is
filled with R-32.
Refrigerant
Safety
Group A2L
Warning
Do not store equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to disconnect the power cable from the socket before
disassembling equipment for repair.
Working on equipment that is connected to the power supply may cause
an electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspect the circuits, do not touch any electrically charged sections of the
equipment.
If refrigerant gas is discharged during repair work, do not touch the
discharged refrigerant gas.
Refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the
compressor at the welded section, evacuate the refrigerant gas
completely at a well-ventilated place first.
If there is gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it
may cause injury.
If refrigerant gas leaks during repair work, ventilate the area.
Refrigerant gas may generate toxic gases when it contacts flames.
Be sure to discharge the capacitor completely before conducting
repair work.
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
A charged capacitor may cause an electrical shock.
background
SiUS122410EA Safety Cautions
Introduction 3
Do not turn the air conditioner on or off by plugging in or
unplugging the power cable.
Plugging in or unplugging the power cable to operate the equipment may
cause an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when
working in a high place (more than 2 m (6.5 ft)).
Insufficient safety measures may cause a fall.
In case of R-32 / R-410A refrigerant models, be sure to use pipes,
flare nuts and tools intended for the exclusive use with the R-32 /
R-410A refrigerant.
The use of materials for R-22 refrigerant models may cause a serious
accident, such as a damage of refrigerant cycle or equipment failure.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner with water.
Washing the unit with water may cause an electrical shock.
Be sure to provide an earth / grounding when repairing the
equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools.
The use of inappropriate tools may cause injury.
Be sure to check that the refrigerating cycle section has cooled
down enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
Conduct welding work in a well-ventilated place.
Using the welder in an enclosed room may cause oxygen deficiency.
Warning
background
Safety Cautions SiUS122410EA
4 Introduction
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating
system, provisions under Work procedure to No ignition sources below shall be
completed prior to conducting work on the system.
Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a
flammable gas or vapor being present while the work is being performed.
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of
work being carried out. Work in confined spaces shall be avoided.
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work,
to ensure the technician is aware of potentially toxic or flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with all applicable
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or
CO
2
fire extinguisher adjacent to the charging area.
No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing
any pipe work shall use any sources of ignition in such a manner that it may lead to the risk
of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and disposal, during
which refrigerant can possibly be released to the surrounding space. Prior to work taking
place, the area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period
that the work is carried out. The ventilation should safely disperse any released refrigerant
and preferably expel it externally into the atmosphere.
Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification.
At all times the manufacturer’s maintenance and service guidelines shall be followed. If in
doubt, consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
The actual refrigerant charge is in accordance with the room size within which the
refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for
the presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
Refrigerating pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless
the components are constructed of materials which are inherently resistant to being
corroded or are suitably protected against being so corroded.
background
SiUS122410EA Safety Cautions
Introduction 5
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault
cannot be corrected immediately but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be reported to the owner of the equipment so all
parties are advised.
Initial safety checks shall include:
that capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
that no live electrical components and wiring are exposed while charging, recovering or
purging the system;
that there is continuity of earth bonding.
Repairs to sealed components
Sealed electrical components shall be replaced.
Repair to intrinsically safe components
Intrinsically safe components must be replaced.
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual vibration from sources such as compressors or
fans.
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall
not be used.
The following leak detection methods are deemed acceptable for all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of
flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration.
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant
used. Leak detection equipment shall be set at a percentage of the LFL (lower flammability
limit) of the refrigerant and shall be calibrated to the refrigerant employed, and the
appropriate percentage of gas (25% maximum) is confirmed.
Leak detection fluids are also suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant
and corrode the copper pipe-work.
Note: Examples of leak detection fluids are
bubble method,
fluorescent method agents.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the system
remote from the leak. Removal of refrigerant shall be according to the following clause,
Removal and evacuation.
Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, for flammable refrigerants it is important
that best practice be followed, since flammability is a consideration. The following procedure
shall be adhered to:
safely remove refrigerant following local and national regulations;
evacuate;
purge the circuit with inert gas (optional for A2L);
evacuate (optional for A2L);
background
Safety Cautions SiUS122410EA
6 Introduction
continuously flush or purge with inert gas when using flame to open circuit;
open the circuit.
The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not
allowed by local and national codes. For appliances containing flammable refrigerants, the
system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable
refrigerants. This process might need to be repeated several times. Compressed air or
oxygen shall not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, refrigerants purging shall be achieved by
breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the
working pressure is achieved, then venting to atmosphere, and finally pulling down to a
vacuum (optional for A2L). This process shall be repeated until no refrigerant is within the
system (optional for A2L). When the final oxygen-free nitrogen charge is used, the system
shall be vented down to atmospheric pressure to enable work to take place.
The outlet for the vacuum pump shall not be close to any potential ignition sources, and
ventilation shall be available.
Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant
contained in them.
Cylinders shall be kept in an appropriate position according to the instructions.
Ensure that the refrigerating system is earthed prior to charging the system with
refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigerating system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging
gas.
The system shall be leak-tested on completion of charging but prior to commissioning.
A follow up leak test shall be carried out prior to leaving the site.
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that
electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
mechanical handling equipment is available, if required, for handling refrigerant
cylinders;
all personal protective equipment is available and being used correctly;
the recovery process is supervised at all times by a competent person;
recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from
various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not overfill cylinders (no more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that
the cylinders and the equipment are removed from site promptly and all isolation valves on
the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigerating system unless it has
been cleaned and checked.
background
SiUS122410EA Safety Cautions
Introduction 7
Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. For appliances containing flammable
refrigerants, ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders for holding the total
system charge is available. All cylinders to be used are designated for the recovered
refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, if possible,
cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning
the equipment that is at hand and shall be suitable for the recovery of the flammable
refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be complete with
leak-free disconnect couplings and in good condition.
The recovered refrigerant shall be processed according to local legislation in the correct
recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in
recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated
to an acceptable level to make certain that flammable refrigerant does not remain within the
lubricant. The compressor body shall not be heated by an open flame or other ignition
sources to accelerate this process. When oil is drained from a system, it shall be carried out
safely.
1.2 Warnings and Cautions Regarding Safety of Users
Warning
Do not store the equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to use parts listed in the service parts list of the applicable
model and appropriate tools to conduct repair work. Never attempt
to modify the equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated,
be sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the
same power outlet with other electrical appliances, since it may
cause an electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and
follow the local technical standards related to the electrical
equipment, the internal wiring regulations, and the instruction
manual for installation when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause
an electrical shock or fire.
background
Safety Cautions SiUS122410EA
8 Introduction
Be sure to use the specified cable for wiring between the indoor and
outdoor units.
Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that
the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may
cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cables may cause an electrical shock or fire.
Placing heavy items on the power cable, or heating or pulling the power
cable may damage it.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R- 22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and
repair it before charging the refrigerant. After charging the
refrigerant, make sure that there is no leak.
If the leaking point cannot be located and the repair work must be
stopped, be sure to pump-down, and close the service valve, to prevent
refrigerant gas from leaking into the room. Refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such
as those from fan type and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation
site has sufficient strength to withstand the weight of the
equipment.
If the installation site does not have sufficient strength or the installation
work is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose,
then insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical
shock or fire.
When replacing the coin battery in the remote controller, be sure to
dispose of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases
depending on the conditions of the installation site, to prevent
electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if parts and wires are mounted and connected
properly, and if connections at the soldered or crimped terminals
are secure.
Improper installation and connections may cause excessive heat
generation, fire or an electrical shock.
Warning
background
SiUS122410EA Safety Cautions
Introduction 9
If the installation platform or frame has corroded, replace it.
A corroded installation platform or frame may cause the unit to fall,
resulting in injury.
Check the earth / grounding, and repair it if the equipment is not
properly earthed / grounded.
Improper earth / grounding may cause an electrical shock.
Be sure to measure insulation resistance after the repair, and make
sure that the resistance is 1 M or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture
and floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
Caution
background
Icons Used SiUS122410EA
10 Introduction
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
Icon Type of
Information
Description
Warning
Warning Warning is used when there is danger of personal injury.
Caution
Caution Caution is used when there is danger that the reader,
through incorrect manipulation, may damage equipment,
lose data, get an unexpected result or have to restart (part
of) a procedure.
Note
Note Note provides information that is not indispensable, but
may nevertheless be valuable to the reader, such as tips
and tricks.
Reference
Reference Reference guides the reader to other places in this binder
or in this manual, where he/she will find additional
information on a specific topic.
background
SiUS122410EA Revision History
Introduction 11
3. Revision History
Month/Year Version Revised contents
09 / 2024 SiUS122410E First edition
10 / 2025 SiUS122410EA
Model addition: 5MXM48AVJU9, 3MXT24AVJU9, 4MXT36AVJU9, 5MXT40AVJU9,
3MXTH24AVJU9, 4MXTH36AVJU9, 5MXTH40AVJU9
background
SiUS122410EA
12 Part 1 General Information
1. Applicable Models .................................................................................13
2. Functions...............................................................................................14
2.1 Indoor Unit..............................................................................................14
2.2 Outdoor Unit ...........................................................................................15
Part 1
General Information
background
SiUS122410EA Applicable Models
Part 1 General Information 13
1. Applicable Models
Indoor Unit
Outdoor Unit
CTXV07AVJU9
FTXV09AVJU9
FTXV12AVJU9
FTXV15AVJU9
FTXV18AVJU9
FTXV24AVJU9
Standard type Cold climate type
2MXM18AVJU9
3MXM24AVJU9
4MXM36AVJU9
5MXM48AVJU9
2MXT18AVJU9
3MXT24AVJU9
4MXT36AVJU9
5MXT40AVJU9
2MXTH18AVJU9 (with drain pan heater)
3MXTH24AVJU9 (with drain pan heater)
4MXTH36AVJU9 (with drain pan heater)
5MXTH40AVJU9 (with drain pan heater)
background
Functions SiUS122410EA
14 Part 1 General Information
2. Functions
2.1 Indoor Unit
Category Functions
CTXV07AVJU9
FTXV09/12AVJU9
FTXV15/18/24AVJU9
Basic Function Inverter (with inverter power control)
Comfortable
Airflow
Power-airflow flap (horizontal blade) —
Power-airflow dual flaps (horizontal blade) —
Wide-angle louvers (vertical blades)
Auto-swing (up and down)
Auto-swing (left and right) — —
3-D airflow — —
COMFORT AIRFLOW operation
Comfort Control Auto fan speed
Switchable fan speed
Indoor unit quiet operation
INTELLIGENT EYE operation — —
2-area INTELLIGENT EYE operation — —
Hot-start function
Operation Automatic cooling/heating change-over
Program dry operation
Fan only
Lifestyle
Convenience
POWERFUL operation (inverter)
ECONO operation
Indoor unit ON/OFF switch
Multi-colored indicator lamp — —
Monitor brightness setting — —
Signal receiving sign
R/C with back light
Health and
Cleanliness
Titanium apatite deodorizing filter
Mold proof air filter
Wipe-clean flat panel
Washable grille — —
Timer WEEKLY TIMER operation — —
24-hour ON/OFF TIMER — —
Count up-down ON/OFF timer
NIGHT SET mode
Worry Free
(Reliability &
Durability)
Auto-restart (after power failure)
Self-diagnosis (R/C, LED)
Flexibility Multi-split/split type compatible indoor unit
Either side drain (left or right)
°F/°C changeover R/C temperature display
(factory setting: °F)
Remote Control Remote control adaptor (normal open pulse contact) Option Option
Remote control adaptor (normal open contact) Option Option
DIII-NET compatible (adaptor) Option Option
Wireless LAN connection
Remote
Controller
Wireless
Wired Option Option
—
: Available
: Not available
background
SiUS122410EA Functions
Part 1 General Information 15
2.2 Outdoor Unit
Function
Standard Cold Climate
2MXM 3/4/5MXM 2MXT 3/4/5MXT 2MXTH 3/4/5MXTH
Inverter (with inverter power control)
Operation limit Refer to P. 194
PAM control
Standby electricity saving — — — — — —
Swing compressor
Reluctance DC motor
NIGHT QUIET mode
QUIET OUTDOOR UNIT operation
Quick warming function — — — — — —
Automatic defrosting
Defrost learning control — — — — — —
Priority room setting
COOL/HEAT mode lock
Self-diagnosis (R/C, LED)
Wiring error check function
Anti-corrosion treatment of outdoor heat
exchanger
Drain pan heater Option Option Option Option
Drain pan heater control by
microcomputer
Chargeless 98.4 ft
(30 m)
131.2 ft
(40 m)
98.4 ft
(30 m)
131.2 ft
(40 m)
98.4 ft
(30 m)
131.2 ft
(40 m)
Low temp. cooling operation (−15°C) (5°F) — — — — — —
—
: Available
: Not available
background
SiUS122410EA
16 Part 2 Specifications
1. Specifications ........................................................................................17
1.1 Indoor Unit..............................................................................................17
1.2 Outdoor Unit ...........................................................................................19
Part 2
Specifications
background
SiUS122410EA Specifications
Part 2 Specifications 17
1. Specifications
1.1 Indoor Unit
Model CTXV07AVJU9 FTXV09AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
Rated Capacity 7 kBtu/h Class 9 kBtu/h Class
Front Panel Color (Munsell No.) White (N9.5) White (N9.5)
Airflow Rates H
cfm
(m³/min)
332 (9.4) 332 (9.4) 381 (10.8) 385 (10.9)
M 268 (7.6) 279 (7.9) 272 (7.7) 304 (8.6)
L 230 (6.5) 230 (6.5) 230 (6.5) 230 (6.5)
SL 166 (4.7) 194 (5.5) 166 (4.7) 194 (5.5)
Fan Type Cross Flow Fan Cross Flow Fan
Drive Input A 0.20 0.20
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward
Air Filter Removable, Washable Removable, Washable
Running Current (Rated) A 0.11 - 0.10 0.12 - 0.11 0.14 - 0.13 0.13 - 0.12
Power Consumption (Rated) W 20 - 20 23 - 23 26 - 26 25 - 25
Power Factor (Rated) % 87.0 - 90.3 94.0 - 91.3 90.4 - 86.2 90.9 - 87.3
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) in. (mm) 11-1/4 × 30-5/16 × 8-3/4 (286 × 770 × 223) 11-1/4 × 30-5/16 × 8-3/4 (286 × 770 × 223)
Packaged Dimensions (H × W × D) in. (mm) 12-5/18 × 32-11/16 × 14-3/16 (320 × 830 × 360) 12-5/8 × 32-11/16 × 14-3/16 (320 × 830 × 360)
Weight (Mass) lbs (kg) 19 (9) 19 (9)
Gross Weight (Gross Mass) lbs (kg) 24 (11) 24 (11)
Sound Pressure Level H / M / L / SL dB(A) 40 / 35 / 31 / 24 39 / 34 / 28 / 25 43 / 35 / 31 / 24 41 / 35 / 28 / 25
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection Liquid in. (mm) 1/4 ( 6.4) 1/4 ( 6.4)
Gas in. (mm) 3/8 ( 9.5) 3/8 ( 9.5)
Drain in. (mm) 5/8 ( 16) 5/8 ( 16)
Drawing No. 3D153215A 3D153215A
Note SL: The quiet fan level of the airflow rate setting. SL: The quiet fan level of the airflow rate setting.
Model FTXV12AVJU9 FTXV15AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
Rated Capacity 12 kBtu/h Class 15 kBtu/h Class
Front Panel Color (Munsell No.) White (N9.5) White (N9.5)
Airflow Rates H
cfm
(m³/min)
392 (11.1) 438 (12.4) 540 (15.3) 636 (18.0)
M 293 (8.3) 318 (9.0) 470 (13.3) 537 (15.2)
L 226 (6.4) 240 (6.8) 381 (10.8) 452 (12.8)
SL 166 (4.7) 205 (5.8) 339 (9.6) 388 (11.0)
Fan Type Cross Flow Fan Cross Flow Fan
Drive Input A 0.23 0.31
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward
Air Filter Removable, Washable Removable, Washable
Running Current (Rated) A 0.17 - 0.15 0.20 - 0.18 0.19 - 0.17 0.20 - 0.18
Power Consumption (Rated) W 29 - 29 35 - 35 36 - 36 39 - 39
Power Factor (Rated) % 81.3 - 84.7 83.7 - 82.7 91.1 - 93.5 93.8 - 92.3
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) in. (mm) 11-1/4 × 30-5/16 × 8-3/4 (286 × 770 × 223) 11-5/8 × 39 × 10-3/8 (295 × 990 × 263)
Packaged Dimensions (H × W × D) in. (mm) 12-5/8 × 32-11/16 × 14-3/16 (320 × 830 × 360) 15-3/16 × 43-3/8 × 15-5/16 (386 × 1,102 × 389)
Weight (Mass) lbs (kg) 19 (9) 27 (13)
Gross Weight (Gross Mass) lbs (kg) 24 (11) 37 (17)
Sound Pressure Level H / M / L / SL dB(A) 45 / 37 / 31 / 24 45 / 37 / 30 / 26 45 / 41 / 36 / 33 45 / 41 / 37 / 33
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection Liquid in. (mm) 1/4 ( 6.4) 1/4 ( 6.4)
Gas in. (mm) 3/8 ( 9.5) 1/2 ( 12.7)
Drain in. (mm) 5/8 ( 16) 5/8 ( 16)
Drawing No. 3D153215A 3D153178A
Note SL: The quiet fan level of the airflow rate setting. SL: The quiet fan level of the airflow rate setting.
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
Specifications SiUS122410EA
18 Part 2 Specifications
Model FTXV18AVJU9 FTXV24AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
Rated Capacity 18 kBtu/h Class 24 kBtu/h Class
Front Panel Color (Munsell No.) White (N9.5) White (N9.5)
Airflow Rates H
cfm
(m³/min)
565 (16.0) 717 (20.3) 629 (17.8) 717 (20.3)
M 463 (13.1) 572 (16.2) 501 (14.2) 572 (16.2)
L 378 (10.7) 452 (12.8) 378 (10.7) 466 (13.2)
SL 335 (9.5) 388 (11.0) 335 (9.5) 413 (11.7)
Fan Type Cross Flow Fan Cross Flow Fan
Drive Input A 0.40 0.45
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward
Air Filter Removable, Washable Removable, Washable
Running Current (Rated) A 0.20 - 0.18 0.29 - 0.26 0.31 - 0.28 0.30 - 0.27
Power Consumption (Rated) W 39 - 39 54 - 54 57 - 57 55 - 55
Power Factor (Rated) % 93.8 - 92.5 89.5 - 89.3 88.4 - 88.7 88.1 - 89.3
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H × W × D) in. (mm) 11-5/8 × 39 × 10-3/8 (295 × 990 × 263) 11-5/8 × 39 × 10-3/8 (295 × 990 × 263)
Packaged Dimensions (H × W × D) in. (mm) 15-3/16 × 43-3/8 × 15-5/16 (386 × 1,102 × 389) 15-3/16 × 43-3/8 × 15-5/16 (386 × 1,102 × 389)
Weight (Mass) lbs (kg) 27 (13) 27 (13)
Gross Weight (Gross Mass) lbs (kg) 37 (17) 37 (17)
Sound Pressure Level H / M / L / SL dB(A) 48 / 43 / 38 / 33 49 / 42 / 37 / 33 52 / 45 / 39 / 34 49 / 43 / 38 / 34
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection Liquid in. (mm) 1/4 ( 6.4) 1/4 ( 6.4)
Gas in. (mm) 1/2 ( 12.7) 5/8 ( 15.9)
Drain in. (mm) 5/8 ( 16) 5/8 ( 16)
Drawing No. 3D153178A 3D153178A
Note SL: The quiet fan level of the airflow rate setting. SL: The quiet fan level of the airflow rate setting.
