Servi ce
Manual
SiUS092519E
Inverter Pair
Duct Connected Type FDMA-A Series
[Applied Models]
Inverter Pair : Heat Pump

SiUS092519E
i Table of Contents
Introduction .................................................................................... 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................7
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Part 1 General Information .......................................................... 12
1. Applicable Models .................................................................................13
2. Functions...............................................................................................14
Part 2 Specifications.................................................................... 16
1. Specifications ........................................................................................17
Part 3 Printed Circuit Board Connector Wiring Diagram............. 20
1. Indoor Unit.............................................................................................21
2. Outdoor Unit..........................................................................................23
2.1 RXP09/12AVJU9....................................................................................23
2.2 RXP15/18/24AVJU9...............................................................................24
Part 4 Functions and Control ....................................................... 25
1. Common Functions ...............................................................................26
1.1 Temperature Control ..............................................................................26
1.2 Frequency Principle................................................................................26
1.3 Fan Speed Control for Indoor Unit .........................................................28
1.4 Program Dry Operation ..........................................................................28
1.5 Automatic Cooling/Heating Change-over ...............................................29
1.6 Clock and Calendar Setting (With BRC1NRV71)...................................30
1.7 Schedule Timer Operation (With BRC1NRV71).....................................32
1.8 Drain Pump Control................................................................................36
1.9 Hot Start Control (In Heating Operation Only)........................................38
1.10 Other Functions......................................................................................39
2. Thermistor Functions ............................................................................40
3. Control Specification .............................................................................41
3.1 Mode Hierarchy ......................................................................................41
3.2 Frequency Control..................................................................................41
3.3 Controls at Mode Changing/Start-up......................................................43
3.4 Discharge Pipe Temperature Control.....................................................45
3.5 Input Current Control..............................................................................46
3.6 High Pressure Protection Control...........................................................47
3.7 Freeze-up Protection Control .................................................................47
3.8 Heating Peak-cut Control .......................................................................48
3.9 Outdoor Fan Control...............................................................................49
3.10 Liquid Compression Protection Function................................................49
3.11 Defrost Control .......................................................................................50
3.12 Electronic Expansion Valve Control .......................................................53
3.13 Malfunctions ...........................................................................................56

SiUS092519E
Table of Contents ii
Part 5 Remote Controller ............................................................. 57
1. Applicable Remote Controller ...............................................................58
2. BRC1NRV71 .........................................................................................59
Part 6 Service Diagnosis .............................................................. 65
1. General Problem Symptoms and Check Items .....................................67
2. Troubleshooting with LED .....................................................................68
2.1 Indoor Unit..............................................................................................68
2.2 Outdoor Unit ...........................................................................................68
3. Service Diagnosis .................................................................................69
3.1 BRC1NRV71 ..........................................................................................69
4. Error Codes and Description.................................................................71
5. Troubleshooting for Indoor Unit.............................................................72
5.1 External Protection Device Abnormality .................................................72
5.2 Refrigerant Leak Detection (Confirmed).................................................73
5.3 Refrigerant Leak Detection (Monitoring) ................................................75
5.4 Indoor Unit PCB Abnormality .................................................................76
5.5 Drain Level Control System Abnormality................................................77
5.6 Indoor Fan Motor (DC Motor) or Related Abnormality ...........................78
5.7 Indoor Fan PCB Abnormality..................................................................80
5.8 Humidifier or Related Abnormality..........................................................81
5.9 Defective Capacity Setting .....................................................................82
5.10 Transmission Abnormality between Indoor Unit Control PCB and
Fan PCB.................................................................................................83
5.11 Thermistor or Related Abnormality.........................................................85
5.12 Refrigerant Leak Detection Sensor Failure ............................................86
5.13 Refrigerant Leak Detection Sensor Disconnection.................................87
5.14 Remote Controller Thermistor Abnormality ............................................88
5.15 Low-voltage Detection or Over-voltage Detection..................................89
5.16 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)......91
5.17 Signal Transmission Error (Between Indoor Unit and Remote
Controller)...............................................................................................93
5.18 Signal Transmission Error (Between MAIN/SUB Remote Controllers) ..94
5.19 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ...............95
5.20 Address Duplication of Centralized Controller........................................96
6. Troubleshooting for Outdoor Unit..........................................................97
6.1 Outdoor Unit PCB Abnormality...............................................................97
6.2 Actuation of High Pressure Switch .........................................................98
6.3 OL Activation (Compressor Overload) ...................................................99
6.4 Compressor Lock .................................................................................101
6.5 DC Fan Lock ........................................................................................102
6.6 Input Overcurrent Detection .................................................................103
6.7 Electronic Expansion Valve Coil Abnormality.......................................104
6.8 Four Way Valve Abnormality................................................................105
6.9 Discharge Pipe Temperature Control...................................................107
6.10 High Pressure Control in Cooling .........................................................108
6.11 System Shutdown due to Temperature Abnormality in the
Compressor..........................................................................................110
6.12 Compressor Sensor System Abnormality ............................................111
6.13 High Pressure Switch System Abnormality ..........................................112