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
SiUS122410EA Specifications
Part 2 Specifications 19
1.2 Outdoor Unit
1.2.1 Standard Type
Model 2MXM18AVJU9 3MXM24AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
COP@5°F W/W — 1.8 — 1.8
EER2 Btu/W·h 12.0 — 12.0 —
SEER2 21.0 — 21.0 —
HSPF2 — 10.0 — 10.0
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y147BKBX1A 2Y260BPAX1A
Motor Output W 1,300 2,400
Refrigerant
Oil
Model FW68DA FW68DA
Charge fl oz (L) 22.0 (0.65) 30.4 (0.9)
Refrigerant Type R-32 R-32
Charge lbs (kg) 3.3 (1.50) 4.9 (2.2)
Airflow Rates cfm 2,112 2,140 2,055 2,140
m³/min 59.8 60.6 58.2 60.6
Fan Type Propeller Propeller
Motor Output W 150 150
Running Current A 0.31 0.33 0.29 0.33
Power Consumption W 65.4 67.7 61.0 67.7
Starting Current A 14.0 17.0
Dimensions (H × W × D) in. (mm) 29-1/2 × 34-1/4 × 12-5/8 (750 × 870 × 320) 29-1/2 × 34-1/4 × 12-5/8 (750 × 870 × 320)
Packaged Dimensions (H × W × D) in. (mm) 32-1/16 × 40-5/16 × 16 (814 × 1,024 × 406) 32-1/16 × 40-5/16 × 16 (814 × 1,024 × 406)
Weight (Mass) lbs (kg) 127 (58) 140 (64)
Gross Weight (Gross Mass) lbs (kg) 135 (61) 148 (67)
Sound Pressure Level dB(A) 52 54 52 54
Piping
Connection
Liquid in. (mm) 1/4 × 2 ( 6.4 × 2) 1/4 × 3 ( 6.4 × 3)
Gas in. (mm) 3/8 × 1, 1/2 × 1 ( 9.5 × 1, 12.7 × 1) 3/8 × 1, 1/2 × 2 ( 9.5 × 1, 12.7 × 2)
Drain in. (mm) I.D. 5/8 ( 15.9) I.D. 5/8 ( 15.9)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
Max. Interunit Piping Length ft (m) 164 (50) (for Total of Each Room) 230 (70) (for Total of Each Room)
ft (m) 82 (25) (for One Room) 82 (25) (for One Room)
Amount of Additional Charge oz/ft
(g/m)
0.22 (20) (98-3/8 ft (30 m) or more) 0.22 (20) (131-1/4 ft (40 m) or more)
Max. Installation Height Difference ft (m) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit)
ft (m) 24-5/8 (7.5) (Between Indoor Units) 24-5/8 (7.5) (Between Indoor Units)
Conditions based on Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Piping length: 25 ft (7.5 m) Piping length: 25 ft (7.5 m)
Drawing No. C: 3D151521A C: 3D152057A
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
Specifications SiUS122410EA
20 Part 2 Specifications
Model 4MXM36AVJU9 5MXM48AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
COP@5°F W/W — 1.8 — 1.9
EER2 Btu/W·h 10.0 — 10.0 —
SEER2 21.0 — 20.0 —
HSPF2 — 9.5 — 9.5
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y260BPAX1A 2Y350BPCX2A
Motor Output W 2,400 3,300
Refrigerant
Oil
Model FW68DA FW68DE
Charge fl oz (L) 30.4 (0.9) 51.4 (1.52)
Refrigerant Type R-32 R-32
Charge lbs (kg) 4.9 (2.2) 6.94 (3.15)
Airflow Rates cfm 2,402 2,518 3,137 3,137
m³/min 68.0 71.3 88.7 88.7
Fan Type Propeller Propeller
Motor Output W 150 192
Running Current A 0.44 0.49 0.48 0.48
Power Consumption W 90.9 102.7 99.5 99.5
Starting Current A 18.5 27.0
Dimensions (H × W × D) in. (mm) 29-1/2 × 34-1/4 × 12-5/8 (750 × 870 × 320) 34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460)
Packaged Dimensions (H × W × D) in. (mm) 32-1/16 × 40-5/16 × 16 (814 × 1,024 × 406) 39-15/16 × 46-7/8 × 21-15/16 (1,014 × 1,190 × 558)
Weight (Mass) lbs (kg) 142 (65) 219 (100)
Gross Weight (Gross Mass) lbs (kg) 150 (68) 238 (108)
Sound Pressure Level dB(A) 56 60 55 57
Piping
Connection
Liquid in. (mm) 1/4 × 4 ( 6.4 × 4) 1/4 × 5 ( 6.4 × 5)
Gas
in. (mm)
3/8 × 1, 1/2 × 2, 5/8 × 1
( 9.5 × 1, 12.7 × 2, 15.9 × 1)
3/8 × 1, 1/2 × 2, 5/8 × 2
( 9.5 × 1, 12.7 × 2, 15.9 × 2)
Drain in. (mm) I.D. 5/8 ( 15.9) I.D. 1 ( 25)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
Max. Interunit Piping Length ft (m) 230 (70) (for Total of Each Room) 262 (80) (for Total of Each Room)
ft (m) 82 (25) (for One Room) 98 (30) (for One Room)
Amount of Additional Charge oz/ft
(g/m)
0.22 (20) (131-1/4 ft (40 m) or more) 0.22 (20) (131-1/4 ft (40 m) or more)
Max. Installation Height Difference ft (m) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit)
ft (m) 24-5/8 (7.5) (Between Indoor Units) 24-5/8 (7.5) (Between Indoor Units)
Conditions based on Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Piping length: 25 ft (7.5 m) Piping length: 25 ft (7.5 m)
Drawing No. C: 3D151522A C: 3D158480
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
SiUS122410EA Specifications
Part 2 Specifications 21
1.2.2 Cold Climate Type
Model 2MXT18AVJU9 2MXTH18AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
COP@5°F W/W — 1.8 — 1.8
EER2 Btu/W·h 12.0 — 12.0 —
SEER2 21.0 — 21.0 —
HSPF2 — 10.0 — 10.0
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y260BPAX1A 2Y260BPAX1A
Motor Output W 2,400 2,400
Refrigerant
Oil
Model FW68DA FW68DA
Charge fl oz (L) 30.4 (0.9) 30.4 (0.9)
Refrigerant Type R-32 R-32
Charge lbs (kg) 4.9 (2.2) 4.9 (2.2)
Airflow Rates cfm 2,112 2,140 2,112 2,140
m³/min 59.8 60.6 59.8 60.6
Fan Type Propeller Propeller
Motor Output W 150 150
Running Current A 0.31 0.33 0.31 0.33
Power Consumption W 65.4 67.7 65.4 67.7
Starting Current A 17.0 17.0
Dimensions (H × W × D) in. (mm) 29-1/2 × 34-1/4 × 12-5/8 (750 × 870 × 320) 29-1/2 × 34-1/4 × 12-5/8 (750 × 870 × 320)
Packaged Dimensions (H × W × D) in. (mm) 32-1/16 × 40-5/16 × 16 (814 × 1,024 × 406) 32-1/16 × 40-5/16 × 16 (814 × 1,024 × 406)
Weight (Mass) lbs (kg) 139 (63) 140 (64)
Gross Weight (Gross Mass) lbs (kg) 147 (67) 148 (67)
Sound Pressure Level dB(A) 52 54 52 54
Piping
Connection
Liquid in. (mm) 1/4 × 2 ( 6.4 × 2) 1/4 × 2 ( 6.4 × 2)
Gas in. (mm) 3/8 × 1, 1/2 × 1 ( 9.5 × 1, 12.7 × 1) 3/8 × 1, 1/2 × 1 ( 9.5 × 1, 12.7 × 1)
Drain in. (mm) I.D. 5/8 ( 15.9) I.D. 5/8 ( 15.9)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
Max. Interunit Piping Length ft (m) 164 (50) (for Total of Each Room) 164 (50) (for Total of Each Room)
ft (m) 82 (25) (for One Room) 82 (25) (for One Room)
Amount of Additional Charge oz/ft
(g/m)
0.22 (20) (98-3/8 ft (30m) or more) 0.22 (20) (98-3/8 ft (30m) or more)
Max. Installation Height Difference ft (m) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit)
ft (m) 24-5/8 (7.5) (Between Indoor Units) 24-5/8 (7.5) (Between Indoor Units)
Conditions based on Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Piping length: 25 ft (7.5 m) Piping length: 25 ft (7.5 m)
Drawing No. C: 3D152058A C: 3D151523A
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
Specifications SiUS122410EA
22 Part 2 Specifications
Model 3MXT24AVJU9 3MXTH24AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
COP@5°F W/W — 1.9 — 1.8
EER2 Btu/W·h 12.5 — 12.5 —
SEER2 19.0 — 19.0 —
HSPF2 — 9.5 — 9.5
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y350BPCX2A 2Y350BPCX2A
Motor Output W 3,300 3,300
Refrigerant
Oil
Model FW68DE FW68DE
Charge fl oz (L) 51.4 (1.52) 51.4 (1.52)
Refrigerant Type R-32 R-32
Charge lbs (kg) 6.94 (3.15) 6.94 (3.15)
Airflow Rates cfm 3,137 3,137 3,137 3,137
m³/min 88.7 88.7 88.7 88.7
Fan Type Propeller Propeller
Motor Output W 192 192
Running Current A 0.48 0.48 0.48 0.48
Power Consumption W 99.5 99.5 99.5 99.5
Starting Current A 25.0 25.0
Dimensions (H × W × D) in. (mm) 34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460) 34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460)
Packaged Dimensions (H × W × D) in. (mm) 39-15/16 × 46-7/8 × 21-15/16 (1,014 × 1,190 × 558) 39-15/16 × 46-7/8 × 21-15/16 (1,014 × 1,190 × 558)
Weight (Mass) lbs (kg) 213 (97) 215 (97)
Gross Weight (Gross Mass) lbs (kg) 231 (105) 233 (106)
Sound Pressure Level dB(A) 55 57 55 57
Piping
Connection
Liquid in. (mm) 1/4 × 3 ( 6.4 × 3) 1/4 × 3 ( 6.4 × 3)
Gas in. (mm) 3/8 × 1, 1/2 × 2 ( 9.5 × 1, 12.7 × 2) 3/8 × 1, 1/2 × 2 ( 9.5 × 1, 12.7 × 2)
Drain in. (mm) I.D. 1 ( 25) I.D. 1 ( 25)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
Max. Interunit Piping Length ft (m) 230 (70) (for Total of Each Room) 230 (70) (for Total of Each Room)
ft (m) 82 (25) (for One Room) 82 (25) (for One Room)
Amount of Additional Charge oz/ft
(g/m)
0.22 (20) (131-1/4 ft (40 m) or more) 0.22 (20) (131-1/4 ft (40 m) or more)
Max. Installation Height Difference ft (m) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit)
ft (m) 24-5/8 (7.5) (Between Indoor Units) 24-5/8 (7.5) (Between Indoor Units)
Conditions based on Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Piping length: 25 ft (7.5 m) Piping length: 25 ft (7.5 m)
Drawing No. C: 3D158476 C: 3D158477
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
SiUS122410EA Specifications
Part 2 Specifications 23
Model 4MXT36AVJU9 4MXTH36AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
COP@5°F W/W — 1.9 — 1.9
EER2 Btu/W·h 12.0 — 12.0 —
SEER2 20.0 — 20.0 —
HSPF2 — 9.5 — 9.5
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y350BPCX2A 2Y350BPCX2A
Motor Output W 3,300 3,300
Refrigerant
Oil
Model FW68DE FW68DE
Charge fl oz (L) 51.4 (1.52) 51.4 (1.52)
Refrigerant Type R-32 R-32
Charge lbs (kg) 6.94 (3.15) 6.94 (3.15)
Airflow Rates cfm 3,137 3,137 3,137 3,137
m³/min 88.7 88.7 88.7 88.7
Fan Type Propeller Propeller
Motor Output W 192 192
Running Current A 0.48 0.48 0.48 0.48
Power Consumption W 99.5 99.5 99.5 99.5
Starting Current A 27.0 27.0
Dimensions (H × W × D) in. (mm) 34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460) 34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460)
Packaged Dimensions (H × W × D) in. (mm) 39-15/16 × 46-7/8 × 21-15/16 (1,014 × 1,190 × 558) 39-15/16 × 46-7/8 × 21-15/16 (1,014 × 1,190 × 558)
Weight (Mass) lbs (kg) 216 (98) 218 (99)
Gross Weight (Gross Mass) lbs (kg) 234 (106) 236 (107)
Sound Pressure Level dB(A) 55 57 55 57
Piping
Connection
Liquid in. (mm) 1/4 × 4 ( 6.4 × 4) 1/4 × 4 ( 6.4 × 4)
Gas
in. (mm)
3/8 × 1, 1/2 × 2, 5/8 × 1
( 9.5 × 1, 12.7 × 2, 15.9 × 1)
3/8 × 1, 1/2 × 2, 5/8 × 1
( 9.5 × 1, 12.7 × 2, 15.9 × 1)
Drain in. (mm) I.D. 1 ( 25) I.D. 1 ( 25)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
Max. Interunit Piping Length ft (m) 230 (70) (for Total of Each Room) 230 (70) (for Total of Each Room)
ft (m) 98 (30) (for One Room) 98 (30) (for One Room)
Amount of Additional Charge oz/ft
(g/m)
0.22 (20) (131-1/4 ft (40 m) or more) 0.22 (20) (131-1/4 ft (40 m) or more)
Max. Installation Height Difference ft (m) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit)
ft (m) 24-5/8 (7.5) (Between Indoor Units) 24-5/8 (7.5) (Between Indoor Units)
Conditions based on Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Piping length: 25 ft (7.5 m) Piping length: 25 ft (7.5 m)
Drawing No. C: 3D158478 C: 3D158479
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
Specifications SiUS122410EA
24 Part 2 Specifications
Model 5MXT40AVJU9 5MXTH40AVJU9
Cooling Heating Cooling Heating
Power Supply Phase 1 1
Hz, V 60 Hz, 208 - 230 V 60 Hz, 208 - 230 V
COP@5°F W/W — 1.9 — 1.9
EER2 Btu/W·h 11.7 — 11.7 —
SEER2 20.0 — 20.0 —
HSPF2 — 9.5 — 9.5
Casing Color Ivory White Ivory White
Compressor Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2Y350BPCX2A 2Y350BPCX2A
Motor Output W 3,300 3,300
Refrigerant
Oil
Model FW68DE FW68DE
Charge fl oz (L) 51.4 (1.52) 51.4 (1.52)
Refrigerant Type R-32 R-32
Charge lbs (kg) 6.94 (3.15) 6.94 (3.15)
Airflow Rates cfm 3,137 3,137 3,137 3,137
m³/min 88.7 88.7 88.7 88.7
Fan Type Propeller Propeller
Motor Output W 192 192
Running Current A 0.48 0.48 0.48 0.48
Power Consumption W 99.5 99.5 99.5 99.5
Starting Current A 27.0 27.0
Dimensions (H × W × D) in. (mm) 34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460) 34-1/4 × 43-5/16 × 18-1/8 (870 × 1,100 × 460)
Packaged Dimensions (H × W × D) in. (mm) 39-15/16 × 46-7/8 × 21-15/16 (1,014 × 1,190 × 558) 39-15/16 × 46-7/8 × 21-15/16 (1,014 × 1,190 × 558)
Weight (Mass) lbs (kg) 219 (100) 221 (100)
Gross Weight (Gross Mass) lbs (kg) 238 (108) 239 (108)
Sound Pressure Level dB(A) 55 57 55 57
Piping
Connection
Liquid in. (mm) 1/4 × 5 ( 6.4 × 5) 1/4 × 5 ( 6.4 × 5)
Gas
in. (mm)
3/8 × 1, 1/2 × 2, 5/8 × 2
( 9.5 × 1, 12.7 × 2, 15.9 × 2)
3/8 × 1, 1/2 × 2, 5/8 × 2
( 9.5 × 1, 12.7 × 2, 15.9 × 2)
Drain in. (mm) I.D. 1 ( 25) I.D. 1 ( 25)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
No. of Wiring Connections 3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring
(Including Ground Wiring)
Max. Interunit Piping Length ft (m) 262 (80) (for Total of Each Room) 262 (80) (for Total of Each Room)
ft (m) 98 (30) (for One Room) 98 (30) (for One Room)
Amount of Additional Charge oz/ft
(g/m)
0.22 (20) (131-1/4 ft (40 m) or more) 0.22 (20) (131-1/4 ft (40 m) or more)
Max. Installation Height Difference ft (m) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit) 49-1/4 (15) (Between Indoor Unit and Outdoor Unit)
ft (m) 24-5/8 (7.5) (Between Indoor Units) 24-5/8 (7.5) (Between Indoor Units)
Conditions based on Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Indoor ; 80°FDB (26.7°CDB)
/ 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB)
/ 75°FWB (24°CWB)
Indoor ; 70°FDB (21°CDB) /
60°FWB (15.6°CWB)
Outdoor ; 47°FDB (8.3°CDB)
/ 43°FWB (6°CWB)
Piping length: 25 ft (7.5 m) Piping length: 25 ft (7.5 m)
Drawing No. C: 3D158484 C: 3D158481
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
background
SiUS122410EA
Part 3 Printed Circuit Board Connector Wiring Diagram 25
1. Indoor Unit.............................................................................................26
2. Outdoor Unit..........................................................................................28
2.1 2/3/4MXM, 2MXT ...................................................................................28
2.2 5MXM, 3/4/5MXT, 3/4/5MXTH ...............................................................31
Part 3
Printed Circuit Board
Connector Wiring Diagram
background
Indoor Unit SiUS122410EA
26 Part 3 Printed Circuit Board Connector Wiring Diagram
1. Indoor Unit
Control PCB
(A1P)
1) S1 Connector for terminal strip
2) S6 Connector for swing motor (horizontal blade)
3) S91 Connector for humidity sensor PCB (A4P)
4) S200 Connector for DC fan motor
5) S403 Connector for optional adaptor
6) S430 Connector for wireless LAN connection PCB (A3P)
7) S501 Connector for indoor heat exchanger thermistor (R1T)
8) S800 Connector for display/signal receiver PCB (A2P)
9) FG Connector for terminal strip (frame ground)
10) FU1 Fuse (3.15 A, 250 V)
11) V2 Varistor
FU1
S1
V2
S91
S6
FGS200
S800 S430
S403S501
2P721387-10
2P721387-11
background
SiUS122410EA Indoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 27
Display/Signal
Receiver PCB
(A2P)
Wireless LAN
connection PCB
(A3P)
Humidity sensor
PCB (A4P)
1) S27 Connector for control PCB (A1P)
2) SW1 Indoor unit ON/OFF switch
(Forced cooling operation ON/OFF switch)
Refer to page 161 for details of forced cooling operation.
3) LED1 LED for operation (green)
4) LED2 LED for timer (orange)
5) LED3 LED for optional wireless LAN connection (orange)
3P719708-1
SW1 LED1LED2LED3
S27
1) S90 Connector for control PCB (A1P)
2P695897-7
S90
1) CON1 Connector for control PCB (A1P)
3E860031-1
CON1
background
Outdoor Unit SiUS122410EA
28 Part 3 Printed Circuit Board Connector Wiring Diagram
Note
2. Outdoor Unit
2.1 2/3/4MXM, 2MXT
Main PCB (A1P)
The symbols in the parenthesis are the names on the appropriate wiring diagram.
1) X190A Connector for ground wire
2) X200A Connector for DC fan motor
3) X240A, X300A,
X480A
Connector for sub PCB (A2P)
4) X800A Connector for four way valve coil
5) X820A Connector for overload protector and high pressure switch
6) X900A Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
7) HL1, HN1 Faston tab for terminal strip (power supply)
8) U, V, W Faston tab for compressor
9) F1U (FU1),
F2U (FU2)
Fuse (3.15 A, 250 V)
10) F3U (FU3) Fuse (30 A, 250 V)
2P757473-4
2P757473-5
F3U
X800A
X240A
X190A
X300A
F1U
X200A
F2U
U
V
W
X480AX820A X900A HN1 HL1
background
SiUS122410EA Outdoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 29
Sub PCB (A2P)
1) X1A Connector for main PCB (A1P)
2) X141A Connector for service monitor PCB (A3P)
3) X161A Connector for COOL/HEAT lock
Refer to page 173 for details.
4) X301A Connector for terminal block (indoor - outdoor transmission)
5) X371A Connector for main PCB (A1P)
6) X621A Connector for electronic expansion valve coil A port
7) X622A Connector for electronic expansion valve coil B port
8) X623A Connector for electronic expansion valve coil C port (24/36 class)
9) X624A Connector for electronic expansion valve coil D port (36 class)
10) X931A Connector for gas pipe thermistor
11) X951A Connector for liquid pipe thermistor
12) HN1 Faston tab for main PCB (A1P)
13) DP3, DP4 Wire harness for drain pan heater (MXTH-A only)
14) F1U Fuse (3.15 A, 250 V)
2P729400-1
X141A
DP3F1U DP4
X624A
X623A
X622A
X621A
X1A
HN1
X301A
X951A
X931AX161A
X371A
background
Outdoor Unit SiUS122410EA
30 Part 3 Printed Circuit Board Connector Wiring Diagram
Service Monitor
PCB (A3P)
SW6-2 and all the switches of SW5 have no function. Keep them OFF.
1) S501, S502 Connector for sub PCB (A2P)
2) LED A LED for service monitor (green)
3) LED1, LED2,
LED3, LED4,
LED5
LED for service monitor (red)
4) SW1 Forced cooling operation ON/OFF switch
Refer to page 161 for details.
5) SW2 Operation mode switch
Refer to page 161 for details.
6) SW3 Wiring error check switch
Refer to page 162 for details.
7) SW4 Priority room setting switch
Refer to page 172 for details.
8) SW6-1 NIGHT QUIET mode setting switch
Refer to page 174 for details.
9) J_DP Jumper for drain pan heater
3P346711-10
S502SW6-1SW2J_DPSW3
LED5 LED4 LED3 LED2 LED1 LED A S501
SW1 SW4
background
SiUS122410EA Outdoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 31
2.2 5MXM, 3/4/5MXT, 3/4/5MXTH
Main PCB (A1P)
1) S, S10 Connector for terminal block (indoor - outdoor transmission)
2) S15 Connector for COOL/HEAT lock
Refer to page 173 for details.
3) S20 Connector for electronic expansion valve coil A port
4) S21 Connector for electronic expansion valve coil B port
5) S22 Connector for electronic expansion valve coil C port
(24/36/40/48 class)
6) S23 Connector for electronic expansion valve coil D port (36/40/48 class)
7) S24 Connector for electronic expansion valve coil E port (40/48 class)
8) S40 Connector for overload protector and high pressure switch
9) S60 Connector for pressure sensor
10) S70 Connector for DC fan motor
11) S80 Connector for four way valve coil
12) S90 Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
13) S92 Connector for gas pipe thermistor
14) S93 Connector for liquid pipe thermistor
15) S201, S202 Connector for service monitor PCB (A2P)
16) DP1, DP2 Connector for drain pan heater (MXTH-A only)
17) HL1, HN1 Faston tab for terminal strip (power supply)
18) E1, E2, E3 Connector for ground wire
19) W, V, U Faston tab for compressor
20) FU1, FU2, FU10 Fuse (3.15 A, 250 V)
21) FU3 Fuse (30 A, 250 V)
2P690309-11
FU10 S10 S DP2 DP1FU1FU3HL1 S15 S40 S60S202 S201
E1
HN1
E2
E3
FU2
S80
S70
S23
S24
S90
S92
S22
S21
S20
S93
UVW
background
Outdoor Unit SiUS122410EA
32 Part 3 Printed Circuit Board Connector Wiring Diagram
Service Monitor
PCB (A2P)
SW6-2 and all the switches of SW5 have no function. Keep them OFF.
1) S501, S502 Connector for main PCB (A1P)
2) LED A LED for service monitor (green)
3) LED1, LED2,
LED3, LED4,
LED5
LED for service monitor (red)
4) SW1 Forced cooling operation ON/OFF switch
Refer to page 161 for details.
5) SW2 Operation mode switch
Refer to page 161 for details.
6) SW3 Wiring error check switch
Refer to page 162 for details.
7) SW4 Priority room setting switch
Refer to page 172 for details.
8) SW6-1 NIGHT QUIET mode setting switch
Refer to page 174 for details.
9) J_DP Jumper for drain pan heater
3P346711-10
S502SW6-1SW2J_DPSW3
LED5 LED4 LED3 LED2 LED1 LED A S501
SW1 SW4
background
SiUS122410EA
Part 4 Functions and Control 33
1. Main Functions......................................................................................34
1.1 Temperature Control ..............................................................................34
1.2 Frequency Principle................................................................................34
1.3 Airflow Direction Control.........................................................................36
1.4 COMFORT AIRFLOW Operation ...........................................................37
1.5 Fan Speed Control for Indoor Unit .........................................................38
1.6 Program Dry Operation ..........................................................................39
1.7 Automatic Cooling/Heating Change-over ...............................................40
1.8 Thermostat Control.................................................................................41
1.9 NIGHT SET Mode ..................................................................................42
1.10 ECONO Operation ................................................................................42
1.11 POWERFUL Operation ..........................................................................43
1.12 Brightness Setting of Indoor Unit Display...............................................44
1.13 Wireless LAN Connection ......................................................................45
1.14 Other Functions......................................................................................49
2. Control Specification .............................................................................50
2.1 Thermistor Functions..............................................................................50
2.2 Mode Hierarchy ......................................................................................52
2.3 Compressor Speed Control....................................................................53
2.4 Controls at Mode Changing/Start-up......................................................55
2.5 Discharge Pipe Temperature Control.....................................................57
2.6 Input Current Control..............................................................................58
2.7 Freeze-up Protection Control .................................................................59
2.8 Heating Peak-cut Control .......................................................................60
2.9 High Pressure Protection Control...........................................................61
2.10 Outdoor Fan Control...............................................................................62
2.11 Liquid Compression Protection Function................................................62
2.12 Defrost Control .......................................................................................62
2.13 Low Compressor Speed High Pressure Limit ........................................69
2.14 Electronic Expansion Valve Control .......................................................70
2.15 Malfunctions ...........................................................................................75
Part 4
Functions and Control
background
Main Functions SiUS122410EA
34 Part 4 Functions and Control
1. Main Functions
1.1 Temperature Control
Definitions of
Temperatures
The definitions of temperatures are classified as following.
Room temperature: temperature of living space of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
Temperature
Control
The temperature of the room is detected by the room temperature thermistor. However, there is
a difference between the temperature detected by room temperature thermistor and the
temperature of living space of the room, depending on the type of the indoor unit or installation
condition. In practice, the temperature control is done by the target temperature appropriately
adjusted for the indoor unit and the temperature detected by room temperature thermistor.
1.2 Frequency Principle
Control
Parameters
The compressor speed is controlled by the following 2 parameters:
The load condition of the operating indoor unit
The difference between the room thermistor temperature and the target temperature
The target compressor speed is adapted by additional parameters in the following cases:
Compressor speed restrictions
Initial settings
Forced cooling operation
Inverter Principle To regulate the capacity, a compressor speed control is needed. The inverter makes it possible
to control the rotation speed of the compressor. The followings explain the inverter principle:
Phase 1
The supplied AC power source is converted into the DC power source for the present.
Phase 2
The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting in
an increase of refrigerant circulation. This leads to a larger amount of heat exchange per
unit.
When the frequency decreases, the rotation speed of the compressor decreases resulting in
a decrease of refrigerant circulation. This leads to a smaller amount of heat exchange per
unit.
Target temperature
Set temperature
Room temperature
Room thermistor temperature
(R12321)
background
SiUS122410EA Main Functions
Part 4 Functions and Control 35
The following drawing shows a schematic view of the inverter principle:
Inverter Features The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor
temperature and cooling/heating load.
Quick heating and quick cooling
The rotation speed of the compressor is increased when starting the heating (cooling).
This enables to reach the set temperature quickly.
Even during extreme cold weather, high capacity is achieved. It is maintained even when the
outdoor temperature is 2C (35.6°F).
Comfortable air conditioning
A fine adjustment is integrated to keep the room temperature constant.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Compressor
Speed Limits
The following functions regulate maximum compressor speed:
Low compressor speed
Four way valve operation compensation. Refer to page 55.
High compressor speed
Compressor protection function. Refer to page 56.
Discharge pipe temperature control. Refer to page 57.
Input current control. Refer to page 58.
Freeze-up protection control. Refer to page 59.
Heating peak-cut control. Refer to page 60.
Defrost control. Refer to page 62.
Forced Cooling
Operation
Refer to page 161 for details.
Refrigerant circulation rate (high)
high f
low f
freq=variable
Refrigerant circulation rate (low)
high speed
low speed
(R2812)
Amount of heat
exchanged air (large)
freq=
constant
50 Hz
50 Hz
60 Hz
60 Hz
capacity=
variable
Amount of heat
exchanged air (small)
AC
power
DC
power
Amount of heat exchanged air
(large)
Amount of heat exchanged air
(small)
background
Main Functions SiUS122410EA
36 Part 4 Functions and Control
1.3 Airflow Direction Control
Power-Airflow
(Dual) Flap(s)
The large flap sends a large volume of air downward to the floor and provides an optimum
control in cooling, dry and heating operation.
Cooling/Dry
During cooling or dry operation, the flap retracts into the indoor unit. Then, cool air can be blown
far and distributed all over the room.
Heating
During heating operation, the large flap directs airflow downward to spread the warm air to the
entire room.
Wide-Angle
Louvers
The louvers, made of elastic synthetic resin, provide a wide range of airflow that guarantees
comfortable air distribution.
Auto-Swing The following tables explain the auto-swing process for cooling, dry, heating and fan:
Flap (up and down)
Cooling/Dry Heating Fan
07/09/12
class
R4004115
15/18/24
class
R4004124 R4004125 R4004126
5°
45°
(R21050)
0°
65°
15°
30°
55°
70°
80°
65°
20°
35°
25°
80°
10°
65°
background
SiUS122410EA Main Functions
Part 4 Functions and Control 37
Note(s)
1.4 COMFORT AIRFLOW Operation
Outline The flow of air will be in the upward direction while in COOL/DRY operation and in the
downward direction while in HEAT operation, which will provide a comfortable wind that will not
come in direct contact with people.
Operation
To start the operation:
Press Comfort button.
The icon appears on the LCD of the remote controller.
To stop the operation:
Press Comfort button again.
The icon disappears from the LCD of the remote controller. The flaps will return to the
memorized position before the start of COMFORT AIRFLOW operation
POWERFUL operation and COMFORT AIRFLOW operation cannot be used at the same
time.
When in AUTO operation, the flap direction differs based on the operation mode (COOL or
HEAT) as shown in the table above.
If the upward and downward airflow direction is selected, the COMFORT AIRFLOW function
will be canceled. Priority is given to the function of whichever button is pressed last.
COOL / DRY operation HEAT operation FAN operation
Flaps direction Goes up Goes down
Not available
Airflow rate AUTO
Comfort
button
background
Main Functions SiUS122410EA
38 Part 4 Functions and Control
Note(s)
1.5 Fan Speed Control for Indoor Unit
Outline Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature.
Automatic Fan
Speed Control
In automatic fan speed operation, the step SL is not available.
R4003512
= The airflow rate is automatically controlled within this range when FAN setting button is
set to automatic
.
Cooling
The following drawing explains the principle of fan speed control for cooling.
R4004133
The upper limit is at M tap in 30 minutes from the operation start.
Heating
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
The fan stops during defrost operation.
HeatingCoolingStep
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
+0.5°C (+0.9°F)
MH*
M
ML
L
+3°C (+5.4°F)
+2.5°C (+4.5°F)
+1.5°C (+2.7°F)
Fan speed
Room thermistor temperature – target temperature
background
SiUS122410EA Main Functions
Part 4 Functions and Control 39
1.6 Program Dry Operation
Outline Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and FAN setting buttons are inoperable.
Details The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
R4004134
Thermostat turns on also when the room temperature is in the zone B for 10 minutes.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24°C or more
(75.2°F or more)
Room thermistor
temperature at start-up
X – 1.0°C
(X – 1.8°F)
X – 0.25°C
(X – 0.5°F)
18 ~ 23.5°C
(64.4 ~ 74.3°F)
X – 0.75°C
(X – 1.4°F)
X – 0.25°C
(X – 0.5°F)
17.5°C or less
(63.5°F or less)
18°C
(64.4°F)
X – 0.75°C
(X – 1.4°F)
X – 0.25°C = 17.75°C
(X – 0.5°F = 63.9°F)
Zone A = Thermostat OFF
Target temperature X
Zone B
Room temperature Room temperature
Zone C = Thermostat ON
Y = X – 1.0°C (1.8°F)
Z = X – 0.25°C (0.5°F)
X – 0.5°C (0.9°F)
background
Main Functions SiUS122410EA
40 Part 4 Functions and Control
1.7 Automatic Cooling/Heating Change-over
Outline When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Details Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C (64.4 ~ 86°F))
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value.
C = 0°C (0°F)
3. Thermostat ON/OFF point and operation mode switching point are as follows.
(1) Heating Cooling switching point:
Tr Tt + 3.0°C (+ 5.4°F)
(2) Cooling Heating switching point:
Tr < Tt – 2.5°C (– 4.5°F)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating
operation.
4. During initial operation
Tr Ts : Cooling operation
Tr < Ts : Heating operation
R4004135
Ex: When the target temperature is 25°C (77°F)
Cooling → 24°C (75.2°F): Thermostat OFF → 22.5°C (72.5°F): Switch to heating
Heating → 26°C (78.8°F): Thermostat OFF → 28°C (82.4°F): Switch to cooling
Target temperature + 3.0°C (+5.4°F)
Heating Operation
Target temperature – 2.5°C (–4.5°F)
Cooling Operation
Target temperature – 1.0°C (–1.8°F)
= Thermostat OFF
Target temperature + 1.0°C (+1.8°F)
= Thermostat OFF
background
SiUS122410EA Main Functions
Part 4 Functions and Control 41
Reference
1.8 Thermostat Control
Outline Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Details Thermostat OFF Conditions
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
Cooling/Dry
R4004136
Heating
R4004137
Refer to Temperature Control on page 34 for details.
Cooling Dry Heating
10 minutes 7.5 minutes 180 seconds
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
Room thermistor temperature – target temperature
–0.5°C (–0.9°F)
–0.25°C (–0.5°F)
–1.0°C (–1.8°F)
Zone B
Zone B
Zone A
Zone A
OFF
OFF
ON
ON
Zone C
Zone C
1.0°C (1.8°F)
0.5°C (0.9°F)
0.25°C (0.5°F)
0.75°C (1.4°F)
1.0°C (1.8°F)
Room thermistor temperature – target temperature
background
Main Functions SiUS122410EA
42 Part 4 Functions and Control
1.9 NIGHT SET Mode
Outline When the OFF TIMER is set, NIGHT SET mode is automatically activated. NIGHT SET mode
keeps the airflow rate setting.
Details NIGHT SET mode continues operation at the target temperature for the first one hour, then
automatically raises the target temperature slightly in the case of cooling, or lowers the target
temperature slightly in the case of heating. This prevents excessive cooling in summer and
excessive heating in winter to ensure comfortable sleeping conditions, and also conserves
electricity.
Cooling
Heating
1.10 ECONO Operation
Outline ECONO operation reduces the maximum operating current and the power consumption.
This operation is particularly convenient for energy-saving. It is also a major bonus when
breaker capacity does not allow the use of multiple electrical devices and air conditioners.
It can be easily activated by pressing ECONO button on the wireless remote controller.
Details When this function is activated, the maximum capacity also decreases.
The remote controller can send the ECONO command when the unit is in cooling, heating,
dry, or automatic operation. This function can only be set when the unit is running. Pressing
ECONO button on the remote controller cancels the function.
This function and POWERFUL operation cannot be used at the same time. The latest
command has the priority.
(R23917)
Target temperature
+0.5°C (+0.9°F)
temperature shift
Operation stops
at the set hour
0.5°C (0.9°F)
1 hour
TIMER operation
NIGHT SET Mode ON
Target temperature
–2°C (–3.6°F)
temperature shift
1 hour
2°C (3.6°F)
(R23918)
TIMER operation
NIGHT SET Mode ON
ECONO operation
(R22012)
Normal operation
Maximum during normal operation
Maximum during ECONO operation
Time
Power
consumption
and current
background
SiUS122410EA Main Functions
Part 4 Functions and Control 43
Note(s)
1.11 POWERFUL Operation
Outline In order to exploit the cooling and heating capacity to full extent, the air conditioner can be
operated by increasing the indoor fan rotating speed and the compressor speed.
Details When POWERFUL button is pressed, the fan speed and target temperature are converted to
the following states for 20 minutes.
A = 40 ~ 80 rpm (depending on the model)
Ex: POWERFUL operation in cooling
During POWERFUL operation, the cooling/heating efficiency of the other rooms may be
slightly reduced.
POWERFUL operation cannot be used together with ECONO, COMFORT AIRFLOW or
OUTDOOR UNIT QUIET operation.
Operation mode Fan speed Target temperature
COOL H tap + A rpm 18°C (64.4°F)
DRY Dry rotating speed + A rpm Lowered by 2.5°C (4.5°F)
HEAT H tap + A rpm 31°C (87.8°F)
FAN H tap + A rpm —
AUTO Same as cooling/heating in
POWERFUL operation
The target temperature is kept
unchanged.
(R24589)
Target temp.
Fan
A rpm
H tap
Set tap
20 minutes
Lower limit of cooling
temperature
Remote controller registers
20 minutes independently.
POWERFUL
ON
POWERFUL
OFF
Ending conditions:
1. Lapse of 20 minutes
2. System operation OFF
3. POWERFUL operation OFF
18°C (64.4°F)
background
Main Functions SiUS122410EA
44 Part 4 Functions and Control
Note(s)
1.12 Brightness Setting of Indoor Unit Display
Outline The brightness of the indoor unit display can be adjusted as desired. Also, the display can be
turned OFF.
Details 1. Press and hold FAN button for 5 seconds.
2. Press TEMP ▲ button to select menu number 1.
LED appears and 1 blinks.
R4004121
3. Press FAN button to confirm the select setting.
4. Press TEMP ▲ or TEMP ▼ button to change the setting as follows:
R4004122
5. Press FAN button again. Brightness will be set to the chosen value.
6. Press and hold FAN button for 5 seconds to return to the default screen.
The display automatically returns to the default screen after 60 seconds. To return to the default
screen sooner, press CANCEL button twice.
H: Bright L: Dark of: OFF
background
SiUS122410EA Main Functions
Part 4 Functions and Control 45
1.13 Wireless LAN Connection
Operation
Wireless LAN connection adapter
The Wireless LAN connection adapter function requires the Daikin One Home for connecting to the air conditioner and controlling
it via your smartphone or tablet over your network.
Attention
•
Wireless LAN sends and receives data using radio waves so there is a risk of transmitted data being subject to eavesdropping and illegal access.
When using wireless LAN, manage the SSID/KEY of the wireless LAN connection adapter, the SSID/KEY of the wireless router, and the app login
information so that they will not be known to others, and ensure that you have an adequate understanding of the risks involved.
In the case that the product is accessed and operated illegally, turn off the wireless LAN connection adapter function.
• Do not use this product near a microwave oven. (This can affect wireless LAN communications.)
• This product cannot be directly connected to the communication line of a telecommunications carrier (internet service provider,
etc.). When connecting to the internet, be sure to connect via a device such as a router.
When the wireless LAN connection adapter function is turned on, the right side of the air conditioner may become slightly warm, but this is not
an abnormality.
WARNING
•
This product may cause electromagnetic interference.
•
This product may cause faulty behavior of the equipment.
• The user is responsible for providing the following items before using this product:
Smartphone or tablet PC
Internet line and communicating device (Modem/router or similar device)
Wireless LAN access point
Application name: [Daikin One Home] (free)
For details on the installation method for the Daikin One Home.
Wireless LAN connection adapter lamp (Orange)
• The Wireless LAN connection adapter lamp lights when connecting to a router (Wireless LAN
access point).
• For Wireless LAN connection adapter operation.
Display
WARNING
When operating an air conditioner from outside the home, it is not possible to check the air conditioner or the surroundings of the air
conditioner, or the state of the people in the room. Therefore, make sure to adequately check for safety before use.
In some cases, there is a risk of death, severe injury, or property damage.
Check the following in advance (while at home)
• Timer settings or reservations that other users may have made. (There is a risk of causing harm to the health of people, animals, or plants in
the home if operation starts and stops unexpectedly)
•
staining of household items)
Check the following before/while operating a unit from outside the home
• If you know that there is someone at home, inform the person when turning the air conditioner on or off from outside the home. (If someone at
home is standing on something such as a stool, the air conditioner turning on or off unexpectedly could surprise them and cause them to fall or
topple over. Additionally, a sudden change in the indoor/outdoor temperature could harm the health of people at home)
· The air conditioner can be turned off and temperature adjustment can be made using a remote controller in the home.
· Do not use the function if the only people at home are persons who are unable to make adjustments to temperature or other settings
themselves, such as young children, disabled persons, or elderly persons.
• Regularly check the settings and operating status of the air conditioner. (Sudden changes in indoor/outdoor temperature pose a health hazard.
There is a risk of harm to animals and plants)
If an error occurs during operation, immediately turn off the air conditioner and contact your dealer.
background
Main Functions SiUS122410EA
46 Part 4 Functions and Control
Wireless LAN connection
Web site:
https://daikinone.com/ductless
For instructions on how to connect y
our unit to wireless LAN and to your Daikin One Home application, please see the website above.
Contains FCC ID: VPYLB1YA
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation.
FCC CAUTION
This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
Contains IC: 772C-LB1YA
This device complies with Industry Canada’s applicable licence-exempt RSSs.
Operation is subject to the following two conditions:
(1) This device may not cause interference; and
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment and meets RSS-102 of the IC radio frequency (RF)
Exposure rules. This equipment should be installed and operated keeping the radiator at least 7-7/8 inches (20cm) or more away from person’s body.
The FCC responsible party is Daikin Comfort Technologies Manufacturing, L.P., and may be contacted by calling (713)-861-2500, or at 19001
Kermier Rd., Waller, TX 77484.
(https://www.northamerica-daikin.com)
radiator.
And this intentional radiator has an industry Canada ID: IC 772C-LB1YA.
The manufacturer of the intentional radiator (model no. Type1YA) is Murata Manufacturing co., Ltd (www.murata.com).
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment and meets the FCC radio frequency (RF) Exposure
Guidelines. This equipment should be installed and operated keeping the radiator at least 7-7/8 inches (20cm) or more away from person’s body.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
background
SiUS122410EA Main Functions
Part 4 Functions and Control 47
Application software installation
For Android Phones
1) Open [Google Play].
2) Search using the application name:
[Daikin One Home].
3) Follow the directions on the screen to install.
For iOS Phones
1) Open the [App Store].
2) Search using the application name:
[Daikin One Home].
3) Follow the directions on the screen to install.
Attention
• The actual application screen layout and content may differ from what is shown. The layout and content of the application screen is subject to
change without notice.
Connect the air conditioner to your home network.
1.
While operation is stopped, press and hold the button for 5 seconds.
2.
Press or and select menu number .
• “ ” appears on the LCD.
• “
” blinks.
3.
Press to connect to the access point.
The wireless LAN
connection adapter
lamp blinks quickly.
Display
4.
Press to return to the default screen.
No more settings need to be carried out from the remote controller.
5.
Open Daikin One Home App and follow the instructions to set up the wireless LAN.
6.
When the wireless LAN connection adapter lamp switches from blinking to lit, the
connection is complete.
NOTE
• While “SP” is displayed, the options that can be selected using and are 1, 3, A, and OFF.
• Perform wireless LAN connection one indoor unit at a time.
• If you are unable to establish a network connection, refer the troubleshooting provided by the Daikin One Home App.
• When the lamp blinks slowly, the connection is not ready. Perform the connection procedure while it blinks quickly.
background
Main Functions SiUS122410EA
48 Part 4 Functions and Control
1.
While operation is stopped, press and hold the button for 5 seconds.
2. Press
• “ ” appears on the LCD.
• “
” blinks.
Check the indoor unit LED.
Wireless LAN connection adapter lamp Status
Blinking for 1 second Connection is not ready
Blinking for 3 seconds
Please initialize the wireless LAN connection adapter
Does not blink or light
Communication is abnormal
There is a possibility of equipment failure
Please request repair
To turn off the wireless connection
To use the remote controller
1.
While operation is stopped, press and hold the button for 5 seconds.
2. Press or and select menu .
• “ ” appears on the LCD.
• “
” blinks, and communication is OFF.
3.
Press
• The wireless LAN connection adapter lamp turn off.
4. Press to return to the default screen.
To reset the connection setting to the factory default
•
If you want to reset the connection settings, it is possible to initialize the wireless LAN connection adapter to its
factory default state. If initialized, data including the network settings and power consumption history will be erased.
• When discarding or transferring to another user, initialize the connection adapter to erase the internal data.
To reset
1.
While operation is stopped, press and hold the button for 5 seconds.
2. Press or and select menu .
• “ ” appears on the LCD.
• “
” blinks.
3.
Press
• The wireless LAN connection adapter lamp blinks for 1 second.
4. Press to return to the default screen.
background
SiUS122410EA Main Functions
Part 4 Functions and Control 49
Note(s)
Note
1.14 Other Functions
1.14.1 Hot-Start Function
In order to prevent the cold air blast that normally occurs when heating operation is started, the
temperature of the indoor heat exchanger is detected, and the airflow is either stopped or
significantly weakened resulting in comfortable heating.
The cold air blast is prevented using similar control when defrost control starts or when the
thermostat is turned ON.
1.14.2 Signal Receiving Sign
When the indoor unit receives a signal from the remote controller, the unit emits a signal
receiving sound and the operation lamp blinks.
1.14.3 Indoor Unit ON/OFF Switch
ON/OFF switch is provided on the display of the unit.
Press ON/OFF switch once to start operation. Press once again to stop it.
ON/OFF switch is useful when the remote controller is missing or the battery has run out.
In the case of multi system operation, there are times when the unit does not activate with
ON/OFF switch.
1.14.4 Auto-restart Function
If a power failure (even a momentary one) occurs during the operation, the system restarts
automatically in the same conditions as before when the power supply is restored to the
conditions prior to the power failure.
It takes 3 minutes to restart the operation because 3-minute standby function is activated.
Operation mode Temperature setting Airflow rate
AUTO 25°C (77°F) Automatic
07/09/12 class 15/18/24 class
R4004127 R4004128
ON/OFF switch
ON/OFF switch
background
Control Specification SiUS122410EA
50 Part 4 Functions and Control
2. Control Specification
2.1 Thermistor Functions
R4004138
The illustration is for the 4-room models as representative and have 4 lines of indoor unit
system (A ~ D).
Each system has respective number of lines according to the specified number of the rooms.
(1) Discharge
Pipe Thermistor
The discharge pipe thermistor is used for controlling discharge pipe temperature. If the
discharge pipe temperature (used in place of the inner temperature of the compressor) rises
abnormally, the operating compressor speed becomes lower or the operation halts.
The discharge pipe thermistor is used for detecting disconnection of the discharge pipe
thermistor.
(2) Outdoor Heat
Exchanger
Thermistor
The outdoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the
outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the outdoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the outdoor heat exchanger temperature by more than a certain value, the discharge
pipe thermistor is judged as disconnected.
In cooling operation, the outdoor heat exchanger thermistor is used for high pressure
protection.
(3) Outdoor
Temperature
Thermistor
The outdoor temperature thermistor detects the outdoor air temperature and is used for
refrigerant shortage detection, input current control, outdoor fan control, liquid compression
protection function, and so on.
(4) Gas Pipe
Thermistor
In cooling operation, the gas pipe thermistor is used for gas pipe isothermal control. The
system controls electronic expansion valve opening so that the gas pipe temperature in each
room becomes equal.
(5) Liquid Pipe
Thermistor
Liquid pipe thermistor is used to protect the compressor against liquid attack during cooling
operation.
In case of low outdoor temperature operation, the system compares the indoor heat
exchanger temperature with the liquid pipe temperature to detect disturbances in the
refrigerant flow. If any, the system adjusts the opening of the electronic expansion valve to
control the refrigerant flow.
Four way valve
Compressor
EVC
EVD
EVB
EVA
Expansion valve
DCBA
(3) Outdoor
Temperature
Thermistor
(2) Outdoor Heat
Exchanger
Thermistor
(1) Discharge Pipe
Thermistor
(4) Gas Pipe
Thermistor
(6) Indoor Heat
Exchanger
Thermistor
(7) Room
Temperature
Thermistor
(5) Liquid Pipe
Thermistor
background
SiUS122410EA Control Specification
Part 4 Functions and Control 51
When only one indoor unit is in heating operation, the liquid pipe thermistor is used for
subcooling control. The actual subcool is calculated with the liquid pipe temperature and the
maximum indoor heat exchanger temperature. The system controls the electronic expansion
valve openings to obtain the target subcool.
In heating operation, the liquid pipe thermistor is used for liquid pipe isothermal control. The
system controls the electronic expansion valve opening so that the liquid pipe temperatures
in each room becomes equal.
(6) Indoor Heat
Exchanger
Thermistor
The indoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the
outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the indoor heat exchanger thermistor is used for freeze-up protection
control. If the indoor heat exchanger temperature drops abnormally, the operating
compressor speed becomes lower or the operation halts.
In cooling operation, the indoor heat exchanger thermistor is used for anti-icing function. If
any of the following conditions are met in the room where operation halts, it is assumed as
icing.
The conditions are
Tc – 1°C (30.2°F)
Ta – Tc 10°C (18°F)
where Ta is the room temperature and Tc is the indoor heat exchanger temperature.
The indoor heat exchanger thermistor is used for wiring error check function. The refrigerant
flows in order from the port A to detect the indoor heat exchanger temperature one by one,
and then wiring and piping can be checked.
In heating operation, the indoor heat exchanger thermistor is used for heating peak-cut
control. If the indoor heat exchanger temperature rises abnormally, the operating
compressor speed becomes lower or the operation halts.
In heating operation, the indoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the highest indoor heat exchanger temperature by more than a certain value, the
discharge pipe thermistor is judged as disconnected.
Excluding the case that all the indoor units are in heating operation, the indoor heat
exchanger thermistor is used for subcooling control. The actual subcool is calculated with
the liquid pipe temperature and the indoor heat exchanger temperature. The system controls
the electronic expansion valve openings to obtain the target subcool.
(7) Room
Temperature
Thermistor
The room temperature thermistor detects the room air temperature and is used for
controlling the room air temperature.
background
Control Specification SiUS122410EA
52 Part 4 Functions and Control
2.2 Mode Hierarchy
Outline The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Details
Unless specified otherwise, dry operation command is regarded as cooling operation.
Indoor fan operation cannot be made in multiple indoor units. (A forced fan command is
made during forced cooling operation.)
Determine Operation Mode
The system judges the operation mode command which is set by each room in accordance with
the procedure, and determines the operation mode of the system.
The following procedure is taken when the modes conflict with each other.
1. The system follows the mode which is set first. (First-push, first-set)
2. For the rooms where the different mode is set, standby mode is activated. (The operation
lamp blinks.)
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Forced heating operation
Wiring error check operation
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Heating
Heating
Defrosting
Stop (indoor unit: OFF)
Preheating operation
Discharging from capacitor
Stop
(R17361)
background
SiUS122410EA Control Specification
Part 4 Functions and Control 53
2.3 Compressor Speed Control
Outline Compressor speed corresponding to each room’s capacity is determined according to the
difference between the target temperature and the temperature of each room.
R4004268
Details The compressor speed is determined by taking the following steps.
1. Determine command compressor speed
Command compressor speed is determined in the following order of priority.
(1) Limiting defrost control time
(2) Forced cooling/heating
(3) Indoor compressor speed command
2. Determine upper limit compressor speed
The minimum value is set as the upper limit compressor speed among the compressor
speed upper limits of the following functions:
Compressor protection, input current, discharge pipe temperature, low compressor speed
high pressure limit, heating peak-cut, freeze-up protection, defrost.
3. Determine lower limit compressor speed
The maximum value is set as the lower limit compressor speed among the compressor
speed lower limits of the following function:
Four way valve operation compensation, draft prevention, pressure difference upkeep.
4. Determine prohibited compressor speed
There is a certain prohibited compressor speed such as a power supply compressor speed.
Parameters Q value
Indoor unit output determined from indoor unit volume, airflow rate and other factors.
S value: Indoor Unit Capacity
S value is the capacity of the indoor unit, and is used for compressor speed command.
Ex:
Command compressor speed
Limit compressor speed
Skip control
Upper limit function
Compressor protection function
Lower limit function
Four way valve operation compensation, etc.
Target compressor speed
When the shift of the compressor speed is less than zero ('F<0) by PI control,
the target compressor speed is used as the command compressor speed.
Dropping function
Input current control, etc.
Upper limit compressor speed
FMAX
Lower limit
compressor speed
FMIN
Initial
compressor speed
PI control
Defrost control
Capacity S value Capacity S value
7 kBtu/h 20 15 kBtu/h 50
9 kBtu/h 25 18 kBtu/h 60
12 kBtu/h 35 24 kBtu/h 71
background
Control Specification SiUS122410EA
54 Part 4 Functions and Control
D signal: Indoor compressor speed command
The difference between the room thermistor temperature and the target temperature is taken as
the D value and is used for D signal of compressor speed command.
Values depend on the type of indoor unit.
OFF = Thermostat OFF
Initial
Compressor
Speed
When starting the compressor, or when conditions are varied due to a change of operating
rooms, the compressor speed must be initialized according to a total of the maximum D value
of each room and a total Q value (Q) of the operating room (the room in which the thermostat
is set to ON).
PI Control 1. P control
MaxD value is calculated in each sampling time (15 seconds), and the compressor speed
is adjusted according to its difference from the compressor speed previously calculated.
2. I control
If the operating compressor speed does not change for more than a certain fixed time, the
compressor speed is adjusted according to maxD value.
When maxD value is low, the compressor speed is lowered.
When maxD value is high, the compressor speed is increased.
3. Compressor speed control when other controls are functioning
When compressor speed is dropping:
Compressor speed control is carried out only when the compressor speed drops.
For limiting lower limit:
Compressor speed control is carried out only when the compressor speed rises.
4. Upper and lower limit of compressor speed by PI control
The compressor speed upper and lower limits are set according to the total of S values.
When the indoor unit quiet operation commands come from all the rooms or when the
outdoor unit quiet operation commands come from all the rooms, the upper limit compressor
speed is lower than the usual setting.
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
–1.0°C (–1.8°F) OFF 0°C (0°F) 4 2.0°C (3.6°F) 8 4.0°C (7.2°F) 12
–0.75°C (–1.4°F) 1 0.5°C (0.9°F) 5 2.5°C (4.5°F) 9 4.5°C (8.1°F) 13
–0.5°C (–0.9°F) 2 1.0°C (1.8°F) 6 3.0°C (5.4°F) 10 5.0°C (9.0°F) 14
–0.25°C (–0.5°F) 3 1.5°C (2.7°F) 7 3.5°C (6.3°F) 11 5.5°C (9.9°F) 15
background
SiUS122410EA Control Specification
Part 4 Functions and Control 55
2.4 Controls at Mode Changing/Start-up
2.4.1 Preheating Control
Outline The inverter operation in open phase starts with the conditions of the outdoor temperature and
the preheating command from the indoor unit.
Details ON Condition
When the outdoor temperature is below A, the inverter operation in open phase starts.
OFF Condition
When the outdoor temperature is higher than B, the inverter operation in open phase stops.
2.4.2 Four Way Valve Switching
Outline The four way valve coil is energized/not energized depending on the operation mode
(Heating: ON, Cooling/Dry/Defrost: OFF).
In order to eliminate the switching sound as the four way valve coil switches from ON to OFF
when the heating is stopped, the OFF delay switch of the four way valve is carried out.
Details OFF delay switch of four way valve
The four way valve coil is energized for 150 seconds after the operation is stopped.
2.4.3 Four Way Valve Operation Compensation
Outline At the beginning of operation as the four way valve is switched, the pressure difference to
activate the four way valve is acquired when the output compressor speed is higher than a
certain fixed compressor speed, for a certain fixed time.
Details Starting Conditions
The compressor starts and the four way valve switches from OFF to ON
The four way valve switches from ON to OFF during operation
The compressor starts after resetting
The compressor starts after the fault of four way valve switching
The lower limit of compressor speed keeps A rps for 70 seconds for any of the conditions
above.
2.4.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
The function is not used when defrosting.
2/3/4MXM
2MXT(H)
5MXM
3/4/5MXT(H)
°C °F °C °F
A 5 41 20 68
B 7 44.6 21.5 70.7
2MXM 3/4MXM 2MXT(H) 5MXM 3/4/5MXT(H)
A (rps) Cooling 48 27 27 32 32
Heating 48 27 27 26 26
background
Control Specification SiUS122410EA
56 Part 4 Functions and Control
2.4.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of compressor speed is set as
follows.
The function is not used when defrosting.
2/3/4MXM, 2MXT(H)
R4004139
5MXM, 3/4/5MXT(H)
R4004266
2MXM 3/4MXM 2MXT(H)
A (rps) 55 35 35
B (rps) 70 65 65
C (rps) 85 80 80
D (seconds) 150 100 100
E (seconds) 180 500 500
F (seconds) 300 200 200
5MXM, 3/4/5MXT(H)
Cooling Heating
A (rps) 35 23 ~ 52
B (rps) 48 30 ~ 48
C (rps) 65 48 ~ 65
D (rps) 83 65 ~ 83
E (rps) 95 83 ~ 95
F (seconds) 120 40 ~ 120
G (seconds) 270 ~ 420 240 ~ 420
H (seconds) 290 ~ 450 180 ~ 450
J (seconds) 170 ~ 250 170 ~ 450
K (seconds) 150 ~ 220 150 ~ 220
A
DEF
B
C
(rps)
Compressor
speed
(sec.)
Time
(sec.)
Time
(rps)
Compressor
speed
C
D
E
B
FGHJK
A
background
SiUS122410EA Control Specification
Part 4 Functions and Control 57
2.5 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of compressor speed is
set to keep the discharge pipe temperature from rising further.
Details
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of compressor speed decreases.
Keep zone The upper limit of compressor speed is kept.
Reset zone The upper limit of compressor speed is canceled.
°C °F
A 120 248
B 111 231.8
C 109 228.2
D 107 224.6
E 107 224.6
Reset zone
Stop zone
Dropping
zone
Keep
zone
(R14266)
A
C
D
E
B
Discharge pipe
temperature
background
Control Specification SiUS122410EA
58 Part 4 Functions and Control
2.6 Input Current Control
Outline The microcomputer calculates the input current while the compressor is running, and sets the
compressor speed upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of the compressor speed and
takes priority over the lower limit control of four way valve operation compensation.
Details
Compressor speed control in each zone
Stop zone
After the input current remains in the stop zone for 2.5 seconds, the compressor is stopped.
Dropping zone
The upper limit of the compressor speed is defined as operation compressor speed – 2 rps.
After this, the output compressor speed is lowered by 2 rps every second until it reaches the
keep zone.
Keep zone
The present maximum compressor speed goes on.
Reset zone
Limit of the compressor speed is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level
(depending on the model).
2MXM 3MXM 4MXM 5MXM
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
A (A) 13.0 15.0 19.0 19.0 19.0 19.5 27.5 29.0
B (A) 11.5 14.0 16.0 17.0 17.0 18.5 25.5 27.0
C (A) 10.5 13.0 15.0 16.0 16.0 17.5 24.5 26.0
2MXT(H) 3MXT(H) 4MXT(H) 5MXT(H)
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
A (A) 19.0 19.0 27.0 27.0 27.5 29.0 27.5 29.0
B (A) 14.0 17.0 25.0 25.0 25.5 27.0 25.5 27.0
C (A) 13.0 16.0 24.0 24.0 24.5 26.0 24.5 26.0
Compressor Stop
Input current
Dropping zone
Stop zone
Keep zone
Reset zone
(R23249)
A
(A)
B
C
background
SiUS122410EA Control Specification
Part 4 Functions and Control 59
2.7 Freeze-up Protection Control
Outline During cooling operation, the signal sent from the indoor unit determines the compressor speed
upper limit and prevents freezing of the indoor heat exchanger. The signals from the indoor unit
are divided into zones.
Details The operating compressor speed limitation is judged with the indoor heat exchanger
temperature.
R4003891
°C °F
A 0 32
B 3 37.4
C 3.5 38.3
D 4 39.2
E 13 55.4
Reset zone
Up zone
Keep zone
Dropping zone
Stop zone
D
E
B
A
C
(Reference)
Indoor heat exchanger
temperature
background
Control Specification SiUS122410EA
60 Part 4 Functions and Control
2.8 Heating Peak-cut Control
Outline During heating operation, the indoor heat exchanger temperature determines the compressor
speed upper limit to prevent abnormal high pressure.
Details The operating compressor speed is judged with the indoor heat exchanger temperature 2
minutes after the operation starts and F seconds after the number of the rooms in operation
is changed.
The maximum value of the indoor heat exchanger temperature controls the following
(excluding the rooms not in operation).
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of compressor speed decreases.
Keep zone The upper limit of compressor speed is kept.
Up zone The upper limit of compressor speed increases.
Reset zone The upper limit of compressor speed is canceled.
2/3/4MXM
2MXT(H)
5MXM
3/4/5MXT(H)
°C °F °C °F
A 59 138.2 59 138.2
B 55 131 54 129.2
C 54 129.2 53 127.4
D 52 125.6 51 123.8
E 50 122 49 120.2
All outdoor units
F
(seconds)
When increasing 30
When decreasing 2
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R23928)
D
C
B
A
E
background
SiUS122410EA Control Specification
Part 4 Functions and Control 61
2.9 High Pressure Protection Control
Outline In order to prevent abnormal high pressures in the system and hence avoiding activation of the
high pressure safety device the below control function will be activated.
Details
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
Pressure
4.15 MPa
High Pressure
Protection
Control
Heating
Peak-cut
control
Condensing
temperature
HPS ≥ 4.15 MPa
(602 psi)
Compressor on
Compressor stop ( E3 indication)
Stopped 4 times
in 60 minutes
Abnormal stop ( E3 indication)
Normal operation
background
Control Specification SiUS122410EA
62 Part 4 Functions and Control
2.10 Outdoor Fan Control
1. Fan OFF control during defrosting
The outdoor fan is turned OFF while defrosting.
2. Fan OFF delay when stopped
The outdoor fan is turned OFF 60 seconds after the compressor stops.
3. Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled
as well as normal operation.
4. Fan control when the number of heating room decreases
When the outdoor temperature is more than 10°C (50°F), the fan is turned off for 30
seconds.
5. Fan speed control during forced cooling operation
The outdoor fan is controlled as well as normal operation during forced cooling operation.
6. Fan speed control for POWERFUL operation
The rotation speed of the outdoor fan is increased during POWERFUL operation.
7. Fan speed control during indoor/outdoor unit quiet operation
The rotation speed of the outdoor fan is reduced by the command of the indoor/outdoor unit
quiet operation.
8. Fan ON/OFF control when operation (cooling, heating, dry) starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF
when the operation stops.
2.11 Liquid Compression Protection Function
Outline The compressor stops according to the outdoor temperature for protection.
Details Operation stops depending on the outdoor temperature.
The compressor turns off under the conditions that the system is in cooling operation and the
outdoor temperature is below –12°C (10.4°F).
2.12 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than a certain value to finish defrosting.