SiUS092519E
iii Table of Contents
6.14 Position Sensor Abnormality ................................................................113
6.15 Fan IPM temperature error...................................................................116
6.16 DC Voltage/Current Sensor Abnormality..............................................117
6.17 Thermistor or Related Abnormality (Outdoor Unit)...............................118
6.18 Electrical Box Temperature Rise..........................................................120
6.19 Radiation Fin Temperature Rise ..........................................................121
6.20 Output Overcurrent Detection ..............................................................122
6.21 IGBT temperature error ........................................................................124
6.22 Signal Transmission Error on Outdoor Unit PCB .................................125
7. Check ..................................................................................................126
7.1 Thermistor Resistance Check ..............................................................126
7.2 Indoor Fan Motor Connector Check .....................................................127
7.3 Power Supply Waveform Check...........................................................127
7.4 Electronic Expansion Valve Check.......................................................128
7.5 Four Way Valve Performance Check ...................................................129
7.6 Inverter Unit Refrigerant System Check...............................................129
7.7 Inverter Analyzer Check .......................................................................130
7.8 Outdoor Fan Motor Check....................................................................132
7.9 Installation Condition Check.................................................................132
7.10 Discharge Pressure Check...................................................................133
7.11 Outdoor Fan System Check .................................................................133
7.12 Main Circuit Short Check......................................................................134
7.13 Power Module Check ...........................................................................136
Part 7 Trial Operation and Field Settings .................................. 138
1. Pump Down Operation........................................................................139
2. Forced Cooling Operation ...................................................................140
3. Trial Operation ....................................................................................141
4. Field Settings ......................................................................................143
4.1 How to Change the Field Settings........................................................143
4.2 Overview of Field Settings....................................................................145
4.3 MAIN/SUB Setting when Using 2 Wired Remote Controllers...............148
5. Field Settings for Outdoor Unit............................................................149
5.1 Facility Setting (cooling at low outdoor temperature) ...........................149
5.2 Warmer Airflow Setting.........................................................................150
5.3 Drain Pan Heater..................................................................................151
6. Silicone Grease on Power Transistor/Diode Bridge............................152
Part 8 Appendix .......................................................................... 153
1. Piping Diagrams..................................................................................154
1.1 Indoor Unit............................................................................................154
1.2 Outdoor Unit .........................................................................................154
2. Wiring Diagrams..................................................................................156
2.1 Indoor Unit............................................................................................156
2.2 Outdoor Unit .........................................................................................157
3. Operation Limit....................................................................................159

SiUS092519E
Introduction 1
1. Safety Cautions.......................................................................................2
1.1 Warnings and Cautions Regarding Safety of Workers.............................2
1.2 Warnings and Cautions Regarding Safety of Users.................................7
2. Icons Used ............................................................................................10
3. Revision History ....................................................................................11
Introduction