Details Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature. (For details, refer to the table on the follow pages. (P. 64, 65, 66))
The system is in heating operation.
The compressor operates for 6 minutes.
More than A minutes of accumulated time have passed after the start of the operation or
ending the previous defrosting.
Furthermore, even if the above conditions are not met, if heating operation accumulates for
approximately S hours under conditions where the outdoor temperature is below T °C and
the outdoor heat exchanger temperature is below U °C, the system starts defrosting.
background
SiUS122410EA Control Specification
Part 4 Functions and Control 63
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature. (B°C (C°F))
R4004140
2MXM 3/4MXM 5MXM 2MXT(H) 3/4/5MXT(H)
A (minutes)
33 26 30 26 30
B (°C)
4 ~ 12 4 ~ 12 4 ~ 12 4 ~ 12 4 ~ 12
C (°F)
39.2 ~ 53.6 39.2 ~ 53.6 39.2 ~ 53.6 39.2 ~ 53.6 39.2 ~ 53.6
D (rps)
54 39 45 39 45
E (rps)
79 63 72 63 72
F (seconds)
90 60 60 60 60
G (seconds)
120 120 120 120 120
H (seconds)
530 530 530 530 530
J (seconds)
60 60 60 60 60
K (pulse)
480 480 480 480 480
L (pulse)
250 400 480 400 480
M (pulse)
300 400 480 400 480
N (pulse)
300 400 480 400 480
P (pulse)
160 160 240 160 240
Q (pulse)
50 50 190 50 190
R (pulse)
50 0 240 0 240
S (hours)
6 6 12 6 12
T (°C)
0 0 2 0 2
U (°C)
0 0 0 0 0
Compressor
speed
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 rps 0 rps
D rps
E rps
5 sec.
PI control
5 sec.
J sec.
F sec.
G sec.
H sec.
Electronic
expansion valve
opening
(operating room)
Electronic
expansion valve
opening (stop
room)
Normal
control
K pulse
zone
P pulse
zone
N pulse
zone
L pulse
zone
M pulse
zone
Starting
control
Normal
control
Q pulse zone R pulse
zone
Starting
control
background
Control Specification SiUS122410EA
64 Part 4 Functions and Control
2MXM
Outdoor heat exchanger temperature of Defrost IN
Outdoor heat exchanger temperature of Defrost OUT
Compressor
speed [rps]
Outdoor temperature (°F)
Outdoor
temperature (°F)
Outdoor
heat exchanger
temperature
(°F)
5.0 14.0 19.4 32.0 35.6 44.6
6 3.5 10.1 14.1 23.3 26.0 28.4 44.6 48.3
8 3.3 9.9 13.9 23.1 25.8 28.4 42.8 49.6
10 3.1 9.7 13.7 22.9 25.6 28.4 41.0 50.9
12 2.9 9.5 13.5 22.7 25.4 28.4 39.2 52.1
14 2.7 9.3 13.3 22.5 25.2 28.4 37.4 53.4
16 2.5 9.1 13.1 22.3 25.0 28.4 35.6 53.6
18 2.3 8.9 12.9 22.1 24.8 28.4 33.8 53.6
20 2.1 8.7 12.7 21.9 24.6 28.4 32.0 53.6
22 1.9 8.5 12.5 21.7 24.4 28.4 30.2 53.6
24 1.7 8.3 12.3 21.5 24.2 28.4 28.4 53.6
26 1.5 8.1 12.1 21.3 24.0 28.4 26.6 53.6
28 1.3 7.9 11.9 21.1 23.8 28.4 24.8 53.6
30 1.1 7.7 11.7 20.9 23.6 28.4 23.0 53.6
32 0.9 7.5 11.5 20.8 23.4 28.4 21.2 53.6
34 0.7 7.3 11.3 20.6 23.2 28.4 19.4 53.6
36 0.5 7.1 11.1 20.4 23.0 28.4 17.6 53.6
38 0.3 6.9 10.9 20.2 22.8 28.4 15.8 53.6
40 0.1 6.7 10.7 20.0 22.6 28.4 14.0 53.6
42 –0.1 6.5 10.5 19.8 22.4 28.4 12.2 53.6
44 –0.3 6.4 10.3 19.6 22.2 28.4 10.4 53.6
46 –0.5 6.2 10.1 19.4 22.0 28.4 8.6 53.6
48 –0.7 6.0 9.9 19.2 21.8 28.4 6.8 53.6
50 –0.9 5.8 9.7 19.0 21.6 28.2 5.0 53.6
52 –1.0 5.6 9.5 18.8 21.4 28.0
54 –1.2 5.4 9.3 18.6 21.2 27.8
56 –1.4 5.2 9.1 18.4 21.0 27.6
58 –1.6 5.0 8.9 18.2 20.8 27.4
60 –1.8 4.8 8.7 18.0 20.6 27.2
62 –2.0 4.6 8.5 17.8 20.4 27.1
64 –2.2 4.4 8.3 17.6 20.2 26.9
66 –2.4 4.2 8.2 17.4 20.0 26.7
68 –2.6 4.0 8.0 17.2 19.9 26.5
70 –2.8 3.8 7.8 17.0 19.7 26.3
72 –3.0 3.6 7.6 16.8 19.5 26.1
74 –3.2 3.4 7.4 16.6 19.3 25.9
76 –3.4 3.2 7.2 16.4 19.1 25.7
78 –3.6 3.0 7.0 16.2 18.9 25.5
80 –3.8 2.8 6.8 16.0 18.7 25.3
82 –4.0 2.6 6.6 15.8 18.5 25.1
84 –4.2 2.4 6.4 15.6 18.3 24.9
86 –4.4 2.2 6.2 15.4 18.1 24.7
88 –4.6 2.0 6.0 15.2 17.9 24.5
90 –4.8 1.8 5.8 15.0 17.7 24.3
92 –5.0 1.6 5.6 14.8 17.5 24.1
94 –5.2 1.4 5.4 14.6 17.3 23.9
96 –5.4 1.2 5.2 14.5 17.1 23.7
98 –5.6 1.0 5.0 14.3 16.9 23.5
100 –5.8 0.8 4.8
14.1 16.7 23.3
102 –6.0 0.6 4.6 13.9 16.5 23.1
104 –6.2 0.4 4.4 13.7 16.3 22.9
106 –6.4 0.2 4.2 13.5 16.1 22.7
108 –6.6 0.1 4.0 13.3 15.9 22.5
110 –6.8 –0.1 3.8 13.1 15.7 22.3
112 –7.0 –0.3 3.6 12.9 15.5 22.1
114 –7.2 –0.5 3.4 12.7 15.3 21.9
background
SiUS122410EA Control Specification
Part 4 Functions and Control 65
2MXT(H)
Outdoor heat exchanger temperature of Defrost IN
Outdoor heat exchanger temperature of Defrost OUT
Compressor
speed [rps]
Outdoor temperature (°F)
Outdoor
temperature (°F)
Outdoor
heat exchanger
temperature
(°F)
–13.0 –11.2 –3.1 14.0 19.4 32.0 35.6 44.6
6 –10.2 –8.9 –2.9 9.6 13.6 22.8 25.5 28.4 44.6 48.3
8 –10.6 –9.2 –3.3 9.3 13.2 22.5 25.1 28.4 42.8 49.6
10 –10.9 –9.6 –3.6 8.9 12.9 22.1 24.8 28.4 41.0 50.9
12 –11.3 –9.9 –4.0 8.6 12.5 21.8 24.4 28.4 39.2 52.1
14 –11.6 –10.3 –4.3 8.2 12.2 21.4 24.1 28.4 37.4 53.4
16 –12.0 –10.6 –4.7 7.9 11.8 21.1 23.7 28.4 35.6 53.6
18 –12.3 –11.0 –5.0 7.5 11.5 20.7 23.4 28.4 33.8 53.6
20 –12.7 –11.3 –5.4 7.2 11.1 20.4 23.0 28.4 32.0 53.6
22 –13.0 –11.7 –5.7 6.8 10.8 20.0 22.7 28.4 30.2 53.6
24 –13.4 –12.0 –6.1 6.5 10.4 19.7 22.3 28.4 28.4 53.6
26 –13.7 –12.4 –6.4 6.1 10.1 19.3 22.0 28.4 26.6 53.6
28 –14.1 –12.7 –6.8 5.8 9.7 19.0 21.6 28.2 24.8 53.6
30 –14.4 –13.1 –7.2 5.4 9.4 18.6 21.3 27.9 23.0 53.6
32 –14.8 –13.5 –7.5 5.1 9.0 18.3 20.9 27.5 21.2 53.6
34 –15.1 –13.8 –7.9 4.7 8.7 17.9 20.6 27.2 19.4 53.6
36 –15.5 –14.2 –8.2 4.4 8.3 17.6 20.2 26.8 17.6 53.6
38 –15.8 –14.5 –8.6 4.0 8.0 17.2 19.9 26.5 15.8 53.6
40 –16.2 –14.9 –8.9 3.7 7.6 16.9 19.5 26.1 14.0 53.6
42 –16.5 –15.2 –9.3 3.3 7.3 16.5 19.2 25.8 12.2 53.6
44 –16.9 –15.6 –9.6 2.9 6.9 16.2 18.8 25.4 10.4 53.6
46 –17.2 –15.9 –10.0 2.6 6.6 15.8 18.5 25.1 8.6 53.6
48 –17.6 –16.3 –10.3 2.2 6.2 15.5 18.1 24.7 6.8 53.6
50 –17.9 –16.6 –10.7 1.9 5.9 15.1 17.8 24.4 5.0 53.6
52 –18.3 –17.0 –11.0 1.5 5.5 14.8 17.4 24.0 3.2 53.6
54 –18.6 –17.3 –11.4 1.2 5.2 14.4 17.1 23.7 1.4 53.6
56 –19.0 –17.7 –11.7 0.8 4.8 14.1 16.7 23.3 –0.4 53.6
58 –19.3 –18.0 –12.1 0.5 4.5 13.7 16.3 23.0 –2.2 53.6
60 –19.7 –18.4 –12.4 0.1 4.1 13.4 16.0 22.6 –4.0 53.6
62 –20.0 –18.7 –12.8 –0.2 3.7 13.0 15.6 22.3 –5.8 53.6
64 –20.4 –19.1 –13.1 –0.6 3.4 12.7 15.3 21.9 –7.6 53.6
66 –20.7 –19.4 –13.5 –0.9 3.0 12.3 14.9 21.6 –9.4 53.6
68 –21.1 –19.8 –13.8 –1.3 2.7 11.9 14.6 21.2 –11.2 53.6
70 –21.5 –20.1 –14.2 –1.6 2.3 11.6 14.2 20.8 –13.0 53.6
72 –21.8 –20.5 –14.5 –2.0 2.0 11.2 13.9 20.5
74 –22.0 –20.8 –14.9 –2.3
1.6 10.9 13.5 20.1
76 –22.0 –21.2 –15.2 –2.7 1.3 10.5 13.2 19.8
78 –22.0 –21.5 –15.6 –3.0 0.9 10.2 12.8 19.4
80 –22.0 –21.9 –15.9 –3.4 0.6 9.8 12.5 19.1
82 –22.0 –22.0 –16.3 –3.7 0.2 9.5 12.1 18.7
84 –22.0 –22.0 –16.6 –4.1 –0.1 9.1 11.8 18.4
86 –22.0 –22.0 –17.0 –4.4 –0.5 8.8 11.4 18.0
88 –22.0 –22.0 –17.3 –4.8 –0.8 8.4 11.1 17.7
90 –22.0 –22.0 –17.7 –5.1 –1.2 8.1 10.7 17.3
92 –22.0 –22.0 –18.0 –5.5 –1.5 7.7 10.4 17.0
94 –22.0 –22.0 –18.4 –5.8 –1.9 7.4 10.0 16.6
96 –22.0 –22.0 –18.8 –6.2 –2.2 7.0 9.7 16.3
98 –22.0 –22.0 –19.1 –6.5 –2.6 6.7 9.3 15.9
100 –22.0 –22.0 –19.5 –6.9 –2.9 6.3 9.0 15.6
102 –22.0 –22.0 –19.8 –7.2 –3.3 6.0 8.6 15.2
104 –22.0 –22.0 –20.2 –7.6 –3.6 5.6 8.3 14.9
106 –22.0 –22.0 –20.5 –8.0 –4.0 5.3 7.9 14.5
108 –22.0 –22.0 –20.9 –8.3 –4.3 4.9 7.6 14.2
110 –22.0 –22.0 –21.2 –8.7 –4.7 4.6 7.2 13.8
112 –22.0 –22.0 –21.6 –9.0 –5.0 4.2 6.9 13.5
114 –22.0 –22.0 –21.9 –9.4 –5.4 3.9 6.5 13.1
background
Control Specification SiUS122410EA
66 Part 4 Functions and Control
3/4MXM
Outdoor heat exchanger temperature of Defrost IN
Outdoor heat exchanger temperature of Defrost OUT
Compressor
speed [rps]
Outdoor temperature (°F)
Outdoor
temperature (°F)
Outdoor
heat exchanger
temperature
(°F)
5.0 14.0 19.4 32.0 35.6 44.6
6 3.0 9.6 13.6 22.8 25.5 28.4 44.6 48.3
8 2.7 9.3 13.2 22.5 25.1 28.4 42.8 49.6
10 2.3 8.9 12.9 22.1 24.8 28.4 41.0 50.9
12 2.0 8.6 12.5 21.8 24.4 28.4 39.2 52.1
14 1.6 8.2 12.2 21.4 24.1 28.4 37.4 53.4
16 1.3 7.9 11.8 21.1 23.7 28.4 35.6 53.6
18 0.9 7.5 11.5 20.7 23.4 28.4 33.8 53.6
20 0.6 7.2 11.1 20.4 23.0 28.4 32.0 53.6
22 0.2 6.8 10.8 20.0 22.7 28.4 30.2 53.6
24 –0.1 6.5 10.4 19.7 22.3 28.4 28.4 53.6
26 –0.5 6.1 10.1 19.3 22.0 28.4 26.6 53.6
28 –0.9 5.8 9.7 19.0 21.6 28.2 24.8 53.6
30 –1.2 5.4 9.4 18.6 21.3 27.9 23.0 53.6
32 –1.6 5.1 9.0 18.3 20.9 27.5 21.2 53.6
34 –1.9 4.7 8.7 17.9 20.6 27.2 19.4 53.6
36 –2.3 4.4 8.3 17.6 20.2 26.8 17.6 53.6
38 –2.6 4.0 8.0 17.2 19.9 26.5 15.8 53.6
40 –3.0 3.7 7.6 16.9 19.5 26.1 14.0 53.6
42 –3.3 3.3 7.3 16.5 19.2 25.8 12.2 53.6
44 –3.7 2.9 6.9 16.2 18.8 25.4 10.4 53.6
46 –4.0 2.6 6.6 15.8 18.5 25.1 8.6 53.6
48 –4.4 2.2 6.2 15.5 18.1 24.7 6.8 53.6
50 –4.7 1.9 5.9 15.1 17.8 24.4 5.0 53.6
52 –5.1 1.5 5.5 14.8 17.4 24.0
54 –5.4 1.2 5.2 14.4 17.1 23.7
56 –5.8 0.8 4.8 14.1 16.7 23.3
58 –6.1 0.5 4.5 13.7 16.3 23.0
60 –6.5 0.1 4.1 13.4 16.0 22.6
62 –6.8 –0.2 3.7 13.0 15.6 22.3
64 –7.2 –0.6 3.4 12.7 15.3 21.9
66 –7.5 –0.9 3.0 12.3 14.9 21.6
68 –7.9 –1.3 2.7 11.9 14.6 21.2
70 –8.2 –1.6 2.3 11.6 14.2 20.8
72 –8.6 –2.0 2.0 11.2 13.9 20.5
74 –8.9 –2.3 1.6 10.9 13.5 20.1
76 –9.3 –2.7 1.3 10.5 13.2 19.8
78 –9.6 –3.0 0.9 10.2 12.8 19.4
80 –10.0 –3.4 0.6 9.8 12.5 19.1
82 –10.3 –3.7 0.2 9.5 12.1 18.7
84 –10.7 –4.1 –0.1 9.1 11.8 18.4
86 –11.0 –4.4 –0.5 8.8 11.4 18.0
88 –11.4 –4.8 –0.8 8.4 11.1 17.7
90 –11.7 –5.1 –1.2 8.1 10.7 17.3
92 –12.1 –5.5 –1.5 7.7 10.4 17.0
94 –12.5 –5.8 –1.9 7.4 10.0 16.6
96 –12.8 –6.2 –2.2 7.0 9.7 16.3
98 –13.2 –6.5 –2.6 6.7 9.3 15.9
100 –13.5 –6.9 –2.9
6.3 9.0 15.6
102 –13.9 –7.2 –3.3 6.0 8.6 15.2
104 –14.2 –7.6 –3.6 5.6 8.3 14.9
106 –14.6 –8.0 –4.0 5.3 7.9 14.5
108 –14.9 –8.3 –4.3 4.9 7.6 14.2
110 –15.3 –8.7 –4.7 4.6 7.2 13.8
112 –15.6 –9.0 –5.0 4.2 6.9 13.5
114 –16.0 –9.4 –5.4 3.9 6.5 13.1
background
SiUS122410EA Control Specification
Part 4 Functions and Control 67
5MXM
Outdoor heat exchanger temperature of Defrost IN
Outdoor heat exchanger temperature of Defrost OUT
Compressor
speed [rps]
Outdoor temperature (°F)
Outdoor
temperature (°F)
Outdoor
heat exchanger
temperature
(°F)
5.0 14.0 19.4 32.0 35.6 44.6
6 4.6 12.4 17.0 27.9 28.4 28.4 44.6 48.3
8 4.5 12.2 16.8 27.7 28.4 28.4 42.8 49.6
10 4.3 12.0 16.7 27.5 28.4 28.4 41.0 50.9
12 4.1 11.8 16.5 27.3 28.4 28.4 39.2 52.1
14 3.9 11.7 16.3 27.1 28.4 28.4 37.4 53.4
16 3.7 11.5 16.1 26.9 28.4 28.4 35.6 53.6
18 3.6 11.3 15.9 26.8 28.4 28.4 33.8 53.6
20 3.4 11.1 15.7 26.6 28.4 28.4 32.0 53.6
22 3.2 10.9 15.6 26.4 28.4 28.4 30.2 53.6
24 3.0 10.7 15.4 26.2 28.4 28.4 28.4 53.6
26 2.8 10.6 15.2 26.0 28.4 28.4 26.6 53.6
28 2.6 10.4 15.0 25.8 28.4 28.4 24.8 53.6
30 2.5 10.2 14.8 25.7 28.4 28.4 23.0 53.6
32 2.3 10.0 14.6 25.5 28.2 28.4 21.2 53.6
34 2.1 9.8 14.5 25.3 28.0 28.4 19.4 53.6
36 1.9 9.6 14.3 25.1 27.9 28.4 17.6 53.6
38 1.7 9.5 14.1 24.9 27.7 28.4 15.8 53.6
40 1.5 9.3 13.9 24.7 27.5 28.4 14.0 53.6
42 1.4 9.1 13.7 24.6 27.3 28.4 12.2 53.6
44 1.2 8.9 13.6 24.4 27.1 28.4 10.4 53.6
46 1.0 8.7 13.4 24.2 27.0 28.4 8.6 53.6
48 0.8 8.5 13.2 24.0 26.8 28.4 6.8 53.6
50 0.6 8.4 13.0 23.8 26.6 28.4 5.0 53.6
52 0.4 8.2 12.8 23.6 26.4 28.4
54 0.3 8.0 12.6 23.5 26.2 28.4
56 0.1 7.8 12.5 23.3 26.0 28.4
58 –0.1 7.6 12.3 23.1 25.9 28.4
60 –0.3 7.4 12.1 22.9 25.7 28.4
62 –0.5 7.3 11.9 22.7 25.5 28.4
64 –0.7 7.1 11.7 22.6 25.3 28.4
66 –0.8 6.9 11.5 22.4 25.1 28.4
68 –1.0 6.7 11.4 22.2 24.9 28.4
70 –1.2 6.5 11.2 22.0 24.8 28.4
72 –1.4 6.4 11.0 21.8 24.6 28.4
74 –1.6 6.2 10.8 21.6 24.4 28.4
76 –1.8 6.0 10.6 21.5 24.2 28.4
78 –1.9 5.8 10.4 21.3 24.0 28.4
80 –2.1 5.6 10.3 21.1 23.8 28.4
82 –2.3 5.4 10.1 20.9 23.7 28.4
84 –2.5 5.3 9.9 20.7 23.5 28.4
86 –2.7 5.1 9.7 20.5 23.3 28.4
88 –2.8 4.9 9.5 20.4 23.1 28.4
90 –3.0 4.7 9.3 20.2 22.9 28.4
92 –3.2 4.5 9.2 20.0 22.7 28.4
94 –3.4 4.3 9.0 19.8 22.6 28.4
96 –3.6 4.2 8.8 19.6 22.4 28.4
98 –3.8 4.0 8.6 19.4 22.2 28.4
100 –3.9 3.8 8.4
19.3 22.0 28.4
102 –4.1 3.6 8.2 19.1 21.8 28.4
104 –4.3 3.4 8.1 18.9 21.7 28.4
106 –4.5 3.2 7.9 18.7 21.5 28.4
108 –4.7 3.1 7.7 18.5 21.3 28.2
110 –4.9 2.9 7.5 18.3 21.1 28.0
112 –5.0 2.7 7.3 18.2 20.9 27.8
114 –5.2 2.5 7.2 18.0 20.7 27.6
background
Control Specification SiUS122410EA
68 Part 4 Functions and Control
3/4/5MXT(H)
Outdoor heat exchanger temperature of Defrost IN
Outdoor heat exchanger temperature of Defrost OUT
Compressor
speed [rps]
Outdoor temperature (°F)
Outdoor
temperature (°F)
Outdoor
heat exchanger
temperature
(°F)
–13.0 –11.2 –3.1 14.0 19.4 32.0 35.6 44.6
6 –10.8 –9.3 –2.3 12.4 17.0 27.9 28.4 28.4 44.6 48.3
8 –11.0 –9.5 –2.5 12.2 16.8 27.7 28.4 28.4 42.8 49.6
10 –11.2 –9.6 –2.7 12.0 16.7 27.5 28.4 28.4 41.0 50.9
12 –11.4 –9.8 –2.9 11.8 16.5 27.3 28.4 28.4 39.2 52.1
14 –11.6 –10.0 –3.0 11.7 16.3 27.1 28.4 28.4 37.4 53.4
16 –11.7 –10.2 –3.2 11.5 16.1 26.9 28.4 28.4 35.6 53.6
18 –11.9 –10.4 –3.4 11.3 15.9 26.8 28.4 28.4 33.8 53.6
20 –12.1 –10.6 –3.6 11.1 15.7 26.6 28.4 28.4 32.0 53.6
22 –12.3 –10.7 –3.8 10.9 15.6 26.4 28.4 28.4 30.2 53.6
24 –12.5 –10.9 –4.0 10.7 15.4 26.2 28.4 28.4 28.4 53.6
26 –12.6 –11.1 –4.1 10.6 15.2 26.0 28.4 28.4 26.6 53.6
28 –12.8 –11.3 –4.3 10.4 15.0 25.8 28.4 28.4 24.8 53.6
30 –13.0 –11.5 –4.5 10.2 14.8 25.7 28.4 28.4 23.0 53.6
32 –13.2 –11.7 –4.7 10.0 14.6 25.5 28.2 28.4 21.2 53.6
34 –13.4 –11.8 –4.9 9.8 14.5 25.3 28.0 28.4 19.4 53.6
36 –13.6 –12.0 –5.1 9.6 14.3 25.1 27.9 28.4 17.6 53.6
38 –13.7 –12.2 –5.2 9.5 14.1 24.9 27.7 28.4 15.8 53.6
40 –13.9 –12.4 –5.4 9.3 13.9 24.7 27.5 28.4 14.0 53.6
42 –14.1 –12.6 –5.6 9.1 13.7 24.6 27.3 28.4 12.2 53.6
44 –14.3 –12.7 –5.8 8.9 13.6 24.4 27.1 28.4 10.4 53.6
46 –14.5 –12.9 –6.0 8.7 13.4 24.2 27.0 28.4 8.6 53.6
48 –14.7 –13.1 –6.2 8.5 13.2 24.0 26.8 28.4 6.8 53.6
50 –14.8 –13.3 –6.3 8.4 13.0 23.8 26.6 28.4 5.0 53.6
52 –15.0 –13.5 –6.5 8.2 12.8 23.6 26.4 28.4 3.2 53.6
54 –15.2 –13.7 –6.7 8.0 12.6 23.5 26.2 28.4 1.4 53.6
56 –15.4 –13.8 –6.9 7.8 12.5 23.3 26.0 28.4 –0.4 53.6
58 –15.6 –14.0 –7.1 7.6 12.3 23.1 25.9 28.4 –2.2 53.6
60 –15.8 –14.2 –7.2 7.4 12.1 22.9 25.7 28.4 –4.0 53.6
62 –15.9 –14.4 –7.4 7.3 11.9 22.7 25.5 28.4 –5.8 53.6
64 –16.1 –14.6 –7.6 7.1 11.7 22.6 25.3 28.4 –7.6 53.6
66 –16.3 –14.8 –7.8 6.9 11.5 22.4 25.1 28.4 –9.4 53.6
68 –16.5 –14.9 –8.0 6.7 11.4 22.2 24.9 28.4 –11.2 53.6
70 –16.7 –15.1 –8.2 6.5 11.2 22.0 24.8 28.4 –13.0 53.6
72 –16.9 –15.3 –8.3 6.4 11.0 21.8 24.6 28.4
74 –17.0 –15.5 –8.5 6.2
10.8 21.6 24.4 28.4
76 –17.2 –15.7 –8.7 6.0 10.6 21.5 24.2 28.4
78 –17.4 –15.9 –8.9 5.8 10.4 21.3 24.0 28.4
80 –17.6 –16.0 –9.1 5.6 10.3 21.1 23.8 28.4
82 –17.8 –16.2 –9.3 5.4 10.1 20.9 23.7 28.4
84 –18.0 –16.4 –9.4 5.3 9.9 20.7 23.5 28.4
86 –18.1 –16.6 –9.6 5.1 9.7 20.5 23.3 28.4
88 –18.3 –16.8 –9.8 4.9 9.5 20.4 23.1 28.4
90 –18.5 –17.0 –10.0 4.7 9.3 20.2 22.9 28.4
92 –18.7 –17.1 –10.2 4.5 9.2 20.0 22.7 28.4
94 –18.9 –17.3 –10.4 4.3 9.0 19.8 22.6 28.4
96 –19.0 –17.5 –10.5 4.2 8.8 19.6 22.4 28.4
98 –19.2 –17.7 –10.7 4.0 8.6 19.4 22.2 28.4
100 –19.4 –17.9 –10.9 3.8 8.4 19.3 22.0 28.4
102 –19.6 –18.0 –11.1 3.6 8.2 19.1 21.8 28.4
104 –19.8 –18.2 –11.3 3.4 8.1 18.9 21.7 28.4
106 –20.0 –18.4 –11.5 3.2 7.9 18.7 21.5 28.4
108 –20.1 –18.6 –11.6 3.1 7.7 18.5 21.3 28.2
110 –20.3 –18.8 –11.8 2.9 7.5 18.3 21.1 28.0
112 –20.5 –19.0 –12.0 2.7 7.3 18.2 20.9 27.8
114 –20.7 –19.1 –12.2 2.5 7.2 18.0 20.7 27.6
background
SiUS122410EA Control Specification
Part 4 Functions and Control 69
2.13 Low Compressor Speed High Pressure Limit
Outline The system controls the upper limit of the compressor speed to prevent abnormal high pressure
while the compressor speed is low. Control is carried out according to three zones.