Safety Cautions SiUS092519E
2 Introduction
1. Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
Caution Items The caution items are classified into Warning and Caution. The Warning items are
especially important since death or serious injury can result if they are not followed closely. The
Caution items can also lead to serious accidents under some conditions if they are not
followed. Therefore, be sure to observe all the safety caution items described below.
Pictograms This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown in the illustration or near the symbol.
1.1 Warnings and Cautions Regarding Safety of Workers
This manual is for the
person in charge of
maintenance and
inspection.
This appliance is
filled with R-32.
Refrigerant
Safety
Group A2L
Warning
Do not store equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to disconnect the power cable from the socket before
disassembling equipment for repair.
Working on equipment that is connected to the power supply may cause
an electrical shock.
If it is necessary to supply power to the equipment to conduct the repair or
inspect the circuits, do not touch any electrically charged sections of the
equipment.
If refrigerant gas is discharged during repair work, do not touch the
discharged refrigerant gas.
Refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the
compressor at the welded section, evacuate the refrigerant gas
completely at a well-ventilated place first.
If there is gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it
may cause injury.
If refrigerant gas leaks during repair work, ventilate the area.
Refrigerant gas may generate toxic gases when it contacts flames.
Be sure to discharge the capacitor completely before conducting
repair work.
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
A charged capacitor may cause an electrical shock.

SiUS092519E Safety Cautions
Introduction 3
Do not turn the air conditioner on or off by plugging in or
unplugging the power cable.
Plugging in or unplugging the power cable to operate the equipment may
cause an electrical shock or fire.
Be sure to wear a safety helmet, gloves, and a safety belt when
working in a high place (more than 2 m (6.5 ft)).
Insufficient safety measures may cause a fall.
In case of R-32 / R-410A refrigerant models, be sure to use pipes,
flare nuts and tools intended for the exclusive use with the R-32 /
R-410A refrigerant.
The use of materials for R-22 refrigerant models may cause a serious
accident, such as a damage of refrigerant cycle or equipment failure.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
Caution
Do not repair electrical components with wet hands.
Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner with water.
Washing the unit with water may cause an electrical shock.
Be sure to provide an earth / grounding when repairing the
equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable
when cleaning the equipment.
The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools.
The use of inappropriate tools may cause injury.
Be sure to check that the refrigerating cycle section has cooled
down enough before conducting repair work.
Working on the unit when the refrigerating cycle section is hot may cause
burns.
Conduct welding work in a well-ventilated place.
Using the welder in an enclosed room may cause oxygen deficiency.
Warning

Safety Cautions SiUS092519E
4 Introduction
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are
necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating
system, provisions under Work procedure to No ignition sources below shall be
completed prior to conducting work on the system.
Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a
flammable gas or vapor being present while the work is being performed.
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of
work being carried out. Work in confined spaces shall be avoided.
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work,
to ensure the technician is aware of potentially toxic or flammable atmospheres.
Ensure that the leak detection equipment being used is suitable for use with all applicable
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any associated parts,
appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or
CO
2
fire extinguisher adjacent to the charging area.
No ignition sources
No person carrying out work in relation to a refrigerating system which involves exposing
any pipe work shall use any sources of ignition in such a manner that it may lead to the risk
of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept
sufficiently far away from the site of installation, repairing, removing and disposal, during
which refrigerant can possibly be released to the surrounding space. Prior to work taking
place, the area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the
system or conducting any hot work. A degree of ventilation shall continue during the period
that the work is carried out. The ventilation should safely disperse any released refrigerant
and preferably expel it externally into the atmosphere.
Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose and to the
correct specification.
At all times the manufacturer’s maintenance and service guidelines shall be followed. If in
doubt, consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
The actual refrigerant charge is in accordance with the room size within which the
refrigerant containing parts are installed;
The ventilation machinery and outlets are operating adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for
the presence of refrigerant;
Marking to the equipment continues to be visible and legible. Markings and signs that are
illegible shall be corrected;
Refrigerating pipe or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components, unless
the components are constructed of materials which are inherently resistant to being
corroded or are suitably protected against being so corroded.