Details
R4004267
Cooling
A (°C) = D × target compressor speed + E × Lowest indoor heat exchanger temperature among
operating rooms + F
Heating
A (°C) = G × target compressor speed + H × outdoor heat exchanger + J
A 56°C (When the above is 56°C or higher)
B (°C): A – 1 (°C)
C (°C): A – 4 (°C)
2MXM
3/4MXM, 2MXT(H)
5MXM, 3/4/5MXT(H)
Target Compressor
speed 8
16 Target Compressor
speed 14
21 Target Compressor
speed 30
D 224/256 546/256 96/256
E 0/256 0/256 0/256
F 34.5 24.5 49
G 224/256 546/256 96/256
H 0/256 0/256 0/256
J 34.5 24.5 49
Target Compressor
speed 15
16 Target Compressor
speed 20
21 Target Compressor
speed 25
D 0/256 312/256 512/256
E 0/256 0/256 0/256
F 43.5 25.5 10
G 0/256 312/256 512/256
H 0/256 0/256 0/256
J 43.5 25.5 10
Target Compressor
speed 16
16 Target Compressor
speed 21
21 Target Compressor
speed 25
D 90/256 130/256 220/256
E 90/256 90/256 60/256
F 32.5 30.5 27.5
G 90/256 130/256 220/256
H 90/256 90/256 60/256
J 32.5 30.5 27.5
A
B
C
(Heating)
Highest indoor heat exchanger
temperature among operating rooms
(Cooling)
Outdoor heat exchanger temperature
(calculated from pressure sensor)
Reset zone
Dropping zone
Keep
zone
background
Control Specification SiUS122410EA
70 Part 4 Functions and Control
2.14 Electronic Expansion Valve Control
Outline The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Room Distribution Control
1. Gas pipe isothermal control
2. SC (subcooling) control
3. Liquid pipe temperature control (with all ports connected and all rooms being
air-conditioned)
4. Liquid pipe temperature control for rooms not in operation
5. Dew prevention control for indoor rotor
Open Control
1. Electronic expansion valve control when starting operation
2. Electronic expansion valve control when the compressor speed changes
3. Electronic expansion valve control for defrosting
4. Electronic expansion valve control for oil recovery
5. Electronic expansion valve control when a discharge pipe temperature is abnormally high
6. Electronic expansion valve control when the discharge pipe thermistor is disconnected
7. Electronic expansion valve control for indoor unit anti-icing control
Feedback Control
Target discharge pipe temperature control
Details The following are the examples of the electronic expansion valve control for each operation
mode.
background
SiUS122410EA Control Specification
Part 4 Functions and Control 71
R4004269
Fully closed when power is turned on
Open control when starting
(Control of target discharge pipe
temperature)
Control when the operating room is
changed
(Control of target discharge pipe
temperature)
Pressure equalizing control
Open control when starting
(Control of target discharge pipe
temperature)
Control when the operating room is
changed
(Control of target discharge pipe
temperature)
(Defrost control)
Pressure equalizing control
Open control when starting
Continue
Pressure equalizing control
Operation pattern
When power is turned on
Cooling, 1 room operation
Cooling, 2 rooms operation to
Cooling, 4 rooms operation
Stop
Heating, 1 room operation
Heating, 2 rooms operation
Stop
Heating operation
Discharge pipe thermistor
disconnection control
Stop
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
+2
—
+2
—
—
—
+2
—
—
—
—
—
—
—
—
+1
—
+1
—
—
—
+1
—
—
—
—
—
—
—
—
+3
—
+3
—
—
—
+3
—
Gas pipe isothermal control
SC (subcooling) control
Control when the compressor
speed changes
Control for abnormally high discharge
pipe temperature
Oil recovery control
Indoor anti-icing control
Liquid pipe temperature control
Liquid pipe temperature control for
non-operating units
Dew prevention control for
indoor rotor
: Available
— : Not available
1: When all the indoor units are operating, liquid pipe temperature control is conducted.
2: SC (subcooling) control is conducted for the operating indoor units, when some of the units are not operating.
3: Liquid pipe temperature control for stopped room is conducted for the non-operating indoor units.
background
Control Specification SiUS122410EA
72 Part 4 Functions and Control
2.14.1 Initialization as Power Supply On
The electronic expansion valve is initialized (fully closed) when the power is turned on. Then,
the valve opening position is set and the pressure is equalized.
2.14.2 Pressure Equalizing Control
When the compressor is stopped, the pressure equalizing control is activated. The electronic
expansion valve opens, and develops the pressure equalization.
2.14.3 Opening Limit Control
The maximum and minimum opening of the electronic expansion valve are limited.
The electronic expansion valve is fully closed in the room where cooling is stopped and is
opened at a fixed degree during defrosting.
2.14.4 Starting Operation Control/Changing Operation Room
The electronic expansion valve opening is controlled when the operation starts, thus preventing
superheating or liquid compression.
2.14.5 Control when the Compressor Speed Changes
When the target discharge pipe temperature control is active, if the target compressor speed
changes to a specified value in a certain period of time, the target discharge pipe temperature
control is canceled and the target opening of the electronic expansion valve is changed.
2.14.6 Oil Recovery Function
Outline The electronic expansion valve opening for the room not in operation is set as to open for a
certain time at a specified interval so that the oil for the room not in operation may not be
accumulated.
Details During cooling operation, the electronic expansion valve for the room not in operation is opened
every 1 hour by 80 pulses for specified time.
2.14.7 High Discharge Pipe Temperature Control
When the compressor is operating, if the discharge pipe temperature exceeds a certain value,
the electronic expansion valve opens and the refrigerant runs to the low pressure side.
This procedure lowers the discharge pipe temperature.
2/3/4MXM
2MXT(H)
5MXM
3/4/5MXT(H)
Max. valve opening (pulse) 480 480
Min. valve opening (pulse) 42 44
* In the room the unit is in operation
background
SiUS122410EA Control Specification
Part 4 Functions and Control 73
2.14.8 Discharge Pipe Thermistor Disconnection Control
Outline The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe
temperature with the condensing temperature. If the discharge pipe thermistor is disconnected,
the electronic expansion valve opens according to the outdoor temperature and the operation
compressor speed, operates for a specified time, and then stops.
After 3 minutes, the operation restarts and checks if the discharge pipe thermistor is
disconnected. If the discharge pipe thermistor is disconnected, the system stops after operating
for a specified time.
If the disconnection is detected repeatedly, the system is shut down. When the compressor runs
for 60 minutes without any error, the error counter is reset.
Details Determining thermistor disconnection
When the starting control (A seconds) finishes, the following adjustment is made.
1. When the operation mode is cooling
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe temperature + 6°C (10.8°F) < outdoor heat exchanger temperature
2. When the operation mode is heating
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe temperature + 6°C (10.8°F) < highest indoor heat exchanger temperature
When the thermistor is disconnected
When the disconnection is ascertained, the compressor continues operation for 9 minutes and
then stops.
2.14.9 Gas Pipe Isothermal Control During Cooling
When the units are operating in multiple rooms, the gas pipe temperature is detected and the
electronic expansion valve opening is adjusted so that the temperature of the gas pipe in each
room becomes equal.
When the gas pipe temperature > the average gas pipe temperature,
the opening degree of electronic expansion valve for the corresponding room increases.
When the gas pipe temperature < the average gas pipe temperature,
the opening degree of electronic expansion valve for the corresponding room decreases.
The temperatures are monitored every A seconds.
2MXM
3/4MXM
2MXT(H)
5MXM
3/4/5MXT(H)
A (seconds) 630 930 1,150
2/3/4MXM
2MXT(H)
5MXM
3/4/5MXT(H)
A (seconds) 40 30
background
Control Specification SiUS122410EA
74 Part 4 Functions and Control
2.14.10 SC (Subcooling) Control
When the units are operating in multiple rooms, the gas pipe temperature is detected and the
electronic expansion valve opening is adjusted so that the temperature of the gas pipe in each
room becomes equal.
When the gas pipe temperature > the average gas pipe temperature,
the opening degree of electronic expansion valve for the corresponding room increases.
When the gas pipe temperature < the average gas pipe temperature,
the opening degree of electronic expansion valve for the corresponding room decreases.
The temperatures are monitored every A seconds.
2.14.11 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual
discharge pipe temperature becomes close to the target discharge pipe temperature. (Indirect
SH (superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every A seconds. The target discharge pipe temperature is controlled by indoor heat exchanger
temperature and outdoor heat exchanger temperature. The opening degree of the electronic
expansion valve is adjusted by the following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
2MXM 3/4MXM 5MXM 2MXT(H) 3/4/5MXT(H)
A (seconds) 20 60 45 60 45
2/3/4MXM
2MXT(H)
5MXM
3/4/5MXT(H)
A (seconds) 20 15
SC
(Subcooling)
SH
(Superheating)
The target discharge pipe
temperature is set as to become
the target SH.
The inclination does not change
depending on the operating condition.
(R23014)
background
SiUS122410EA Control Specification
Part 4 Functions and Control 75
2.15 Malfunctions
2.15.1 Sensor Malfunction Detection
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Gas pipe thermistor
5. Outdoor temperature thermistor
6. Liquid pipe thermistor
2.15.2 Detection of Overcurrent and Overload
Outline In order to protect the inverter, an excessive output current is detected and the OL temperature
is observed to protect the compressor.
Details If the inverter current exceeds A A, the system shuts down the compressor.
If the OL (Compressor head) temperature exceeds B°C (°F), the compressor stops.
2.15.3 Anti-icing Function
During cooling, if the indoor heat exchanger temperature in the room not in operation becomes
below the specified temperature for the specified time, the electronic expansion valve is opened
in the operation stopped room as specified, and the fully closed operation is carried out. After
this, if freezing abnormality occurs longer than specified time, the system shuts down as the
system abnormality.
2MXM 3/4MXM 5MXM 2MXT(H) 3MXT(H) 4/5MXT(H)
A (A) Cooling 13.0 19.0 27.5 19.0 27.0 27.5
Heating 15.0 19.0 29.0 19.0 27.0 29.0
B (°C) 125 125 125 125 125 125
(°F) 257 257 257 257 257 257
background
SiUS122410EA
76 Part 5 Remote Controller
1. Applicable Remote Controller ...............................................................77
2. ARC480A83 ..........................................................................................78
3. BRC073A6 ............................................................................................80
4. BRC944B2 ............................................................................................84
Part 5
Remote Controller
background
SiUS122410EA Applicable Remote Controller
Part 5 Remote Controller 77
Note
1. Applicable Remote Controller
Refer to the operation manual of applicable model for details. You can download operation
manuals from Daikin Business Portal:
Daikin Business Portal Document Search Item Category Installation/Operation Manual
(URL: https://global1d.daikin.com/business_portal/login/
)
Model Name Wireless R/C
Reference
Page
Wired R/C
Reference
Page
CTXV07AVJU9
ARC480A83 78
BRC073A6
BRC944B2
80
84
FTXV09AVJU9
FTXV12AVJU9
FTXV15AVJU9
FTXV18AVJU9
FTXV24AVJU9
background
ARC480A83 SiUS122410EA
78 Part 5 Remote Controller
2. ARC480A83
R5000453
Signal transmitter
Receiver
• To use the remote controller, aim the
transmitter at the indoor unit. If there
is anything blocking the signals
between the unit and the remote
controller, such as a curtain, the unit
may not operate.
• The maximum transmission distance
is about 23 ft. (7 m).
OFF button
• Press this button once to stop the
operation.
Display (LCD)
• Displays the current settings.
(In this illustration, each section is
shown with all its displays on for the
purpose of explanation.)
• Selects an appropriate operation
mode (COOL or HEAT) automatically
based on the indoor temperature and
starts the operation.
AUTO button
• Starts the COOL, DRY, HEAT or
FAN ONLY operation.
Direct operation buttons
background
SiUS122410EA ARC480A83
Part 5 Remote Controller 79
Reference
R5000461
Refer to the following pages for details.
Airflow rate 1-5 (Low to High)
TIMER CANCEL button
• Cancels the timer setting.
• Adjusts the airflow direction.
• When you press SWING
button, the flap moves up and
down. The flap stops when you
press SWING button again.
SWING
5
buttons
OFF TIMER button
(NIGHT SET mode)
•
Adjusts the OFF TIMER
setting.
•
The timer can be set
1 ~ 12 hours.
ECONO
4
button
• Starts ECONO operation.
COMFORT button
1
• Starts COMFORT AIRFLOW
operation.
ON TIMER button
•
Adjusts the ON TIMER setting.
• The time can be set
1 ~ 12 hours.
• Starts POWERFUL operation.
• Wireless LAN connection.
POWERFUL
2
button
and Wireless LAN
3
button
(push 5 seconds)
FAN setting button
• Selects the airflow rate setting
every time you press this button.
• In indoor unit quiet operation,
operation sound becomes weak.
(The airflow rate also decreases.)
• In DRY operation, the airflow rate
setting is not available.
• Changes the temperature
setting.
TEMPERATURE
adjustment buttons
: AUTO
: DRY
: COOL
: HEAT
: FAN
18 ~ 30 °C
(64 ~ 86 °F)
Not available
18 ~ 32 °C
(64 ~ 90 °F)
10 ~ 30 °C
(50 ~ 86 °F)
Not available
AUTO
Indoor unit quiet
1 COMFORT AIRFLOW operation P.37
2 POWERFUL operation P.43
3 Wireless LAN connection P.45
4 ECONO operation P.42
5 Auto-swing P.36
background
BRC073A6 SiUS122410EA
80 Part 5 Remote Controller
3. BRC073A6
2. Fan Speed/Airflow
Direction button
3. Menu/Enter button
8. ON/OFF button
10. Cancel button
9. Operation lamp
11. LCD (with backlight)
4. Up button
5. Down button
6. Right button
7. Left button
1. Operation Mode
Selector button
background
SiUS122410EA BRC073A6
Part 5 Remote Controller 81
• Press this button to select the operation
mode of your preference.
• Available modes may vary with the
connected model.
1. Operation Mode Selector button
• Used to change the fan speed and airflow
direction.
• Available fan speeds and airflow directions
may vary with the connected model.
2. Fan Speed/Airflow Direction
button
• This button is enabled by default.
• Used to display the Main Menu or enter
the selected item.
3. Menu/Enter button
• Used to raise the set temperature.
• The next item on the upper side will be
highlighted.
(Keep pressing the button to cycle through
the values or items).
• Used to change the selected item.
4. Up button
• Used to lower the set temperature.
• The next item on the lower side will be
highlighted.
(Keep pressing the button to cycle through
the values or items).
• Used to change the selected item.
5. Down button
• Used to highlight the next items on the
right-hand side.
• The display contents are changed to the
next screen.
• Used to highlight the next items on the
left-hand side.
• The display contents are changed to the
previous screen.
• This lamp lights up during operation.
• This lamp is not lit when the unit operation
is OFF.
• This lamp blink if an error or mode conflict
occurs.
• This button is enabled by default.
• Used to return to the previous screen.
• Press to start or stop the air conditioner.
6. Right button
7. Left button
8. ON/OFF button
9. Operation lamp (Green)
10. Cancel button
• The backlight will be lit for approximately
30
seconds when one of the buttons is
pressed.
• The actions linked to the buttons, except
for the ON/OFF button, are not carried out
when the backlight is not lit.
11. LCD (with backlight)
background
BRC073A6 SiUS122410EA
82 Part 5 Remote Controller
Liquid Crystal Display
• There are four display methods for the liquid crystal display (LCD) available. The
Standard display, which is used by default, and the Detailed display. There is also the
possibility to use only Icon or Icon and Text mode (see the Installation manual).
• To change the active display method, select the desired display method in the Display
Method screen.
• The displayed contents on the screen may vary with the operation mode of the
connected models. (E.g.: The following display will appear when the air conditioner is
in heating operation).
Standard display
Detailed display
The clock and Detailed selection items appear on the Detailed
display in addition to the items appearing on the Standard display.
With icons With icons and text (default)
82
°F
5
7
4
6
8
3
2
1
82
°F
Heat
Error: Push Menu button
5
7
4
6
8
3
2
1
Set to
With icons With icons and text
10
9
4
Mon
68
82
F
F
5
:
58
P
10
9
Mon
5
:
58
P
3
4
11
Error: Push Menu button
Heat
2
Set to Room
82
F
F
68
background
SiUS122410EA BRC073A6
Part 5 Remote Controller 83
1. Operation mode
2. Fan Speed
3. Airflow direction
4. Set/Setback temperature display
Indicates the current operation mode.
Indicates the fan speed that is set for the
air conditioner.
The fan speed will not be displayed if the
air conditioner does not have the fan speed
control function.
Displayed only when the air conditioner is
in operation.
Indicates the airflow direction that is set for
the air conditioner.
The possible directions depend on the
indoor unit.
When the unit is turned ON, the
temperature that is set for the air
conditioner is displayed.
When the unit is turned OFF and Setback
is disabled, the temperature that is set for
the air conditioner is displayed.
When the unit is turned OFF and Setback
is enabled, the temperature that is set for
the setback function is displayed in smaller
digits.
•
•
•
•
•
•
•
•
•
Operation Mode
Cool Heat Auto (Heat)
Fan Dry Auto (Cool)
5. Error “ ”
Indicates a unit error.
•
9. Clock (12/24 hours real time clock)
Indicates that the clock is set.
If the clock is not set, “ -- : -- ” will be
displayed.
•
•
10. Detailed selection
Displayed when the detailed display mode
is selected.
No detailed items are selected by default.
•
•
6. Timer enabled “ ”
Indicates that the schedule timer or the
OFF timer is enabled.
•
7. Under Centralised control “ ”
Indicates that the air conditioner is under
the management of central control
equipment (optional accessories) and the
operation of the system through the remote
controller is prohibited.
•
8. Setback “ ”
The setback icon flashes when the unit is
turned on under the setback control.
•
Indicates that the clock needs to be set
again.
The schedule timer function will not work
unless the clock is set again.
•
•
11. Timer problem “ ”
background
BRC944B2 SiUS122410EA
84 Part 5 Remote Controller
Caution
4. BRC944B2
R5000214
This remote controller cannot be used together with a standard wireless remote controller.
Otherwise, what appears on this remote controller's display may fail to correspond to actual
operating conditions.
background
SiUS122410EA
Part 6 Service Diagnosis 85
1. General Problem Symptoms and Check Items .....................................87
2. Troubleshooting with LED .....................................................................88
2.1 Indoor Unit..............................................................................................88
2.2 Outdoor Unit ...........................................................................................89
3. Service Diagnosis .................................................................................90
3.1 ARC480 Series.......................................................................................90
3.2 BRC073A6 .............................................................................................93
4. Code Indication on Remote Controller ..................................................95
4.1 Indoor Unit..............................................................................................95
4.2 Outdoor Unit ...........................................................................................96
5. Troubleshooting for Indoor Unit.............................................................97
5.1 Indoor Unit PCB Abnormality .................................................................97
5.2 Freeze-up Protection Control/Heating Peak-cut Control ........................98
5.3 Indoor Fan Motor (DC Motor) or Related Abnormality ...........................99
5.4 Indoor Heat Exchanger Thermistor or Related Abnormality.................101
5.5 Room Temperature Sensor Abnormality/Humidity Sensor
Abnormality ..........................................................................................102
5.6 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)....103
5.7 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) .............105
6. Troubleshooting for Outdoor Unit........................................................106
6.1 Refrigerant Shortage ............................................................................106
6.2 Low-voltage Detection or Over-voltage Detection................................109
6.3 Wiring Error Check Unexecuted...........................................................111
6.4 Unspecified Voltage (Between Indoor Unit and Outdoor Unit),
Anti-icing Control in Other Rooms........................................................112
6.5 Anti-icing Control for Indoor Unit ..........................................................113
6.6 Outdoor Unit PCB Abnormality.............................................................115
6.7 Actuation of High Pressure Switch .......................................................116
6.8 OL Activation (Compressor Overload) .................................................117
6.9 Compressor Lock .................................................................................119
6.10 DC Fan Lock ........................................................................................121
6.11 Input Overcurrent Detection .................................................................122
6.12 Electronic Expansion Valve Coil Abnormality.......................................124
6.13 Four Way Valve Abnormality................................................................125
6.14 Discharge Pipe Temperature Control...................................................127
6.15 High Pressure Control in Cooling .........................................................128
6.16 System Shutdown due to Temperature Abnormality in the
Compressor..........................................................................................130
6.17 Compressor Sensor System Abnormality ............................................131
6.18 High Pressure Switch System Abnormality ..........................................133
6.19 Position Sensor Abnormality ................................................................134
6.20 Thermistor or Related Abnormality (Outdoor Unit)...............................136
Part 6
Service Diagnosis
background
SiUS122410EA
86 Part 6 Service Diagnosis
6.21 High Pressure Sensor Abnormality ......................................................138
6.22 Electrical Box Temperature Rise..........................................................139
6.23 Radiation Fin Temperature Rise ..........................................................141
6.24 Output Overcurrent Detection ..............................................................143
7. Check ..................................................................................................146
7.1 Thermistor Resistance Check ..............................................................146
7.2 Indoor Fan Motor Connector Check .....................................................147
7.3 Power Supply Waveform Check...........................................................147
7.4 Electronic Expansion Valve Check.......................................................148
7.5 Four Way Valve Performance Check ...................................................149
7.6 Inverter Unit Refrigerant System Check...............................................149
7.7 Inverter Analyzer Check .......................................................................150
7.8 Outdoor Fan Motor Check....................................................................151
7.9 Installation Condition Check.................................................................152
7.10 Discharge Pressure Check...................................................................152
7.11 Outdoor Fan System Check .................................................................153
7.12 Main Circuit Short Check......................................................................153
7.13 Capacitor Voltage Check......................................................................155
7.14 Power Module Check ...........................................................................156
7.15 High Pressure Sensor Check ...............................................................158
background
SiUS122410EA General Problem Symptoms and Check Items
Part 6 Service Diagnosis 87
1. General Problem Symptoms and Check Items
Symptom Check Item Details
Reference
Page
None of the units
operates.
Check the power supply. Check if the rated voltage is supplied. —
Check the types of the indoor
units.
Check if the indoor unit type is compatible
with the outdoor unit.
—
Check the outdoor temperature. Heating/cooling operations are not
available when the outdoor temperature is
out of the operation limit. Check the
reference page for the operation limit.
194
Diagnose with remote controller
indication
— 95, 96
Check the wireless remote
controller addresses.
Check if address settings for the wireless
remote controller and indoor unit are
correct.
166
Operation sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles can stop
air conditioner operation. (Operation lamp
OFF)
—
Check the outdoor temperature. Heating/cooling operations are not
available when the outdoor temperature is
out of the operation limit. Check the
reference page for the operation limit.
194
Diagnose with remote controller
indication.
— 95, 96
Some indoor units do
not operate.
Check the type of the indoor
units.
Check if the indoor unit type is compatible
with the outdoor unit.
—
Diagnose with remote controller
indication
— 95, 96
Units operate but do not
cool, or do not heat.
Check for wiring and piping
errors in the connection
between the indoor and outdoor
units.
Check the piping.
Conduct the wiring error check described
on the product diagnosis nameplate.
—
Check for thermistor detection
errors.
Check if the thermistor is mounted
securely.
—
Check for faulty operation of the
electronic expansion valve.
Set all the units to cooling operation, and
compare the temperatures of the liquid
pipes to see if the each electronic
expansion valve works.
—
Diagnose with remote controller
indication.
— 95, 96
Diagnose by service port
pressure and operating current.
Check for refrigerant shortage.
106
Large operating noise
and vibrations
Check the installation condition. Check if the required spaces for
installation (specified in the installation
manual) are provided.
—
background
Troubleshooting with LED SiUS122410EA
88 Part 6 Service Diagnosis
2. Troubleshooting with LED
2.1 Indoor Unit
Operation Lamp The operation lamp blinks when any of the following errors is detected.
1. When a protection device of the indoor or outdoor unit is activated, or when the thermistor
malfunctions.
2. When a signal transmission error occurs between the indoor and outdoor units.
In either case, conduct the diagnostic procedure described in the following pages.
07/09/12 class 15/18/24 class
R6001149 R6001150
Operation lamp
(green)
Operation lamp
(green)
background
SiUS122410EA Troubleshooting with LED
Part 6 Service Diagnosis 89
Reference
2.2 Outdoor Unit
The outdoor unit has a green LED (LED A) and red LEDs (LED 1 ~ LED 5) on the PCB.
When the microcomputer works in order, the LED A blinks, and when the system is in normal
condition, the red LEDs are OFF.
Even after the error is canceled and the unit operates in normal condition, the LED indication
remains.
R6001151
This illustration is for the 4MXM-A series as a representative.
Refer to page 28 for the location of LED.
Service monitor PCB
1
12 3
231
12 3
23
A
1
2
3
4
5
LED A
LED 1
LED 2
LED 3
LED 4
LED 5
background
Service Diagnosis SiUS122410EA
90 Part 6 Service Diagnosis
Note(s)
3. Service Diagnosis
3.1 ARC480 Series
3.1.1 Method 1
1. When TIMER CANCEL button is held down for 5 seconds, 00 is displayed on the
temperature display screen.
2. Press TIMER CANCEL button repeatedly until a long beep sounds.
R6001152
1. A short beep or two consecutive beeps indicate non-corresponding codes.
2. To return to the normal mode, hold TIMER CANCEL button down for 5 seconds. When the
remote controller is left untouched for 60 seconds, it also returns to the normal mode.
3. Not all the error codes are displayed. When you cannot find the error code, try method 2.
Refer to page 91.
The code indication changes in the sequence shown below.
ARC480A83
TIMER CANCEL button
< ARC480 Series >
No. Code No. Code No. Code
1 00 16 A3 31 UF
2 A5 17 H8 32 UH
3 E7 18 H9 33 P4
4 F3 19 C9 34 H7
5 F6 20 CC 35 U2
6 L3 21 C4 36 EA
7 L4 22 C5 37 AH
8 L5 23 J3 38 E9
9 U4 24 J6 39 FA
10 E6 25 J8 40 E8
11 H6 26 E5 41 CH
12 H0 27 A1 42 J9
13 A6 28 E1 43 E3
14 U0 29 UA 44 H3
15 C7 30 U3 45 F8
background
SiUS122410EA Service Diagnosis
Part 6 Service Diagnosis 91
3.1.2 Method 2
1. Press the center of TEMP button and OFF button at the same time.
R6001161
SC is displayed on the LCD.
R6001158
2. Select SC (service check) with TEMP ▲ or TEMP ▼ button.
3. Press FAN button to enter the service check mode.
R6001162
00 is displayed and the left-side number blinks.
R6001159
4. Press TEMP ▲ or TEMP ▼ button and change the number until you hear the two
consecutive beeps or the long beep.
R6001163
5. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the
right-side number does not.
Long beep: Both the left-side and right-side numbers correspond with the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to Error codes and description on page 95.
background
Service Diagnosis SiUS122410EA
92 Part 6 Service Diagnosis
6. Press FAN button.
R6001162
The right-side number blinks.
R6001160
7. Press TEMP ▲ or TEMP ▼ button and change the number until you hear the long beep.
R6001163
8. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the
right-side number does not.
Long beep: Both the left-side and right-side numbers correspond with the error code.
9. Determine the error code.
The numbers indicated when you hear the long beep are the error code.
Refer to Error codes and description on page 95.
10.Press FAN button for 5 seconds to exit from the service check mode.
When the remote controller is left untouched for 60 seconds, it returns to the normal mode
also.
R6001162
background
SiUS122410EA Service Diagnosis
Part 6 Service Diagnosis 93
3.2 BRC073A6
Relations
Between Modes
On power-up, the message “Checking the connection. Please standby.” will be displayed on
the remote controller screen temporarily and then the basic screen will be displayed. To access
a mode from the basic screen, refer to the figure below.
When any of the operation buttons are pressed, the backlight will come on and remain lit for
about 30 seconds. Be sure to press a button while the backlight is on.