SiUS092519E Safety Cautions
Introduction 5
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. If a fault exists that could compromise safety, then no
electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault
cannot be corrected immediately but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be reported to the owner of the equipment so all
parties are advised.
Initial safety checks shall include:
that capacitors are discharged: this shall be done in a safe manner to avoid possibility of
sparking;
that no live electrical components and wiring are exposed while charging, recovering or
purging the system;
that there is continuity of earth bonding.
Repairs to sealed components
Sealed electrical components shall be replaced.
Repair to intrinsically safe components
Intrinsically safe components must be replaced.
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual vibration from sources such as compressors or
fans.
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or
detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall
not be used.
The following leak detection methods are deemed acceptable for all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks but, in the case of
flammable refrigerants, the sensitivity may not be adequate, or may need re-calibration.
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant
used. Leak detection equipment shall be set at a percentage of the LFL (lower flammability
limit) of the refrigerant and shall be calibrated to the refrigerant employed, and the
appropriate percentage of gas (25% maximum) is confirmed.
Leak detection fluids are also suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant
and corrode the copper pipe-work.
Note: Examples of leak detection fluids are
bubble method,
fluorescent method agents.
If a leak is suspected, all naked flames shall be removed/extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the system
remote from the leak. Removal of refrigerant shall be according to the following clause,
Removal and evacuation.
Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose –
conventional procedures shall be used. However, for flammable refrigerants it is important
that best practice be followed, since flammability is a consideration. The following procedure
shall be adhered to:
safely remove refrigerant following local and national regulations;
evacuate;
purge the circuit with inert gas (optional for A2L);
evacuate (optional for A2L);

Safety Cautions SiUS092519E
6 Introduction
continuously flush or purge with inert gas when using flame to open circuit;
open the circuit.
The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not
allowed by local and national codes. For appliances containing flammable refrigerants, the
system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable
refrigerants. This process might need to be repeated several times. Compressed air or
oxygen shall not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, refrigerants purging shall be achieved by
breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the
working pressure is achieved, then venting to atmosphere, and finally pulling down to a
vacuum (optional for A2L). This process shall be repeated until no refrigerant is within the
system (optional for A2L). When the final oxygen-free nitrogen charge is used, the system
shall be vented down to atmospheric pressure to enable work to take place.
The outlet for the vacuum pump shall not be close to any potential ignition sources, and
ventilation shall be available.
Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
Ensure that contamination of different refrigerants does not occur when using charging
equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant
contained in them.
Cylinders shall be kept in an appropriate position according to the instructions.
Ensure that the refrigerating system is earthed prior to charging the system with
refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigerating system.
Prior to recharging the system, it shall be pressure-tested with the appropriate purging
gas.
The system shall be leak-tested on completion of charging but prior to commissioning.
A follow up leak test shall be carried out prior to leaving the site.
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar
with the equipment and all its detail. It is recommended good practice that all refrigerants are
recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be
taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that
electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
mechanical handling equipment is available, if required, for handling refrigerant
cylinders;
all personal protective equipment is available and being used correctly;
the recovery process is supervised at all times by a competent person;
recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from
various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not overfill cylinders (no more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that
the cylinders and the equipment are removed from site promptly and all isolation valves on
the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigerating system unless it has
been cleaned and checked.

SiUS092519E Safety Cautions
Introduction 7
Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of
refrigerant. The label shall be dated and signed. For appliances containing flammable
refrigerants, ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of cylinders for holding the total
system charge is available. All cylinders to be used are designated for the recovered
refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure-relief valve and associated shut-off
valves in good working order. Empty recovery cylinders are evacuated and, if possible,
cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning
the equipment that is at hand and shall be suitable for the recovery of the flammable
refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be complete with
leak-free disconnect couplings and in good condition.
The recovered refrigerant shall be processed according to local legislation in the correct
recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants in
recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated
to an acceptable level to make certain that flammable refrigerant does not remain within the
lubricant. The compressor body shall not be heated by an open flame or other ignition
sources to accelerate this process. When oil is drained from a system, it shall be carried out
safely.
1.2 Warnings and Cautions Regarding Safety of Users
Warning
Do not store the equipment in a room with fire sources (e.g., naked
flames, gas appliances, electric heaters).
Be sure to use parts listed in the service parts list of the applicable
model and appropriate tools to conduct repair work. Never attempt
to modify the equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires are scratched or have deteriorated,
be sure to replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the
same power outlet with other electrical appliances, since it may
cause an electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and
follow the local technical standards related to the electrical
equipment, the internal wiring regulations, and the instruction
manual for installation when conducting electrical work.
Insufficient power circuit capacity and improper electrical work may cause
an electrical shock or fire.