R6001167
Basic screen
Main Menu screen
Service Settings screen** Maintenance Menu screen
Main Menu
• Airflow Direction
• Energy Saving Options
• Schedule
• Maintenance Information
• Current Settings
• Clock & Calendar
• Language
Press Cancel
button once.
Press
Menu/OK
button once.
Basic Screen
• Operation mode changeover
• Fan speed control
• Menu display
• Confirmation of each setting
• On
• Off
• Cancel
• Operation lamp
Press Cancel button
for 4 seconds or more.
Press Cancel
button once.
Press Cancel button
for 4 seconds or more.
Press Cancel
button once.
Maintenance Menu
• Error Display
Service Settings
• Test Operation
• Maintenance Contact
• Field Settings
• Error History
# The items shown on the remote controller are different depending on the connected indoor unit.
** Not displayed in multi-split system.
SettingReturn
Airflow Direction
Energy Saving Options
Schedule
Maintenance Information
Configuration
Current Settings
1/2Main Menu
82°F
Cool
Set to
Test Operation
Maintenance Contact
Field Settings
Error History
Service Settings
SettingReturn
Error Display
Maintenance Menu
SettingReturn
background
Service Diagnosis SiUS122410EA
94 Part 6 Service Diagnosis
Service
Diagnosis
The following message is displayed on the screen when an error occurs during operation.
Check the error code and take the corrective action specified for the particular model.
Screen
Operation lamp
Menu/OK button
1
82
°F
Cool
Set to
Error: Push Menu button
82
°F
• If an error occurs, the error message or error icon
and the operation lamp will blink.
• To display the error code and contact information,
the Menu/Enter button needs to be enabled.
• Press the Menu/Enter button.
Operation
lamp
2
Contact Info
012
–
345
–
6789
Indoor Model
––––––––––
Outdoor Model
––––––––––
Error Code:
Return
• The error code blinks and the contact address will
appear.
• Notify your Daikin dealer of the Error code and
Model name.
Operation Method
background
SiUS122410EA Code Indication on Remote Controller
Part 6 Service Diagnosis 95
4. Code Indication on Remote Controller
4.1 Indoor Unit
Error
Codes
Description
Reference
Page
00 Normal condition —
A1 Indoor unit PCB abnormality 97
A5 Freeze-up protection control/heating peak-cut control 98
A6 Indoor fan motor (DC motor) or related abnormality 99
C4 Indoor heat exchanger thermistor or related abnormality 101
C9 Room temperature sensor or related abnormality 102
CC Humidity sensor abnormality 102
U4 Signal transmission error (between indoor unit and outdoor unit) 103
UA Unspecified voltage (between indoor unit and outdoor unit) 105
background
Code Indication on Remote Controller SiUS122410EA
96 Part 6 Service Diagnosis
Notes
4.2 Outdoor Unit
i: ON, h: OFF, j: Blinks
1. The error codes in the parenthesis ( ) are displayed only when the system is shut down.
2. When a sensor error occurs, check the remote controller display to determine which sensor
is malfunctioning.
If the remote controller does not indicate the error code, conduct the following procedure.
Turn the power off and then on again. If the same LED indication appears again
immediately after the power is turned on, the fault is in the thermistor.
If the above condition does not result, the fault is in the CT.
3. The indoor unit error code may take the precedence in the remote controller display.
4. Turn the power off and then on again. If the same LED indication appears again, outdoor
unit PCB is faulty. Replace the outdoor unit PCB.
Outdoor Unit LED Indication
Error
Codes
Description
Reference
Page
Green Red
A 1 2 3 4 5
j h h h h h
00 Normal condition —
UA
Unspecified voltage (between indoor unit and
outdoor unit)
112
UH Anti-icing control in other rooms 112
j h h i i h (U0) Refrigerant shortage 106
j i h h i h U2 Low-voltage detection or over-voltage detection 109
j h i h h h U3 Wiring error check unexecuted 111
j i h i i h A5 Anti-icing control for indoor unit 113
j i i i h h E1 Outdoor unit PCB abnormality 115
j i h h h h E3 Actuation of high pressure switch 116
j i h i h h (E5) OL activation (compressor overload) 117
j h i i h h (E6) Compressor lock 119
j i i i i h E7 DC fan lock 121
j h i h i h E8 Input overcurrent detection 121
j h h h h i E9 Electronic expansion valve abnormality 124
j i h h h h EA Four way valve abnormality 125
j i h i h h F3 Discharge pipe temperature control 127
j i h i i h F6 High pressure control in cooling 128
j h h i i h F8
System shutdown due to temperature abnormality
in the compressor
130
j i i h h h
H0 Master circuit malfunction 131
H3 High pressure switch system abnormality 133
H6 Position sensor abnormality 134
H9
Outdoor temperature thermistor or related
abnormality
136
JA High pressure sensor abnormality 138
(J3) Discharge pipe thermistor or related abnormality 136
J6
Outdoor heat exchanger thermistor or related
abnormality
136
J8 Liquid pipe thermistor or related abnormality 136
J9 Gas pipe thermistor or related abnormality 136
P4 Radiation fin thermistor or related abnormality 136
j i i h i h L3 Electrical box temperature rise 139
j h h h i h L4 Radiation fin temperature rise 141
j h h i h h L5 Output overcurrent detection 143
i — — — — — — See the note 4. —
h — — — — — — Check the power supply. —
background
SiUS122410EA Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 97
Note
5. Troubleshooting for Indoor Unit
5.1 Indoor Unit PCB Abnormality
Error Code A1
Method of Error
Detection
The system checks if the circuit works properly within the microcomputer of the indoor unit.
Error Decision
Conditions
The system cannot set the internal settings.
Supposed
Causes
Wrong models interconnected
Defective indoor unit PCB
Disconnection of connector
Reduction of power supply voltage
Troubleshooting
Wire Harness (Connector): Terminal strip ~ Control PCB (S1)
Correct the connection.
OK?
Check the power supply
voltage.
Start operation.
Voltage as rated?
Error repeats?
Check the power supply
voltage.
Start operation.
Voltage as rated?
Error repeats?
Error repeats?
Combination of the
indoor and outdoor unit
matched?
Check the connection of
connectors. ★
YES
NO
NO
YES
NO
NO
YES
(R23407)
Caution
* To secure the connection,
disconnect the connectors once
and then reconnect.
YES
NO
YES
NO
YES
NO
YES
Match the compatible
models.
Correct the power
supply.
Replace the indoor unit
PCB (control PCB).
Completed.
Completed.
Correct the power
supply.
Replace the indoor unit
PCB (control PCB).
Completed.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting for Indoor Unit SiUS122410EA
98 Part 6 Service Diagnosis
Reference
5.2 Freeze-up Protection Control/Heating Peak-cut Control
Error Code A5
Method of Error
Detection
Freeze-up protection control
During cooling operation, the freeze-up protection control (operation halt) is activated
according to the temperature detected by the indoor heat exchanger thermistor.
Heating peak-cut control
During heating operation, the temperature detected by the indoor heat exchanger thermistor
is used for the heating peak-cut control (operation halt, outdoor fan stop, etc.)
Error Decision
Conditions
Freeze-up protection control
During cooling operation, the indoor heat exchanger temperature is below 0°C (32°F).
Heating peak-cut control
During heating operation, the indoor heat exchanger temperature is above 59 ~ 60°C (138.2
~ 140°F).
Supposed
Causes
Short-circuited air
Clogged air filter of the indoor unit
Dust accumulation on the indoor heat exchanger
Defective indoor heat exchanger thermistor
Defective indoor unit PCB
Troubleshooting
Check No.01 Refer to P.146
NO
NO
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
YES
YES
(R21064)
YES
YES
NO
Caution
Provide sufficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor unit PCB
(control PCB).
Replace the indoor heat
exchanger thermistor.
As
described in the
thermistor characteristic
chart?
Check the air filter.
Check the dust accumulation on
the indoor heat exchanger.
Is there any short circuit?
Dirty?
Dirty?
Check the air passage.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS122410EA Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 99
5.3 Indoor Fan Motor (DC Motor) or Related Abnormality
Error Code A6
Method of Error
Detection
The rotation speed detected by the Hall IC during fan motor operation determines abnormal fan
motor operation.
Error Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
Remarkable decrease in power supply voltage
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB
Troubleshooting
Caution
OK?
NO
YES
YES
NO
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the connector for
connection.
Note: The motor may break when the
motor connector is disconnected
with the power supply on.
(Turn off the power supply before
connecting the connector also.)
∗ To secure the connection,
once disconnect the connector
and then reconnect it.
Foreign matters in or
around the fan?
Rotate the fan by hand.
Correct the connection.
Remove the foreign matters.
Turn off the power supply.
(Unplug the power cable or turn
the breaker off.)
A Go to the next page
(R23939)
background
Troubleshooting for Indoor Unit SiUS122410EA
100 Part 6 Service Diagnosis
Reference
Check No.03 Refer to P.147
Rubber cushion
07/09/12 class 15/18/24 class
R6000581
R6000306
Check No. 03
Check No. 03
Check No. 03
NO
YES
YES
YES
NO
NO
YES
NO
Is the rotation pulse
generated?
Turn the power on again.
Check the fan motor for
breakdown or short circuit.
Check the motor control voltage.
Check the indoor unit PCB for
rotation pulse.
Fan rotates smoothly?
Resistance OK?
Is the motor control
voltage 15 VDC
generated?
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
YES
NO
NO
Abnormal
sound occurs?
Is the rubber cushion
properly fitted?
YES
Correct the position of
rubber cushion or replace
the rubber cushion.
Replace the bearing rubber
cushion.
A Continued from the
previous page
(R24945)
Rubber
cushion
Bearing
rubber
cushion
Rubber
cushion
Bearing
rubber
cushion
background
SiUS122410EA Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 101
Reference
5.4 Indoor Heat Exchanger Thermistor or Related
Abnormality
Error Code C4
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
with the power on.
Supposed
Causes
Disconnection of connector
Defective thermistor(s)
Defective indoor unit PCB
Troubleshooting
C4 : Indoor heat exchanger thermistor
Check No.01 Refer to P.146
YES
(R21870)
NO
Check No. 01
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the defective
thermistor(s).
Replace the indoor unit PCB
(control PCB).
Normal?
Normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting for Indoor Unit SiUS122410EA
102 Part 6 Service Diagnosis
5.5 Room Temperature Sensor Abnormality/Humidity
Sensor Abnormality
Error Code C9, CC
Method of Error
Detection
Sensor abnormality is detected by input value.
Error Decision
Conditions
The input from the humidity sensor is 4.96 V and more or 0.04 V and less.
Supposed
Causes
Disconnection of connector
Defective humidity sensor
Defective indoor unit PCB
Troubleshooting
R6000515
C9 : Room temperature sensor
CC : Humidity sensor
Correct the connection.
Replace the control PCB.
Completed.
Normal?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the connection of
connectors.
NO
YES
* Connect the connector again for
ensuring the connection.
Replace the humidity sensor
PCB.
Error code displayed?
YES
NO
background
SiUS122410EA Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 103
5.6 Signal Transmission Error (Between Indoor Unit and
Outdoor Unit)
Error Code U4
Method of Error
Detection
The signal transmission data received from the outdoor unit is checked whether it is normal.
Error Decision
Conditions
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Supposed
Causes
Reduction of power supply voltage
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Short circuit inside the fan motor winding
Defective indoor unit PCB
Disturbed power supply waveform
background
Troubleshooting for Indoor Unit SiUS122410EA
104 Part 6 Service Diagnosis
Reference
Troubleshooting
Check No.11 Refer to P.147
Check No.11
Check the power supply
waveform.
Check the voltage of the
connection wires on the indoor
terminal strip/block between
No. 1 and No. 3, and between
No. 2 and No. 3.
YES
Blink
Replace the indoor unit PCB
(control PCB).
Locate and eliminate the
cause of the disturbance of
the power supply waveform.
NO
(R24621)
Continuously ON or OFF
NO
YES
YES
NO
Caution
Correct the connection wires
between the indoor unit and
the outdoor unit.
Replace the outdoor unit PCB
(main PCB).
Replace the connection wires
between the indoor unit and
outdoor unit.
Is LED A
blinking?
Properly
insulated?
Is there any
disturbance?
Is there any
wiring error?
Check the connection wires
between the indoor unit and the
outdoor unit.
Check the LED A on the outdoor
unit PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Check the power supply voltage.
Correct the power supply.
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Rotate the
outdoor fan manually.
Does the outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the rated
value?
background
SiUS122410EA Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 105
5.7 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
Error Code UA
Method of Error
Detection
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor/outdoor transmission signal.
Error Decision
Conditions
The pair type and multi type are interconnected.
Supposed
Causes
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Troubleshooting
(R23001)
Caution
NO
YES
YES
NO
Match the compatible models.
OK?
Correct the connection.
Check the part numbers of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
Are the
connecting wires
connected properly?
Check the combination of the
indoor and outdoor unit.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting for Outdoor Unit SiUS122410EA
106 Part 6 Service Diagnosis
6. Troubleshooting for Outdoor Unit
6.1 Refrigerant Shortage
Error Code U0
Outdoor Unit LED
Display
A j 1 h 2 h 3 i 4 i 5 h
Method of Error
Detection
Refrigerant shortage is detected by checking the input current value and the compressor
running speed. If there is insufficient refrigerant, the input current tends to be lower than the
normal value.
Error Decision
Conditions
The following conditions continue for 7 minutes.
Input current A × output compressor speed + B
Output compressor speed C
Power consumption A × output compressor speed + B
Output compressor speed C
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
The installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor,
room or outdoor temperature thermistor
Closed stop valve
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Defective electronic expansion valve
2MXM 3/4MXM 2/3MXT(H)
A (coefficient) 10/1000 27/1000 27/1000
B (A) 0.3 2 2
C (rps) 40 40 40
A (coefficient) 2500/256
B (W) 50
C (rps) 40
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 107
Troubleshooting
R6000442
Caution
YES
NO
NO
YES
YES
YES
NO
NO
YES
NO
∗ Discharge pipe thermistor
∗ Indoor or outdoor heat exchanger thermistor
∗ Room temperature thermistor
∗ Outdoor temperature thermistor
Check for refrigerant shortage.
A
Go to the next page
Reconnect the thermistor(s).
Open the stop valve.
Repair the pipe flare or
replace the union.
Check if any harnesses are
in contact with the piping
and correct as required.
Also, replace any cracked
pipes.
Check the connection of the
power transistor harness.
Also, replace any cracked
pipes.
Oil leak at
internal piping?
Stop valve
closed?
Compressor
vibrating too much?
Oil leak at relay
pipe connections?
Any thermistor
disconnected?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
Check No. 19
Check the outdoor fan.
Check No. 17
Check the installation
condition.
background
Troubleshooting for Outdoor Unit SiUS122410EA
108 Part 6 Service Diagnosis
Reference
Reference
Reference
Reference
R6000552
Check No.01 Refer to P.146
Check No.12 Refer to P.148
Check No.17 Refer to P.152
Check No.19 Refer to P.153
NG
YES
NO
Change for a specified amount of
fresh refrigerant.
NO
Check No. 12
Electronic expansion valve
functioning?
Replace the electronic
expansion valve.
YES
Replace the defective
thermistor(s).
Completed.
Refrigerant
shortage error again?
Check No. 01
Check the thermistors.
OK
NO
YES
Replace the outdoor unit PCB
(main PCB).
Replace the compressor.
Completed.
Error again?
Continued from the
previous page
A
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 109
6.2 Low-voltage Detection or Over-voltage Detection
Error Code U2
Outdoor Unit LED
Display
A j 1 i 2 h 3 h 4 i 5 h
Method of Error
Detection
Indoor Unit
The zero-cross detection of the power supply is evaluated by the indoor unit PCB.
Outdoor Unit
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Indoor Unit
There is no zero-cross detection in approximately 10 seconds.
Outdoor Unit
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below A V for 0.1 second.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage out of specification
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB
Defective indoor unit PCB
A (V) 170
background
Troubleshooting for Outdoor Unit SiUS122410EA
110 Part 6 Service Diagnosis
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB (main PCB).
Check for such factors for a
long term.
(R22370)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
NO
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
Disturbance factors
Noise
Power supply distortion
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Replace the indoor
unit PCB (control PCB).
Turn on
the power. System
restarted? (Repeat
a few times.)
Error again
within 3 minutes after
turning on the power?
Loose or
disconnected?
NO
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Does the
outdoor fan rotate smoothly?
Is the
voltage fluctuation
within ±10% from the rated
value?
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 111
Reference
6.3 Wiring Error Check Unexecuted
Error Code U3
Outdoor Unit LED
Display
A j 1 h 2 i 3 h 4 h 5 h
Method of Error
Detection
The system checks if wiring error check is executed after clearing the memory.
Error Decision
Conditions
An error is determined when the unit is operated by the remote controller without executing
wiring error check after the memory was cleared.
Supposed
Causes
The wiring error switch (SW3) may have been pressed for 10 seconds or more and the memory
may have been deleted. The unit cannot be operated unless wiring error check is executed.
Troubleshooting
Refer to Wiring Error Check Function on page 162 for details.
(R23952)
Caution
NO
YES
Wiring error
check executed?
Conduct wiring error check.
Wiring error check may not
have been finished because of
the trouble of indoor/outdoor
unit.
Conduct wiring error check
again.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting for Outdoor Unit SiUS122410EA
112 Part 6 Service Diagnosis
Note
6.4 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit), Anti-icing Control in Other Rooms
Error Code UA, UH
Outdoor Unit LED
Display
A j 1 h 2 h 3 h 4 h 5 h
Method of Error
Detection
A wrong connection is detected by checking the combination of indoor and outdoor units on the
microcomputer.
Error Decision
Conditions
Anti-icing control in other rooms
Unspecified internal and/or external voltages
Mismatching of indoor and outdoor units
Supposed
Causes
Anti-icing function in other rooms
Power supply voltage out of specification
Wrong models interconnected
Wrong indoor unit PCB or outdoor unit PCB mounted
Troubleshooting
Refer to Anti-icing control for indoor unit on page 113 for details.
(R21922)
Caution
NO
YES
NO
YES
NO
YES
Check the model combination.
Error displayed
while operating?
Power supply
voltage as specified?
Matched
compatibly?
The anti-icing function is
activated in other rooms.
Refer to A5.
Correct the power supply
voltage.
Match the compatible models.
Check the combination of all
connected models.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 113
6.5 Anti-icing Control for Indoor Unit
Error Code A5
Outdoor Unit LED
Display
A j 1 i 2 h 3 i 4 i 5 h
Method of Error
Detection
During cooling operation, indoor unit icing is detected by checking the temperatures sensed by
the indoor heat exchanger thermistor and room temperature thermistor that are located in a
shut-down room.
Error Decision
Conditions
In cooling operation, the both conditions (A) and (B) are met for 5 minutes.
(A) Room temperature – Indoor heat exchanger temperature ≥ 10°C (18°F)
(B) Indoor heat exchanger temperature ≤ –1°C (30.2°F)
If the error repeats, the system is shut down.
Reset condition: 3-minute standby is over and the indoor heat exchanger temperature is
above 0°C (32°F)
Supposed
Causes
Wrong wiring or piping
Defective electronic expansion valve
Short-circuited air
Defective indoor heat exchanger thermistor
Defective room temperature thermistor
background
Troubleshooting for Outdoor Unit SiUS122410EA
114 Part 6 Service Diagnosis
Reference
Reference
Troubleshooting
R6001320
Check No.01 Refer to P.146
Check No.12 Refer to P.148
Caution
YES
NO
NO
YES
YES
YES
NO
YES
NO
NO
Check No. 12
Check the electronic expansion
valve.
Check No. 01
Check the indoor heat exchanger
thermistor.
Check No. 01
Check the room temperature
thermistor.
Activate the wiring error check
function.
Replace the electronic
expansion valve or coil.
Replace the outdoor heat
exchanger thermistor.
Replace the room temperature
thermistor.
Replace the room temperature
thermistor or indoor heat
exchanger thermistor.
Do the vacuum drying.
Replace the indoor unit PCB
(control PCB) and then start
the wiring error check function.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the wiring and piping.
Wrong wiring or
piping?
Functioning?
As described in
the thermistor
characteristic
chart?
As described in
the thermistor
characteristic
chart?
Change the refrigerant to remove
moisture from the piping (after
drawing a vacuum).
Error again?
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 115
6.6 Outdoor Unit PCB Abnormality
Error Code E1
Outdoor Unit LED
Display
A j 1 i 2 i 3 i 4 h 5 h
Method of Error
Detection
Detect within the program of the microcomputer.
Error Decision
Conditions
The program of the microcomputer is in abnormal running order.
Supposed
Causes
Defective outdoor unit PCB
Defective electronic expansion valve driver
Defective IGBT temperature detection thermistor circuit
Defective Fan IPM temperature detection thermistor circuit
Fan IPM temperature error
IGBT temperature error
ACS transmission error
Communication error between PCBs
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
R6001191
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
NO
YES
Replace the outdoor unit PCBs
(main PCB, sub PCB).
Ground the system.
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
Turn on the power.
Check wiring between PCBs.
Error again?
Check if the outdoor unit is
grounded.
Grounded?
background
Troubleshooting for Outdoor Unit SiUS122410EA
116 Part 6 Service Diagnosis
6.7 Actuation of High Pressure Switch
Error Code E3
Outdoor Unit LED
Display
A j 1 i 2 h 3 h 4 h 5 h
Method of Error
Detection
Abnormality is detected when the contact of the high pressure switch opens.
Error Decision
Conditions
High pressure switch (S1PH) activating pressure: 4.15 MPa
High pressure switch (S1PH) recovery pressure: 3.2 MPa
Supposed
Causes
Actuation of high pressure switch (S1PH)
Closed stop valve
Disconnection of connector X820A or S40
Disconnection of 2 terminals of high pressure switch (S1PH)
Defective outdoor unit PCB
Broken S1PH harness
Defective high pressure switch (S1PH)
Troubleshooting
R6001170
NO
YES
Nearly 0 :
Resistance f
Check
the resistance between
the pins 1 - 2 on the connector
X820A or S40.
Stop valve open?
Open the stop valve.
Nearly 0 :
Resistance f
Replace the harness for the high
pressure switch.
Replace the high pressure switch
(S1PH).
Disconnect the connector
X820A or S40 from the PCB.
Replace the outdoor unit PCB
(main PCB).
Disconnect the 2 terminals of
the high pressure switch
(S1PH).
NO
YES
High
pressure switch
connector X820A or S40 properly
connected?
Reconnect the connector.
Check
the resistance
between the 2
terminals of the high
pressure switch
(S1PH).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 117
6.8 OL Activation (Compressor Overload)
Error Code E5
Outdoor Unit LED
Display
A j 1 i 2 h 3 i 4 h 5 h
Method of Error
Detection
A compressor overload is detected through compressor OL.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of discharge pipe thermistor
Defective discharge pipe thermistor
Disconnection of connector X820A or S40
Disconnection of 2 terminals of OL (Q1M)
Defective OL (Q1M)
Broken OL harness
Defective electronic expansion valve or coil
Defective four way valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
background
Troubleshooting for Outdoor Unit SiUS122410EA
118 Part 6 Service Diagnosis
Notes
Reference
Reference
Reference
Reference
Troubleshooting
R6001171
OL (Q1M) activating temperature: 125°C (257°F)
OL (Q1M) activating temperature: 110°C (230°F)
Check No.01 Refer to P.146
Check No.12 Refer to P.148
Check No.13 Refer to P.149
Check No.14 Refer to P.149
Caution
YES
NG
NO
OK
OK
NG
NG
OK
YES
NO
NG
OK
Refrigerant shortage
Water mixed
Stop valve
Disconnect the connector
X820A or S40 from the PCB.
Disconnect the 2 terminals of
the OL (Q1M).
Resistance
f
Resistance
f
Nearly 0 :
Nearly 0 :
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB (main PCB).
Discharge pipe
thermistor disconnected?
Check No. 01
Check the discharge pipe
thermistor.
Check No. 13
Check the four way valve.
Check No. 14
Check the refrigerant line.
Check No. 12
Check the electronic
expansion valve.
Replace the OL (Q1M).
Replace the OL harness.
Connect the connector
X820A or S40 properly.
Is the connector
X820A or S40 properly
connected?
Check the
resistance between the 2
terminals on connector
X820A or S40.
Check the
resistance between the 2
terminals of the OL
(Q1M).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 119
6.9 Compressor Lock
Error Code E6
Outdoor Unit LED
Display
A j 1 h 2 i 3 i 4 h 5 h
Method of Error
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Error Decision
Conditions
Judging from the current waveform generated when high-frequency voltage is applied to the
compressor.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Closed stop valve
Defective outdoor unit PCB
Defective compressor
Defective electronic expansion valve
background
Troubleshooting for Outdoor Unit SiUS122410EA
120 Part 6 Service Diagnosis
Reference
Reference
Troubleshooting
Check No.12 Refer to P.148
Check No.15 Refer to P.150
Turn off the power. Disconnect the
harnesses U, V, and W.
(R21067)
Caution
NO
YES
YES
NO
NO
YES
NO
YES
Check No.15
Check with the inverter analyzer.
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Open the stop valve.
∗ Inverter analyzer:
RSUK0917C
Replace the compressor.
Replace the compressor.
Check the electronic
expansion valve coil.
Go to Check No. 12.
Any LED off?
Stop valve
closed?
Emergency stop
without compressor running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 121
Reference
6.10 DC Fan Lock
Error Code E7
Outdoor Unit LED
Display
A j 1 i 2 i 3 i 4 i 5 h
Method of Error
Detection
An error is determined when actual rotation speed per second (rps) is significantly apart from
instructed rotation speed.
Error Decision
Conditions
The fan does not start in 30 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
Check No.16 Refer to P.151
(R20416)
Caution
YES
YES
NO
YES
NO
NO
YES
NO
Turn on the power.
Rotate the fan.
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the outdoor unit
PCB (main PCB).
Fan motor
connector disconnected?
Foreign matters
in or around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal
generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting for Outdoor Unit SiUS122410EA
122 Part 6 Service Diagnosis
6.11 Input Overcurrent Detection
Error Code E8
Outdoor Unit LED
Display
A j 1 h 2 i 3 h 4 i 5 h
Method of Error
Detection
Detected by checking the input current value
Error Decision
Conditions
The input current is at a certain value (depending on the condition) for 2.5 seconds.
The compressor halts if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Outdoor temperature is out of operation range.
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 123
Reference
Reference
Reference
Troubleshooting
Check No.15 Refer to P.150
Check No.17 Refer to P.152
Check No.18 Refer to P.152
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
* An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
(R21863)
NO
YES
YES
NO
Start operation and measure the
input current.
Check No. 18
Check the discharge pressure.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Any LED off?
Input current
flowing above its stop level?
* Inverter analyzer:
RSUK0917C
background
Troubleshooting for Outdoor Unit SiUS122410EA
124 Part 6 Service Diagnosis
Reference
6.12 Electronic Expansion Valve Coil Abnormality
Error Code E9
Outdoor Unit LED
Display
A j 1 h 2 h 3 h 4 h 5 i
Method of Error
Detection
Detect errors based on check of continuity of the electronic expansion valve.
Error Decision
Conditions
High input voltage from electronic expansion valve to the microcomputer due to overcurrent.
Low input voltage from electronic expansion valve to the microcomputer due to
disconnected connectors.
Supposed
Causes
Defective electronic expansion coil
Broken harness of electronic expansion coil
Defective connection of electronic expansion coil connector
Defective outdoor unit main PCB
Troubleshooting
R6001181
Check No.12 Refer to P.148
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
NO
YES
YES
Restart operation.
Turn OFF the power supply once
and turn ON again.
Check the connection of
connectors.
NO
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
Replace the electronic
expansion valve.
Replace the outdoor unit
PCB (sub PCB).
Normal?
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
E9 error again?
E9 error again?
Check No. 12
Is the coil resistance of
the electronic expansion
valve normal?