Safety Cautions SiUS092519E
8 Introduction
Be sure to use the specified cable for wiring between the indoor and
outdoor units.
Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that
the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may
cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cables may cause an electrical shock or fire.
Placing heavy items on the power cable, or heating or pulling the power
cable may damage it.
Do not mix air or gas other than the specified refrigerant (R-32 /
R-410A / R-22) in the refrigerant system.
If air enters the refrigerant system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and
repair it before charging the refrigerant. After charging the
refrigerant, make sure that there is no leak.
If the leaking point cannot be located and the repair work must be
stopped, be sure to pump-down, and close the service valve, to prevent
refrigerant gas from leaking into the room. Refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such
as those from fan type and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation
site has sufficient strength to withstand the weight of the
equipment.
If the installation site does not have sufficient strength or the installation
work is not conducted securely, the equipment may fall and cause injury.
Check to make sure that the power cable plug is not dirty or loose,
then insert the plug into a power outlet securely.
If the plug is dusty or has a loose connection, it may cause an electrical
shock or fire.
When replacing the coin battery in the remote controller, be sure to
dispose of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases
depending on the conditions of the installation site, to prevent
electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if parts and wires are mounted and connected
properly, and if connections at the soldered or crimped terminals
are secure.
Improper installation and connections may cause excessive heat
generation, fire or an electrical shock.
Warning

SiUS092519E Safety Cautions
Introduction 9
If the installation platform or frame has corroded, replace it.
A corroded installation platform or frame may cause the unit to fall,
resulting in injury.
Check the earth / grounding, and repair it if the equipment is not
properly earthed / grounded.
Improper earth / grounding may cause an electrical shock.
Be sure to measure insulation resistance after the repair, and make
sure that the resistance is 1 M or higher.
Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage may cause water to enter the room and wet the furniture
and floor.
Do not tilt the unit when removing it.
The water inside the unit may spill and wet the furniture and floor.
Caution

Icons Used SiUS092519E
10 Introduction
2. Icons Used
The following icons are used to attract the attention of the reader to specific information.
Icon Type of
Information
Description
Warning
Warning Warning is used when there is danger of personal injury.
Caution
Caution Caution is used when there is danger that the reader,
through incorrect manipulation, may damage equipment,
lose data, get an unexpected result or have to restart (part
of) a procedure.
Note
Note Note provides information that is not indispensable, but
may nevertheless be valuable to the reader, such as tips
and tricks.
Reference
Reference Reference guides the reader to other places in this binder
or in this manual, where he/she will find additional
information on a specific topic.

SiUS092519E Revision History
Introduction 11
3. Revision History
Month/Year Version Revised contents
10 / 2025
SiUS092519E First edition

SiUS092519E Applicable Models
Part 1 General Information 13
1. Applicable Models
Indoor Unit Outdoor Unit
FDMA09AVJU9
FDMA12AVJU9
FDMA15AVJU9
FDMA18AVJU9
FDMA24AVJU9
RXP09AVJU9
RXP12AVJU9
RXP15AVJU9
RXP18AVJU9
RXP24AVJU9

Functions SiUS092519E
14 Part 1 General Information
2. Functions
Category Functions FDMA Series
Basic Function Inverter (with inverter power control)
Operation limit Refer to
page 159
PAM control
Standby electricity saving —
Compressor Swing compressor
Reluctance DC motor
Comfort Control Auto fan speed
Switchable fan speed 3 steps
Indoor unit quiet operation —
2 selectable temperature sensors
Hot-start function
QUIET OUTDOOR UNIT operation —
INTELLIGENT EYE operation
(auto energy saving)
—
Quick warming function
Automatic defrosting
Operation Automatic cooling/heating change-over
Program dry operation
Fan only
Lifestyle
Convenience
POWERFUL operation (inverter) —
ECONO operation —
Indoor unit ON/OFF switch —
Signal receiving sign —
Remote controller with back light
Health and
Cleanliness
Titanium apatite deodorizing filter —
Mold proof air filter —
Filter cleaning indicator
Silver ion anti-bacterial drain pan
Timer WEEKLY TIMER operation —
Schedule timer
Setpoint auto reset —
Setpoint range set
24-hour ON/OFF TIMER —
72-hour ON/OFF TIMER —
Off timer (turns unit off after set time) —
NIGHT SET mode —
Worry Free
(Reliability &
Durability)
Auto-restart (after power failure)
Self-diagnosis (Remote controller, LED)
Anti-corrosion treatment of outdoor heat exchanger
Flexibility Multi-split/split type compatible indoor unit
Chargeless 49.2 ft.
(15 m)
Either side drain (left or right) —
Drain pump
Low temperature cooling operation (14°F) (–10°C)
Low temperature cooling operation (–4°F) (–20°C)
Requires wind baffle and field settings
°F/°C changeover R/C temperature display
(factory setting: °F)
Remote Control Remote control adaptor
(normal open pulse contact)
—
Remote control adaptor (normal open contact) —
DIII-NET compatible (adaptor) —
Wireless LAN connection —