NO
YES
Correct the connection.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 125
6.13 Four Way Valve Abnormality
Error Code EA
Outdoor Unit LED
Display
A j 1 i 2 h 3 h 4 h 5 h
Method of Error
Detection
Detects whether the four-way valve is switching normally by the indoor heat exchanger
temperature.
Error Decision
Conditions
The following condition continues for A seconds after the compressor has started.
Cooling operation
The lowest indoor heat exchanger temperature > 45°C (113°F)
Heating operation
The highest indoor heat exchanger temperature < 0°C (32°F)
Tde: outdoor heat exchanger temperature
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
2/3/4MXM
2MXT(H)
5MXM
3/4/5MXT(H)
A (seconds) Cooling 240 680
Heating outdoor temperature ≥
–15°C (5°F)
240 680
outdoor temperature <
–15°C (5°F)
460 680
background
Troubleshooting for Outdoor Unit SiUS122410EA
126 Part 6 Service Diagnosis
Reference
Reference
Reference
Troubleshooting
R6001164
Check No.01 Refer to P.146
Check No.13 Refer to P.149
Check No.14 Refer to P.149
NG
OK
NO
OK
NG
OK
YES
NG
Correct the four way valve
coil.
Reconnect the harness.
YES
YES
YES
NO
NO
Replace the outdoor
unit PCB (main PCB).
Replace the defective
thermistor(s).
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
Reconnect the
thermistor(s).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Refrigerant shortage
Water mixed
Stop valve
Four way valve
coil disconnected (loose)?
Harness
disconnected?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Check No. 13
Check the four way valve
switching output.
Check the continuity of the four way
valve coil and harness.
Replace the four way
valve coil.
NO
Resistance
between harnesses
about 556 ~ 614 :?
Disconnect the harness from the
connector.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 127
Reference
Reference
Reference
6.14 Discharge Pipe Temperature Control
Error Code F3
Outdoor Unit LED
Display
A j 1 i 2 h 3 i 4 h 5 h
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
stops.
The error is cleared when the discharge pipe temperature is dropped below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
R6001193
Check No.01 Refer to P.146
Check No.12 Refer to P.148
Check No.14 Refer to P.149
°C °F
A 120 248
B 107 224.6
Caution
NG
OK
OK
OK
NG
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
Refrigerant shortage
Four way valve
Water mixed
Stop valve
Check No. 12
Check the electronic
expansion valve.
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (sub PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
background
Troubleshooting for Outdoor Unit SiUS122410EA
128 Part 6 Service Diagnosis
6.15 High Pressure Control in Cooling
Error Code F6
Outdoor Unit LED
Display
A j 1 i 2 h 3 i 4 i 5 h
Method of Error
Detection
High pressure control (operation halt, compressor speed drop, etc.) is activated in cooling
operation if the temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Error Decision
Conditions
The temperature sensed by the outdoor heat exchanger thermistor rises above about A.
The error is cleared when the temperature drops below about B.
Supposed
Causes
The installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
°C °F
A 59 138.2
B 50 122
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 129
Reference
Reference
Reference
Reference
Reference
Troubleshooting
R6001194
Check No.01 Refer to P.146
Check No.12 Refer to P.148
Check No.17 Refer to P.152
Check No.18 Refer to P.152
Check No.19 Refer to P.153
Caution
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (subPCB).
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB (sub PCB).
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Check No. 19
Check the outdoor fan.
Check No. 18
Check the discharge
pressure.
Check No. 12
Check the electronic
expansion valve.
Check No. 01
Check the outdoor heat
exchanger thermistor.
Check No. 17
Check the installation
condition.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting for Outdoor Unit SiUS122410EA
130 Part 6 Service Diagnosis
Reference
6.16 System Shutdown due to Temperature Abnormality in
the Compressor
Error Code F8
Outdoor Unit LED
Display
A j 1 h 2 h 3 i 4 i 5 h
Method of Error
Detection
Operation is halted when the temperature detected by the discharge pipe thermistor exceeds
the determined limit.
Error Decision
Conditions
Temperature exceeds the detection threshold of 127.5°C (261.5°F) during forced cooling
operation.
Supposed
Causes
Abnormal operation due to air intrusion
Defective discharge pipe thermistor
Troubleshooting
Check No.01 Refer to P.146
YES
(R23655)
NO
OK
NG
Caution
Replace the outdoor unit. #
Replace both the discharge pipe
thermistor and the outdoor unit
PCB (main PCB).
Replace the outdoor unit.
#
Abnormal
deformation of piping in the
outdoor unit
Check No. 01
Check the discharge pipe
thermistor
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
#
Replace the unit as directed in the installation manual, making sure that air does not intrude
into the refrigerant piping.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 131
6.17 Compressor Sensor System Abnormality
Error Code H0
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
The system checks the power supply voltage and the DC voltage before the compressor
starts.
The system checks the DC current of the compressor right after the compressor starts.
Error Decision
Conditions
The power supply voltage and the DC voltage is obviously low or high.
The DC current of the compressor does not flow when the compressor starts.
Supposed
Causes
Disconnection of reactor
Disconnection of compressor harness
Defective outdoor unit PCB
Defective compressor
+
–
PCB
Compressor
DC voltage
DC current
Power
Module
(R22001)
background
Troubleshooting for Outdoor Unit SiUS122410EA
132 Part 6 Service Diagnosis
Troubleshooting
Connect the reactor properly.
(R20419)
NO
YES
Connect the compressor
properly.
NO
YES
Replace the reactor.
NO
YES
Replace the compressor or
the compressor relay
harness.
Restart the operation again
and if the error occurs
again, replace the outdoor
unit PCB (main PCB).
NO
YES
Disconnect the reactor from the outdoor
unit PCB and measure the resistance
value between reactor terminals with
multimeter.
Disconnect the compressor relay harness
from the outdoor unit PCB and measure
the resistance value between the each 3
terminals of the compressor with
multimeter.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
10 : or less
between each terminal?
Check the connection of the
compressor.
Check the reactor.
Check the compressor.
Turn off the power.
Check the connection of the
reactor.
Connection OK?
Connection OK?
10 : or less?
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 133
Note(s)
6.18 High Pressure Switch System Abnormality
Error Code H3
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
The protection device circuit cheeks continuity in the high pressure switch.
Error Decision
Conditions
There is no continuity in the high pressure switch when the compressor stops operating.
Supposed
Causes
Defective high pressure switch
Defective connection of high pressure switch connector
Defective outdoor unit main PCB
Disconnected lead wire
Troubleshooting
R6001112
1. Connector and high pressure switch
Connect the connector
correctly.
Is high
pressure switch
connector (1) correctly
connected to outdoor unit
PCB?
Replace the outdoor unit
main PCB (A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Wait for 10 minutes after the unit
stops operating, then check the
following.
YES
Replace the high pressure
switch with no continuity.
Resistance in normal
operation: 10 : or less
Is there
continuity in each high
pressure switch?
NO
YES
Replace the lead wire.
Is there continuity in
lead wire?
NO
YES
High pressure switch Connector for high pressure switch Activation pressure
S1PH X820A or S40 4.15 MPa
background
Troubleshooting for Outdoor Unit SiUS122410EA
134 Part 6 Service Diagnosis
6.19 Position Sensor Abnormality
Error Code H6
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage outside the specified range
Troubleshooting
R6001174
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the power supply voltage.
Correct the power supply.
NO
YES
A Go to the next page
Check No. 20
Check the short circuit of the diode
bridge.
Replace the outdoor unit
PCB (main PCB).
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
Is the voltage
fluctuation within
±10% from the rated
value?
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 135
Reference
Reference
Reference
Reference
R6001175
Check No.15 Refer to P.150
Check No.18 Refer to P.152
Check No.20 Refer to P.153
Check No.21 Refer to P.155
Check the connection.
NO
NO
NO
YES
YES
YES
Check No.15
Check with the inverter analyzer.
Check No.21
Turn on the power. Check the
capacitor voltage.
Turn off the power. Disconnect the
harnesses U, V, and W.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Reconnect the electrical
components or compressor
harnesses as specified.
Inverter analyzer:
RSUK0917C
Within 320 VDC?
Any LED OFF?
+ 100
- 50
A Continued from the
previous page
background
Troubleshooting for Outdoor Unit SiUS122410EA
136 Part 6 Service Diagnosis
6.20 Thermistor or Related Abnormality (Outdoor Unit)
Error Code H9, J3, J6, J8, J9, P4
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The voltage between the both ends of the thermistor is above 4.96 V or below 0.04 V with
the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
The system is shut down if all the units are judged as the J8 error.
Supposed
Causes
Disconnection of the connector for the thermistor
Defective thermistor(s)
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting In case of P4
Replace the outdoor unit PCB (main PCB).
P4 : Radiation fin thermistor
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 137
Reference
Troubleshooting In case of H9, J3, J6, J8, J9
H9 : Outdoor temperature thermistor
J3 : Discharge pipe thermistor
J6 : Outdoor heat exchanger thermistor
J8 : Liquid pipe thermistor
J9 : Gas pipe thermistor
Check No.01 Refer to P.146
(R21118)
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connectors
or thermistors.
J3 error: The discharge
pipe temperature is lower
than the heat exchanger
temperature.
Replace the defective
thermistor(s).
∗ Outdoor temperature
thermistor
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger
thermistor
∗ Liquid pipe thermistor
∗ Gas pipe thermistor
Cooling: Outdoor heat
exchanger
thermistor
Heating: Indoor heat
exchanger
thermistor
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Error displayed
again on remote controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
background
Troubleshooting for Outdoor Unit SiUS122410EA
138 Part 6 Service Diagnosis
Reference
6.21 High Pressure Sensor Abnormality
Applicable
Models
5MXM48AVJU9
3MXT(H)24AVJU9, 4MXT(H)36AVJU9, 5MXT(H)40AVJU9
Error Code JA
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
Error is detected from the pressure detected by the high pressure sensor.
Error Decision
Conditions
The high pressure sensor is short circuited or open circuited.
Pressure range: 0 - 4.17 MPa
Supposed
Causes
Defective high pressure sensor
Connection of low pressure sensor with wrong connection
Defective outdoor unit PCB
Disconnection of high pressure sensor
Troubleshooting
R6001351
Check No.23 Refer to P.158
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor main PCB
(A1P).
Replace the high pressure sensor
(S1NPH).
YES
NO
Replace the outdoor main PCB
(A1P).
NO
Replace the high pressure sensor
(S1NPH).
YES
YES
NO
YES
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of the
high pressure sensor
normal?
Connect to the high-pressure
sensor and then reconnect to the
power.
NO
Does the
high-pressure sensor
connect to the corresponding
connector of the outdoor
main PCB (A1P)?
Are the characteristics of the
high pressure sensor normal? (Make a
comparison between the voltage
characteristics and the
gauge pressure.)
Is the PCB pressure detection
normal? (Make a comparison
between the checker pressure
data and the voltage
characteristics.)
Check No.23
Check No.23
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 139
6.22 Electrical Box Temperature Rise
Error Code L3
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 i 5 h
Method of Error
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Error Decision
Conditions
With the compressor off, the radiation fin temperature is above A.
The error is cleared when the temperature drops below B.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above C and stops when the radiation fin temperature drops below B.
2/3/4MXM, 2MXT(H)
5MXM, 3/4/5MXT(H)
Normal operation
After completion of forced cooling operation until next compressor startup
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
°C °F
A 100 212
B 70 158
C 85 185
°C °F
A 70 158
B 60 140
°C °F
A 74 165.2
B 60 140
background
Troubleshooting for Outdoor Unit SiUS122410EA
140 Part 6 Service Diagnosis
Reference
Reference
Troubleshooting
R6000426
Check No.17 Refer to P.152
Check No.19 Refer to P.153
Caution
YES
NO
YES
NG
NO
OK
NO
YES
Turn off the power. Then, turn on
the power to restart the system.
Check the radiation fin
temperature.
Radiation fin
dirty?
Check No. 19
Check the outdoor fan.
Error again or
outdoor fan activated?
Replace the outdoor unit
PCB (main PCB).
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Above A?
Check the installation
condition.
Go to Check No. 17.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 141
6.23 Radiation Fin Temperature Rise
Error Code L4
Outdoor Unit LED
Display
A j 1 h 2 h 3 h 4 i 5 h
Method of Error
Detection
A radiation fin temperature rise is detected by checking the radiation fin temperature with the
compressor on.
Error Decision
Conditions
The radiation fin temperature with the compressor on is above A.
The error is cleared when the temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
2/3/4MXM, 2MXT(H)
5MXM, 3/4/5MXT(H)
Normal operation
In forced cooling operation
Supposed
Causes
Defective outdoor fan motor
Short circuit
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
°C °F
A 95 203
B 85 185
°C °F
A 70 158
B 64 147.2
°C °F
A 74 165.2
B 64 147.2
background
Troubleshooting for Outdoor Unit SiUS122410EA
142 Part 6 Service Diagnosis
Note
Reference
Reference
Troubleshooting
Refer to Silicone Grease on Power Transistor/Diode Bridge on page 175 for details.
Check No.17 Refer to P.152
Check No.19 Refer to P.153
Caution
Turn off the power. Then, turn on
the power to restart the system.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R23953)
NO
NG
OK
NO
YES
Check the radiation fin
temperature.
NO
YES
YES
Above A?
Check No. 19
Check the outdoor fan.
Error displayed
again?
Has the PCB
been replaced?
Check if silicone grease is
applied properly on the
radiation fin. If not, apply
the silicone grease.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB (main PCB).
YES
NO
Radiation fin
dirty?
Clean up the radiation fin.
Check the installation
condition.
Go to Check No. 17.
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 143
6.24 Output Overcurrent Detection
Error Code L5
Outdoor Unit LED
Display
A j 1 h 2 h 3 i 4 h 5 h
Method of Error
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Error Decision
Conditions
A position signal error occurs while the compressor is running.
A rotation speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal power supply voltage
Defective outdoor unit PCB
Supply voltage out of specification
Defective compressor
background
Troubleshooting for Outdoor Unit SiUS122410EA
144 Part 6 Service Diagnosis
Troubleshooting
(R22566)
Caution
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
YES
NO
∗
An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output overcurrent
after the wires have been disconnected and reconnected for part replacement, check the wiring again.
Check No. 22
Check the power module.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Turn off the power. Then, turn on
the power to restart the system.
See if the same error occurs.
Check the power supply voltage.
Monitor the power supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
∗ Momentary drop of power supply
voltage
∗ Compressor overload
∗ Short circuit
Not a malfunction.
Keep observing.
Check the connectors and
other components.
Fully open the stop valve.
Correct the power supply.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB (main PCB).
Replace the outdoor unit
PCB (main PCB).
Error again?
Stop valve fully
open?
Any LED off?
Normal?
∗ Inverter analyzer:
RSUK0917C
Short circuit
or wire breakage
between compressor's coil
phases?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the discharge
pressure.
Go to Check No. 18.
Is the voltage
fluctuation within ±10%
from the rated value?
background
SiUS122410EA Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 145
Reference
Reference
Reference
Reference
Check No.15 Refer to P.150
Check No.17 Refer to P.152
Check No.18 Refer to P.152
Check No.22 Refer to P.156
background
Check SiUS122410EA
146 Part 6 Service Diagnosis
Notes
7. Check
7.1 Thermistor Resistance Check
Check No.01 Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be
replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance
between the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
R6001195
When replacing the defective thermistor(s), replace the thermistor as ASSY.
Thermistors of some models are fixed to piping with a thermal insulation tube and clamp as
in the figure. After thermistors are removed, attach them in the original position with caution
not to contact the surrounding objects.
Multimeter
Resistance range
Thermistor ASSY Soldered thermistor
Multimeter
R(25°C / 77°F) = 20 k:, B = 3950 K
Thermistor
temperature
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
R(25°C / 77°F) = 20 k:
B = 3950 K
Resistance (k:)
197.8
148.2
112.1
85.60
65.93
51.14
39.99
31.52
25.02
20.00
16.10
13.04
10.62
8.707
7.17650
–4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
°C °F
(˚C)
(k:)
–15
0
15 30
45
150
100
50
(˚F)
5 32 59 86 113
Clamp
Piping
Thermistor
Thermal
insulation tube
background
SiUS122410EA Check
Part 6 Service Diagnosis 147
7.2 Indoor Fan Motor Connector Check
Check No.03 Check the connection of connector.
1. Check connector the for connection.
2. Turn the power off.
3. Check if each resistance at the phases U - V and V - W is within specified rage in the table
below.
R6001148
7.3 Power Supply Waveform Check
Check No.11 Measure the power supply waveform between No. 1 and No. 2 on the terminal strip, and check
the waveform disturbance.
Check if the power supply waveform is a sine wave (Fig.1).
Check if there is waveform disturbance near the zero-cross (sections circled in Fig.2).
U - V/V - W Resistance ()
07/09/12 class 70.9 ~ 78.3
15/18/24 class 42.9 ~ 47.5
3
2
1
Phase U
Phase W
Phase V
S200
[Fig.1] [Fig.2]
(R1736)
(R1444)
background
Check SiUS122410EA
148 Part 6 Service Diagnosis
7.4 Electronic Expansion Valve Check
Check No.12 Conduct the followings to check the electronic expansion valve (EV).
1. Check if the EV connector is correctly inserted in the PCB. Match the EV unit number and
the connector number.
2. Turn the power off and on again, and check if all the EVs generate latching sound.
3. If any of the EVs does not generate latching sound in the above step 2, disconnect that
connector and check the continuity using a multimeter.
Check the continuity between the pins 5 - 1, 5 - 2, 5 - 3, 5 - 4. If there is no continuity
between the pins, the EV coil is faulty.
4. If no EV generates a latching sound in the above step 2, the outdoor unit PCB is faulty.
5. If the continuity is confirmed in the above step 3, mount a good coil (which generated
latching sound) in the EV unit that did not generate a latching sound, and check if that EV
generates a latching sound.
If a latching sound is generated, the outdoor unit PCB is faulty.
If a latching sound is not generated, the EV unit is faulty.
If the system keeps operating with a defective electronic expansion valve, the following problem
may occur.
Valve
opening
position
Possible problem Check method
Open
Cooling:
Flowing noise of refrigerant in the
unit which is not in operation
Water leakage at the unit which is
not in operation
Operation half due to anti-icing
function
Reset power supply and conduct cooling operation unit
by unit.
Heating:
Flowing noise of refrigerant in the
unit which is not in operation
The unit does not heat the room.
Close
Cooling:
The problem unit does not cool
the room.
Only the problem unit is in
operation, the unit starts pump
down.
(The low pressure of the unit
becomes vacuum.)
Abnormal discharge pipe
temperature
Reset power supply and conduct cooling operation unit
by unit.
Heating:
Refrigerant shortage due to
stagnation of liquid refrigerant inside
the faulty indoor unit
The unit does not heat the room.
Abnormal discharge pipe
temperature
Check the liquid pipe temperature
of no-operation unit.
YES
(R16019)
NO
The EV is not
defective.
Replace the EV
of the room.
Almost the same
as the outdoor
temperature?
Check the low pressure.
(R16020)
YES
NO
Replace the EV
of the room.
The EV is not
defective.
Does the pressure
become into vacuum
zone?
background
SiUS122410EA Check
Part 6 Service Diagnosis 149
7.5 Four Way Valve Performance Check
Check No.13
R6001165
7.6 Inverter Unit Refrigerant System Check
Check No.14
Start heating operation.
NO
YES
YES
Four way valve
coil resistance at
556 ~ 614 :?
NO
Turn off the power and turn it on
again.
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
NO
YES
X800A or S80
voltage at 0 VDC with
compressor on?
X800A or
S80 voltage at
120 ~ 380 VDC for 3 sec.
after compressor starts, and
then at about 10 VDC?
(Fig. 1)
Disconnect the four way valve coil
from the connector and check the
continuity.
(Fig. 1)
Voltage at X800A or S80
120 ~ 380 VDC
10 VDC
Time
Compressor
ON
3 sec.
< Caution on resetting the power supply >
Be sure to wait for 30 sec. or more after turning off the power.
Four way valve coil
Cooling / Dry : No continuity
Heating : Continuity
Refrigerant system check
Is the discharge pipe
thermistor disconnected from
the holder?
Check for refrigerant leakage.
See the section on refrigerant
shortage detection.
(R18870)
YES
NO
Reconnect the thermistor.
Replace the refrigerant.
background
Check SiUS122410EA
150 Part 6 Service Diagnosis
7.7 Inverter Analyzer Check
Check No.15 Characteristics
Inverter analyzer: RSUK0917C
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using
an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or
some other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to
judge the cause of trouble easily and securely. Connect an inverter analyzer as a
quasi-compressor instead of compressor and check the output of the inverter.
Operation Method
Step 1
Be sure to turn the power off.
Step 2
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10 VDC
or below before carrying out the service work.
Reference:
If the terminals of the compressor are not FASTON terminals (difficult to remove the wire on the
terminals), it is possible to connect wires available on site to the outdoor unit from output side of
PCB. Do not connect them to the compressor at the same time, otherwise it may result in
incorrect detection.
Step 3
Activate the power transistor test operation from the outdoor unit.
Press the forced cooling operation ON/OFF switch for 5 seconds.
(Refer to page 161 for the position.)
Power transistor test operation starts.
Diagnose method (Diagnose according to 6 LEDs lighting status.)
1. If all the LEDs are lit uniformly, the compressor is defective.
Replace the compressor.
2. If the LEDs are not lit uniformly, check the power module.
Refer to Check No.22.
(
R22731
)
(1) Remove the terminals from
the compressor.
(2) Connect the terminals to the
terminals of the inverter
analyzer.
Compressor
Inverter analyzer
Be careful not to let the terminals (U,V,W)
touch each other. Otherwise, high voltage
is applied.
Compressor
background
SiUS122410EA Check
Part 6 Service Diagnosis 151
Caution
3. If NG in Check No.22, replace the power module.
(Replace the main PCB. The power module (IPM1) is united with the main PCB.)
If OK in Check No.22, check if there is any solder cracking on the PCB.
4. If any solder cracking is found, replace the PCB or repair the soldered section.
If there is no solder cracking, replace the PCB.
1. When the output compressor speed is low, the LEDs blink slowly. As the output compressor
speed increases, the LEDs blink quicker. (The LEDs look like they are lit.)
2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
7.8 Outdoor Fan Motor Check
Check No.16 Outdoor fan motor
2/3/4MXM, 2MXT(H)
Check if the sinusoidal voltage is generated between pins 1 - 3 and 3 - 5 when the fan motor is
manually rotated once.
R6001166
5MXM, 3/4/5MXT(H)
Check if the sinusoidal voltage is generated between pins 1 - 2 and 2 - 3 when the fan motor is
manually rotated once.
R6000524
(R15292)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.
5
4
3
2
1 Phase U
Phase V
Phase W
Free
Free
X200A
PCB
3
2
1
U (red)
S70
V (white)
W (black)
background
Check SiUS122410EA
152 Part 6 Service Diagnosis
7.9 Installation Condition Check
Check No.17
7.10 Discharge Pressure Check
Check No.18
Installation condition check
OK
Check the allowable
dimensions of the air
suction and
discharge area.
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
(R19394)
NG
YES
YES
NO
Is the discharged air
short-circuited?
NO
NO
YES
Is the outdoor heat
exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be within the operation
range.)
(R21121)
YES
YES
YES
NO
NO
NO
NO
YES
Is the air filter or
indoor/outdoor heat
exchanger dirty?
Is the
connection pipe deformed?
Is the stop valve
open?
High?
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty air filter or
indoor/outdoor heat exchanger.
Replace the compressor.
Discharge pressure check
background
SiUS122410EA Check
Part 6 Service Diagnosis 153
7.11 Outdoor Fan System Check
Check No.19 DC motor
7.12 Main Circuit Short Check
Check No.20 Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about
0 V before checking
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is or less than 1 k, short circuit occurs on the main circuit.
(R21195)
YES
NO
NO
YES
Outdoor fan system is functioning.
Check the outdoor fan system.
Reconnect the connector.
Is
the outdoor fan
running?
Fan motor lead
wire connector
disconnected?
Go to Check No. 16.
Positive terminal (+) of
digital multimeter
~ (2, 3) + (4) ~ (2, 3) – (1)
Negative terminal (–) of
digital multimeter
+ (4) ~ (2, 3) – (1) ~ (2, 3)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
background
Check SiUS122410EA
154 Part 6 Service Diagnosis
2/3/4MXM, 2MXT
R6001176
1234
Multimeter
–
~~+
–
+
background
SiUS122410EA Check
Part 6 Service Diagnosis 155
5MXM, 3/4/5MXT, 3/4/5MXTH
R6001314
7.13 Capacitor Voltage Check
Check No.21 Before this check, turn the circuit breaker off and wait for 10 minutes for prevention of electric
shock.
2/3/4MXM, 2MXT(H)
R6001172
To prevent electrical shock, use a multimeter to check that the voltage between DC +
and DC – is 50 V or less.
The surface of the test points (DC +, DC –) may be covered with the coating. Be sure to
make firm contact between the multimeter probes and the test points.
R6001173
432 1
Multimeter
–
~~+
–
+
Multimeter
(DC. voltage range)
DC–
DC+
Coating
PCB
Multimeter probe
background
Check SiUS122410EA
156 Part 6 Service Diagnosis
5MXM, 3/4/5MXT(H)
R6000525
To prevent an electrical shock, use a multimeter to check that the voltage between DC +
and DC – is 50 V or less.
The surface of the test points (DC +, DC –) may be covered with the coating. Be sure to
make firm contact between the multimeter probes and the test points.
R6000551
7.14 Power Module Check
Check No.22 Check to make sure that the voltage between (+) and (–) of the power module is about 0 V
before checking.
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the (+) or (–) terminal of the
power module and the U, V, or W terminal of the compressor with a multimeter. Evaluate the
measurement results referring to the following table.
Multimeter
(DC, voltage)
Multimeter probe
Multimeter
probe
Coating
PCB
DC (−) DC (+)
Positive terminal (+) of
digital multimeter
Power module
(+)
UVW
Power module
(–)
UVW
Negative terminal (–) of
digital multimeter
UVW
Power module
(+)
UVW
Power module
(–)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
background
SiUS122410EA Check
Part 6 Service Diagnosis 157
2/3/4MXM, 2MXT
R6001177
5MXM, 3/4/5MXT, 3/4/5MXTH
R6001315
DC+
W
V
U
DC–
UVW
DC-
DC+
background
Check SiUS122410EA
158 Part 6 Service Diagnosis
7.15 High Pressure Sensor Check
Check No.23 High pressure sensor
R6001352
Pressure sensor and voltage characteristics
Detected pressure
0 ~ 4.15 MPaG
Output voltage
0.5 V at 0 MPaG
3.5 V at 4.15 MPaG
Main PCB (A1P)
Micro-computer
A/D input
Measure DC voltage
here.
Red
Black
White
S60 (red)
(4)
(3)
(2)
(1)
High pressure sensor
background
SiUS122410EA
Part 7 Trial Operation and Field Settings 159
1. Pump Down Operation........................................................................160
2. Forced Cooling Operation ...................................................................161
3. Wiring Error Check Function ...............................................................162
4. Trial Operation ....................................................................................164
5. Field Settings ......................................................................................166
5.1 Indoor Unit............................................................................................166
5.2 Outdoor Unit .........................................................................................172
6. Silicone Grease on Power Transistor/Diode Bridge............................175
Part 7
Trial Operation and
Field Settings
background
Pump Down Operation SiUS122410EA
160 Part 7 Trial Operation and Field Settings
Reference
1. Pump Down Operation
Outline In order to protect the environment, be sure to conduct pump down operation when relocating or
disposing of the unit.
Details 2/3/4MXM, 2MXT
1. Remove the valve cap from liquid stop valve and gas stop valve.
2. Carry out forced cooling operation.
3. After 3 to 5 minutes, close the liquid stop valve with a hexagonal wrench.
4. After 3 to 4 minutes, close the gas stop valve and stop forced cooling operation.
5. Attach the valve caps once procedures are complete.
5MXM, 3/4/5MXT, 3/4/5MXTH
1. Remove the valve caps from the liquid stop valve and the gas stop valve.
2. Carry out forced cooling operation.
3. After 1 - 2 minutes, close the liquid stop valve with a hexagonal wrench.
4. After 3 - 4 minutes, close the gas stop valve and stop the forced cooling operation.
5. Attach the valve cap once procedures are complete.
R7000216
Refer to page 161 for details of forced cooling operation.
Gas stop valve
Close
Liquid stop valve
Valve cap
Hexagonal wrench
(R25062)
Close
Gas stop valve
Hexagonal
wrench
Liquid stop
valve
Valve caps
background
SiUS122410EA Forced Cooling Operation
Part 7 Trial Operation and Field Settings 161
2. Forced Cooling Operation
Outline The forced cooling operation is allowed when both the following conditions are met.
1. The outdoor unit is not abnormal and not in the 3-minute standby mode.
2. The outdoor unit is not operating.
Protection functions have priority over all other functions during forced cooling operation.
Procedure 2/3/4MXM, 2MXT
1. Turn off the power.
2. Remove the service lid (2 screws).
3. Remove the service monitor PCB switch cover (1 screw).
4. Switch SW5 and SW6 to off.
5. Turn the operation mode switch (SW2) to COOL.
6. Screw the service monitor PCB switch cover back on (1 screw).
7. Turn on the power.
8. Push the forced operation switch (SW1) above the service monitor PCB cover. (The
operation will start.)
Forced cooling operation will stop automatically after about 11 ~ 15 minutes.
To stop the operation, press the forced operation switch (SW1) again.
5MXM, 3/4/5MXT, 3/4/5MXTH
1. Turn off the power.
2. Remove the protection plate (right) (2 screws).
3. Remove the switch cover (1 screw).
4. Switch SW5 and SW6 to off.
5. Turn the operation mode switch (SW2) to COOL.
6. Screw the switch cover back on (1 screw).
7. Attach the protection plate (right) (2 screws).
8. Turn on the power.
9. Push the forced operation switch (SW1) above the service PCB cover. (The operation will
start.)
Forced cooling operation will stop automatically after about 8 minutes.
To stop the operation, push the forced operation switch (SW1) again.
R7000217
Service monitor PCB
HEAT
COOL
4
3
2
1
2
1
E
D
C
B
A
COOL
4
3
2
1
2
1
E
D
C
B
A
Screw
Remove
the switch
cover
Forced operation switch (SW1)
•Switch SW5 and SW6 to off.
•Set to COOL.
Operation mode switch (SW2)
2
1
ON OFF
4
3
ON
OFF
2
1
HEAT
COOL
SW6
SW5
background
Wiring Error Check Function SiUS122410EA
162 Part 7 Trial Operation and Field Settings
3. Wiring Error Check Function
Outline Wiring error check function is designed for the microcomputer to correct wiring errors itself.
If local wiring is unclear in the case of buried piping, for example, just press the wiring error
check switch on the outdoor unit. Even if the connections for Room A and Room B are
confused, the system may run without a hassle.
Note that this check function does not work in the following cases.
For 3-minute standby period after the power is turned on or after the compressor has
stopped.
When the outdoor temperature is below 5°C (41°F).
If the indoor unit is in trouble (also in case of all-room transmission failure).
When the piping and wiring are perfect, there is no need to use this function.
Procedure 1. Press the wiring error check switch (SW3) on the service monitor PCB of the outdoor unit,
and the wiring error check function is activated.
2. In about 15 ~ 20 minutes, the check finishes automatically.
3. When the check is over, the service monitor LED indicators start blinking.
Self-correction complete…The LED indicators blink one after another (only connected
parts).
Self-correction impossible…The LED indicators blink all at the same time.
Transmission failure occurs at any of the indoor units.
The indoor unit heat exchanger thermistor is disconnected.
An indoor unit is in trouble (if a trouble occurs during the wiring error checking).
Emergency stop…If any of the LED indicators stays on, follow the diagnostic procedure.
LED 1 2 3 4 5 Judgment
Status
Blinking one after another Self-correction completed
All blinking Self-correction impossible
Any of the LEDs stay on Emergency stop
Service monitor PCB
(R22003)
A
1
2
3
4
5
Wiring error
check switch
(SW3)
background
SiUS122410EA Wiring Error Check Function
Part 7 Trial Operation and Field Settings 163
Notes
Details Wiring error check is realized by feeding refrigerant one by one through each piping port and
detecting indoor heat exchanger temperature with the indoor heat exchanger thermistor in
each room to see if the temperature changes in correct order.
During wiring error check, freezing (cracking) noise may be heard from the indoor unit. This
is not a malfunction. The noise is generated by the heat exchanger that is cooled below 0°C
(32°F) to make temperature change more visible.
Indoor fan motor turns on and off during wiring error check.
Wiring error check result is indicated using service monitor LEDs when all the checking
procedures are completed. LEDs stop blinking when the system returns to the normal operation.
In a multi system with 2 ports (Port A and Port B), LED 1 and LED 2 indicate wiring to Room A
and Room B respectively. The LED that blinks first and second indicate piping Port A and Port B
respectively.
Ex: Suppose the LED indicators are blinking as follows.
In this example, Port A and wiring to Room B are connected to the same room and Port B and
wiring to Room A are connected to another room. Incorrect wiring is then corrected
automatically.
1. Wrongly connected liquid and gas pipes cannot be self-corrected. Be sure to make the liquid
pipe and the gas pipe in pairs.
2. To cancel the wiring error check procedure halfway, press the wiring error check switch
again.
In this case, the memory of the microcomputer returns to its initial status (Room A wiring
Port A piping, Room B wiring Port B piping).
3. When replacing the outdoor unit PCB, be sure to use this function.
4. Make the priority room setting after wiring error check. If you set the priority room before
wiring error check, the prioritized room may be changed after self-correction.
A 1 2 3 4 5
Green Red
Green Red
Green Red
A 1 2 3 4 5
A 1 2 3 4 5
(R22004)
L
E
D
L
E
D
L
E
D
Wiring
Outdoor unit
Indoor unit
Piping
(R22274)
Wiring
Piping
A
B
A
B
background
Trial Operation SiUS122410EA
164 Part 7 Trial Operation and Field Settings
4. Trial Operation
Outline During the trial operation, first check the operation of each unit individually. After this, check
the simultaneous operation of all indoor units. Check both COOL and HEAT operations.
1. Measure the supply voltage and make sure that it is within the specified range.
2. In COOL operation, select the lowest programmable temperature. In HEAT operation, select
the highest programmable temperature.
When operating the air conditioner in COOL operation in winter, or HEAT operation in
summer, activate trial operation mode by following the instructions in the installation
manual for the indoor unit.
3. Carry out the trial operation following the instructions in the operation manual to ensure that
all functions and parts, such as the movement of the flap, are working properly.
To protect the air conditioner, restart operation is disabled for 3 minutes after the system
has been turned off.
When trial operation is conducted in heating operation directly after the circuit breaker is
turned on, in some cases no air will be output for about 3 to 20 minutes in order to protect
the air conditioner.
During COOL operation, frost may form on the gas stop valve or other parts. This is
normal.
4. After running the unit for about 20 minutes, measure the temperatures at the indoor unit inlet
and outlet.
If the measurements are above the values shown in the table below, then they are
normal.
5. After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to
28°C) in COOL operation, 68°F to 75°F (20°C to 24°C) in HEAT operation).
Procedure When operating the air conditioner in cooling operation in winter, set it to the trial operation
mode using the following method.
1. Press both of TEMP buttons and OFF button at the same time.
2. Press either of TEMP ▲ or TEMP ▼ button and select "T".
3. Press FAN button.
4. Press COOL or HEAT button. ("T" will be displayed and the unit will start forced cooling
operation.)
5. Trial operation will stop automatically after about 30 minutes. To stop trial operation, press
OFF button
About 14°F (8°C)
Temperature difference
between inlet and outlet
About 36°F (20°C)
COOL operation
HEAT operation
(When running in one room)
background
SiUS122410EA Trial Operation
Part 7 Trial Operation and Field Settings 165
Note(s)
R7000445
The air conditioner draws a small amount of power in its standby mode. If the system is not
to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restores
the original operation mode when the circuit breaker is opened again.
Test Items
1, 5
3
1, 2
4
4
2
Test items Symptom
Indoor and outdoor units are installed securely. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain hose
extension are thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
System is properly earthed. Electrical leakage
Only specified wires are used for all wiring and all wires
connected correctly.
No operation or burn damage
Indoor or outdoor unit’s air inlet or outlet are
unobstructed.
Incomplete cooling/heating function
Stop valves are opened. Incomplete cooling/heating function
Indoor unit properly receives remote controller
commands.
No operation
Pipes and wires are connected to the corresponding
terminal blocks/connection ports for the connected unit.
No cooling/heating
The priority room setting is set for only 1 room. The priority room setting will not
function.
Explain to the user that when using a smartphone for
operation, it is necessary to prepare a repeater, or
similar device, if the signal from the wireless LAN router
is weak near the air conditioner.
Air conditioner not responding to
smartphone
background
Field Settings SiUS122410EA
166 Part 7 Trial Operation and Field Settings
Note(s)
Caution
5. Field Settings
5.1 Indoor Unit
5.1.1 When 2 Units are Installed in 1 Room
Outline When 2 indoor units are installed in one room, the 2 wireless remote controllers can be set for
different addresses. Change the address setting of one of the 2 units.
Procedure ARC480A83 Wireless Remote Controller
1. Remove the battery cover of the remote controller.
2. Cut the address jumper.
3. Press the center of TEMP button and OFF button on the remote controller at the same time.
4. Press TEMP ▲ or TEMP ▼ button to select A (address setting).
5. Press FAN button to enter the address setting mode.
Then, the indoor unit OPERATION lamp will blink for about 1 minute.
6. Press the indoor unit ON/OFF switch while the OPERATION lamp is blinking.
7. Press FAN button on the remote controller for 5 seconds to return to the previous display.
If setting could not be carried out completely while the OPERATION lamp was blinking, carry
out the setting process once again from the beginning.
Replace the remote controller if you cut a jumper unintentionally
.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
R7000030
R7000447
Indoor Unit
R7000448
Address
EXIST
Jumper
CUT
1
2
Jumper
4
3, 4
3
5, 7
Indoor unit
ON/OFF switch
OPERATION
lamp
background
SiUS122410EA Field Settings
Part 7 Trial Operation and Field Settings 167
Procedure BRC073A6 Wired Remote Controller
<Basic screen>
6-1 Press and hold the Cancel
button for 4 seconds or longer.
The Service Settings menu is
displayed.
6-1
82°F
Cool
Set to
<Service Settings>
6-2 Select Field Settings and press
the Menu/Enter button.
6-2
Test Operation
Maintenance Contact
Field Settings
Error History
Service Settings
SettingReturn
<Field settings>
6-3 Highlight the "Mode No.", and
select the desired "Mode No." by
using the (Up/Down) buttons.
6-3
Field Settings
Mode
1b
SettingReturn
● The current settings are displayed.
● CODE NO. " -- " means that there is no function
available.
6-4 Highlight the SECOND CODE.
of the FIRST CODE NO. to be
changed and select the desired
SECOND CODE NO. by using the
(Up/Down) buttons. Multiple
identical mode number settings
are available.
Press the Menu/Enter
button.
6-5 Press the Menu/Enter button. The
6-6 Select Yes and press the Menu/
Enter button. The settings are
saved and the Field settings
screen returns.
6-5
6-6
NoYes
Field Settings
Save the settings?
SettingReturn
<Field Settings>
FIRST CODE (SW) NO.
SECOND CODE NO.
background
Field Settings SiUS122410EA
168 Part 7 Trial Operation and Field Settings
6-7 After all changes are completed,
press the Cancel button twice.
6-8 The backlight goes out and
"Checking the connection. Please
stand by" is displayed during
initialization. After the initialization,
the Basic screen returns.
Mode
No.
First
Code
No.
Description of the setting
Second code No.
01 02 03 04
1b
8 Daylight Saving Time Disable Enable* — —
11 (Private use) NA* NA — —
13 Basic screen display Icon+Text* Icon — —
15 (Private use) NA* NA — —
1c
0 (Private use) NA NA* — —
2 (Private use) NA NA* — —
4 (Private use) NA NA* — —
5 (Private use) NA* — — —
6 (Private use) NA* — — —
14 (Private use) NA* NA — —
1e
1 (Private use) NA NA* — —
2 Setback function Do not use Heat only Cool only Cool and Heat*
5 (Private use) NA NA* — —
6 (Private use) NA NA* — —
8 (Private use) NA* — — —
9 (Private use) NA NA* — —
a (Private use) NA* — — —
* Factory default setting
background
SiUS122410EA Field Settings
Part 7 Trial Operation and Field Settings 169
5.1.2 Temperature Display Switch
ARC480A83 You can select Fahrenheit or Celsius for temperature display.
Press TEMP ▲ button and ON TIMER buttons simultaneously for 5 seconds to change the
unit of temperature display.
BRC073A6 You can select Fahrenheit or Celsius for temperature display.
Display the Configuration menu.
Press the ▲ or ▼ buttons to select "Celsius / Fahrenheit" and press the Menu/Enter
button.
Press the ▲ or ▼ buttons to select Celsius or Fahrenheit.
Press the Menu/Enter button to confirm the settings and to return to the Basic Screen.
(R14477)
Display
Celsius / Fahrenheit
Contrast Adjustment
Configuration
SettingReturn
Fahrenheit
Celsius / Fahrenheit
Celsius / Fahrenheit
SettingReturn
background
Field Settings SiUS122410EA
170 Part 7 Trial Operation and Field Settings
5.1.3 Service Mode of Wireless Remote Controller
The remote controller mode is hierarchized by special conditions and operation content.
Refer below for the main hierarchy of the menu.
R5000463
Normal mode
Service mode
Normal mode is operated by the end user.
Simplified service diagnosis on normal mode
The code indication changes every time the TIMER CANCEL button is
pressed.
Service Check mode
In service check mode, the left-side number and the right-side
number can be identified individually.
Address setting mode
This mode sets the address corresponding to the jumper position.
Trial operation mode
Press for
5 seconds
Press for
5 seconds
Press for 5 seconds
Pressing the center of the temperature adjustment
button has the same function as pressing both
buttons simultaneously.
Proceed to
1
background
SiUS122410EA Field Settings
Part 7 Trial Operation and Field Settings 171
Note(s)
R5000462
Overview of Settings
After replacing the indoor unit PCB, all the values are returned to the factory settings.
Use the remote controller to change the settings again.
When only the remote controller is replaced, the values stored in the PCB remain the same.
There is no hassle to the end user.
1
Field settings mode
Room temperature adjustment settings may be applied.
When changing the settings, make sure the button was correctly pressed by listening for
the beep sound. (The beep can be heard even if the button is pressed within a setting
which is unavailable. In this case, the setting will be invalid.)
Press the buttons to change the setting items and the setting values.
•
Confirm/Send
Setting items
Setting values
Setting items Setting options
Factory
Setting
Contents
3
Suspend 0: OFF
1: ON
1
Activation/Deactivation of Standby electricity saving
(suspend function)
0: Power will still be supplied to the outdoor unit PCB
after the unit operation stopped.
1: Three minutes after the unit operation stops, the
power supply to the outdoor unit PCB is shut off.
(This function is only available on certain models.)
4
Dry keep 0: OFF
1: ON
0
Stops the airflow of indoor unit when the thermostat is
OFF to prevent increase of room humidity.
0: When thermostat is OFF, the fan rotor will still be
OPERATING, hence there is airflow.
1: When thermostat is OFF, the fan rotor will be
STOPPED, hence there is no airflow.
5
Preheating control 0: OFF
1: ON
0
Activation/Deactivation of compressor preheating
0: Deactivation of compressor preheating
1: Activation of compressor preheating
6
Room temperature
adjustment (cooling)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in cooling
operation.
Used for adjustment of room temperature control.
7
Room temperature
adjustment (heating)
0: Low 2 (–2°C)
1: Low 1 (–1°C)
2: Standard (0°C)
3: High 1 (+1°C)
4: High 2 (+2°C)
2
Adjustment of indoor temperature thermistor in heating
operation.
Used for adjustment of room temperature control.
10
Auto-restart 0: OFF
1: ON
1
This setting decides the operation of the unit when the
power supply resumed after a power supply shutdown
(i.e. power failure).
0: When the power supply resumes, the unit remains in
stopped operation.
1: When the power supply resumes, the unit resumes
the operation before the shutdown of power supply.
12
Warmer airflow setting 0: OFF
1: ON
0
This setting makes the discharge airflow temperature
warmer.
background
Field Settings SiUS122410EA
172 Part 7 Trial Operation and Field Settings
5.2 Outdoor Unit
5.2.1 Priority Room Setting
Outline The indoor unit for which priority room setting is applied takes priority in the following cases.
Operation mode priority
The operation mode of the prioritized room takes precedence. For example, when the
prioritized indoor unit starts cooling operation, the other indoor units which have been in
heating operation enter the standby mode. Heating operation will resume if the prioritized
indoor unit stops cooling operation.
Priority during POWERFUL operation
The electronic expansion valves are controlled to provide more capacity to the prioritized
room and the capacities for the other indoor units will be slightly reduced.
OUTDOOR UNIT QUIET operation priority
When the OUTDOOR UNIT QUIET operation is selected in the prioritized room, the outdoor
unit runs quietly.
Without priority room setting, OUTDOOR UNIT QUIET operation starts only when the
function is set for all the operating indoor units.
Procedure 1. Turn the circuit breaker off before changing the setting.
2. Turn on the one of the switches of the SW4 on the service monitor PCB.
Only one room can be set as the priority room.
3. Turn the power on.
R7000367
Service monitor PCB
HEAT
COOL
4
3
2
1
2
1
E
D
C
B
A
COOL
4
3
2
1
2
1
E
D
C
B
A
Screw
Remove
the switch
cover
Priority room setting switch (SW4)
ON OFF
E
D
C
B
A
background
SiUS122410EA Field Settings
Part 7 Trial Operation and Field Settings 173
Note(s)
5.2.2 COOL/HEAT Mode Lock
Use the X161A or S15 connector to set the unit to cooling only or heating only.
Setting to heating only (H): short-circuit the pins 1 and 3 of the connector X161A or S15.
Setting to cooling only (C): short-circuit the pins 3 and 5 of the connector X161A or S15.
The following specifications apply to the connector housing and pins.
JST products:
Housing: VHR-5N
Pin: SVH-21T-P1.1
2/3/4MXM, 2MXT(H)
R7000449
5MXM, 3/4/5MXT(H)
R7000163
Forced operation is also possible in cooling/heating mode
31
HEAT mode (H)
COOL mode (C)
5
Top panel
Right side panel
Shield
plate
Front panel
Hooks
HEAT mode (H)
COOL mode (C)
S15 connector
5
3
1
background
Field Settings SiUS122410EA
174 Part 7 Trial Operation and Field Settings
5.2.3 NIGHT QUIET Mode
Outline If NIGHT QUIET mode is to be used, initial settings must be made when the unit is installed.
Explain the function of NIGHT QUIET mode, as described below, to the customer, and confirm
whether or not the customer wants to use NIGHT QUIET mode.
NIGHT QUIET mode function reduces operating noise of the outdoor unit at nighttime. This
function is useful if the customer is worried about the effects of the operating noise on the
neighbors. However, if NIGHT QUIET mode is running, cooling capacity is reduced.
Procedure Turn on the SW6-1 on the service monitor PCB of the outdoor unit.
5.2.4 Drain Pan Heater
Applicable
Models
2MXM18AVJU9, 3MXM24AVJU9, 4MXM36AVJU9, 5MXM48AVJU9
2MXT18AVJU9, 3MXT24AVJU9, 4MXT36AVJU9, 5MXT40AVJU9
Outline In high humidity areas or heavy snow areas, it is recommended to attach a drain pan heater to
prevent ice build-up from the bottom frame.
Field setting is necessary when attaching the optional drain pan heater.
Procedure 1. Attach the drain pan heater in accordance with the installation manual included with the
drain pan heater.
2. Using a tool such as nippers, cut the jumper (J_DP) on the service monitor PCB.
R7000372
Service monitor PCB
HEAT
COOL
4
3
2
1
2
1
E
D
C
B
A
2
1
ON OFF
COOL
4
3
2
1
2
1
E
D
C
B
A
Screw
Remove
the switch
cover.
Night Quiet mode
setting switch
(SW6-1)
(R22008)
Service monitor PCB
HEAT
COOL
4
3
2
1
2
1
E
D
C
B
A
4
3
2
1
2
1
E
D
C
B
Jumper (J_DP)
Remove
the switch
cover.
Screw
background
SiUS122410EA Silicone Grease on Power Transistor/Diode Bridge
Part 7 Trial Operation and Field Settings 175
Note(s)
6. Silicone Grease on Power Transistor/Diode
Bridge
Outline Apply the specified silicone grease to the heat generation part of a power transistor/diode bridge
when you replace an outdoor unit PCB. The silicone grease encourages the heat dissipation of
a power transistor/diode bridge.
Details 1. Wipe off the old silicone grease on the refrigerant pipe completely.
2. Apply the silicone grease on the heat sink evenly. See the illustrations below for examples of
application.
3. Tighten the screws of cover.
4. Make sure that the heat generation parts are firmly contacted to refrigerant pipe.
Smoke emission may be caused by bad heat radiation when the silicone grease is not
appropriately applied.
OK: Evenly applied
R7000168
NG: Not evenly applied
R7000158
NG: Foreign matter is stuck.
R7000159
Power transistor
(or diode bridge)
Silicone grease
Silicone grease,
which you do not
need to apply.
Heat sink
PCB
Refrigerant pipe
Cover
Foreign matter
background
SiUS122410EA
176 Part 8 Appendix
1. Piping Diagrams..................................................................................177
1.1 Indoor Unit............................................................................................177
1.2 Outdoor Unit .........................................................................................178
2. Wiring Diagrams..................................................................................182
2.1 Indoor Unit............................................................................................182
2.2 Outdoor Unit .........................................................................................184
3. Operation Limit....................................................................................194
Part 8
Appendix
background
SiUS122410EA Piping Diagrams
Part 8 Appendix 177
1. Piping Diagrams
1.1 Indoor Unit
CTXV07AVJU9, FTXV09/12AVJU9 FTXV15/18AVJU9
FTXV24AVJU9
4D150950
4D091769E
4D091768C
background
Piping Diagrams SiUS122410EA
178 Part 8 Appendix
1.2 Outdoor Unit
2MXM18AVJU9
3MXM24AVJU9
3D149796
3D149798
background
SiUS122410EA Piping Diagrams
Part 8 Appendix 179
4MXM36AVJU9
5MXM48AVJU9, 5MXT40AVJU9, 5MXTH40AVJU9
3D149799
3D157508
background
Piping Diagrams SiUS122410EA
180 Part 8 Appendix
2MXT18AVJU9, 2MXTH18AVJU9
3MXT24AVJU9, 3MXTH24AVJU
3D149797
3D157510
background
SiUS122410EA Piping Diagrams
Part 8 Appendix 181
4MXT36AVJU9, 4MXTH36AVJU9
3D157509
background
Wiring Diagrams SiUS122410EA
182 Part 8 Appendix
Note
2. Wiring Diagrams
2.1 Indoor Unit
CTXV07AVJU9, FTXV09/12AVJU9
A1P: Control PCB
A2P: Display/signal receiver PCB
A3P: Wireless LAN connection PCB
A4P: Humidity sensor PCB
Refer to page 26 for Printed Circuit Board Connector Wiring Diagram.
3D147521A
background
SiUS122410EA Wiring Diagrams
Part 8 Appendix 183
Note
FTXV15/18/24AVJU9
A1P: Control PCB
A2P: Display/signal receiver PCB
A3P: Wireless LAN connection PCB
A4P: Humidity sensor PCB
Refer to page 26 for Printed Circuit Board Connector Wiring Diagram.
3D147460B
background
Wiring Diagrams SiUS122410EA
184 Part 8 Appendix
Note(s)
2.2 Outdoor Unit
2MXM18AVJU9, 2MXT18AVJU9
A1P: Main PCB
A2P: Sub PCB
A3P: Service monitor PCB
Refer to page 28 for Printed Circuit Board Connector Wiring Diagram.
C: 3D149179
background
SiUS122410EA Wiring Diagrams
Part 8 Appendix 185
Note(s)
3MXM24AVJU9
A1P: Main PCB
A2P: Sub PCB
A3P: Service monitor PCB
Refer to page 28 for Printed Circuit Board Connector Wiring Diagram.
C: 3D149180
background
Wiring Diagrams SiUS122410EA
186 Part 8 Appendix
Note(s)
4MXM36AVJU9
A1P: Main PCB
A2P: Sub PCB
A3P: Service monitor PCB
Refer to page 28 for Printed Circuit Board Connector Wiring Diagram.
C: 3D149197
background
SiUS122410EA Wiring Diagrams
Part 8 Appendix 187
Note(s)
5MXM48AVJU9, 5MXT40AVJU9
A1P: Main PCB
A2P: Service monitor PCB
Refer to page 31 for Printed Circuit Board Connector Wiring Diagram.
C: 3D156355
background
Wiring Diagrams SiUS122410EA
188 Part 8 Appendix
Note(s)
2MXTH18AVJU9
A1P: Main PCB
A2P: Sub PCB
A3P: Service monitor PCB
Refer to page 28 for Printed Circuit Board Connector Wiring Diagram.
C: 3D149587
background
SiUS122410EA Wiring Diagrams
Part 8 Appendix 189
Note(s)
3MXT24AVJU9
A1P: Main PCB
A2P: Service monitor PCB
Refer to page 31 for Printed Circuit Board Connector Wiring Diagram.
C: 3D156320
background
Wiring Diagrams SiUS122410EA
190 Part 8 Appendix
Note(s)
3MXTH24AVJU9
A1P: Main PCB
A2P: Service monitor PCB
Refer to page 31 for Printed Circuit Board Connector Wiring Diagram.
C: 3D156321
background
SiUS122410EA Wiring Diagrams
Part 8 Appendix 191
Note(s)
4MXT36AVJU9
A1P: Main PCB
A2P: Service monitor PCB
Refer to page 31 for Printed Circuit Board Connector Wiring Diagram.
C: 3D156353
background
Wiring Diagrams SiUS122410EA
192 Part 8 Appendix
Note(s)
4MXTH36AVJU9
A1P: Main PCB
A2P: Service monitor PCB
Refer to page 31 for Printed Circuit Board Connector Wiring Diagram.
C: 3D156354
background
SiUS122410EA Wiring Diagrams
Part 8 Appendix 193
Note(s)
5MXTH40AVJU9
A1P: Main PCB
A2P: Service monitor PCB
Refer to page 31 for Printed Circuit Board Connector Wiring Diagram.
C: 3D156356
background
Operation Limit SiUS122410EA
194 Part 8 Appendix
3. Operation Limit
2MXM18AVJU9, 3MXM24AVJU9, 4MXM36AVJU9
2MXT18AVJU9, 2MXTH18AVJU9
3D048149D
3D101428B
background
SiUS122410EA Operation Limit
Part 8 Appendix 195
5MXM48AVJU
3MXT24AVJU, 3MXTH24AVJU, 4MXT36AVJU, 4MXTH36AVJU, 5MXT40AVJU, 5MXTH40AVJU
3D158370
3D158371
background
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
©
All rights reserved
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorized importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
Specifications, designs and other content appearing in this brochure are current as of October 2025 but subject to change without notice.
SiUS122410EA
10/2025 AK.K
Service Manual / Multi-Split Type Air Conditioners MXM-A, MXT-A, MXTH-A Series SiUS122410EA