SiUS092519E Functions
Part 1 General Information 15
Remote
Controller
Wireless —
Wired Option
—
: Available
: Not available
Category Functions FDMA Series

SiUS092519E Specifications
Part 2 Specifications 17
1. Specifications
Model
Indoor Unit FDMA09AVJU9 FDMA12AVJU9
Outdoor Unit
RXP09AVJU9 RXP12AVJU9
Cooling Heating Cooling Heating
3RZHU6XSSO\
1 I9+] 1 I9+]
&DSDFLW\5DWHG0LQ0D[ %WXK a a a a
5XQQLQJ&XUUHQW5DWHG A 4.00 - 3.62 5.22 - 4.72 5.30 - 4.79 5.95 - 5.38
3RZHU&RQVXPSWLRQ5DWHG W 811 - 811
3RZHU)DFWRU5DWHG % 97.5 - 97.3 98.1 - 98.2 98.0 - 98.1 98.7 - 98.6
6((5 16.0 — 16.0 —
HSPF2 — 9.0 — 9.0
((55DWHG %WX:āK 11.1 — 10.0 —
&235DWHG W/W — 3.0 — 3.0
Piping
Connections
Liquid LQPP
I I
*DV LQPP
I I
'UDLQ LQPP
I.D. I2'I I.D. I2'I
+HDW,QVXODWLRQ %RWK/LTXLGDQG*DV3LSHV %RWK/LTXLGDQG*DV3LSHV
0D[,QWHUXQLW3LSLQJ/HQJWK IWP
0D[,QWHUXQLW+HLJKW'LႇHUHQFH IWP
&KDUJHOHVV IWP
$PRXQWRI$GGLWLRQDO&KDUJHRI
5HIULJHUDQW
R]IW
JP
Indoor Unit FDMA09AVJU9 FDMA12AVJU9
+HDW([FKDQJHU
5RZVî6WDJHV)LQSHU,QFK î î
)LQ6SHF7XEH
Multi Slit Fin / I+L;$7XEH Multi Slit Fin / I+L;$7XEH
$LUÀRZ5DWH H / M / L
FIP 401 / 338 / 279 401 / 338 / 279 440 / 367 / 299 440 / 367 / 299
m
3
/min 11.4 / 9.6 / 7.9 11.35 / 9.6 / 7.9 12.5 / 10.4 / 8.5 12.45 / 10.4 / 8.5
)DQ0RWRU
H / M / L rpm
Drive input A 0.52 0.61
)DQ Type 6LURFFR)DQ 6LURFFR)DQ
([WHUQDO6WDWLF3UHVVXUH
inH
2
O 6WDQGDUG 6WDQGDUG
3D 6WDQGDUG 6WDQGDUG
5XQQLQJ&XUUHQW5DWHG A 0.53 - 0.48 0.53 - 0.48 0.56 - 0.51 0.56 - 0.51
3RZHU&RQVXPSWLRQ5DWHG W 96 - 96 96 - 96 108 - 108 108 - 108
3RZHU)DFWRU5DWHG % 86.9 - 87.0 86.9 - 87.0 92.6 - 91.2 92.6 - 91.2
7HPSHUDWXUH&RQWURO Microcomputer Control Microcomputer Control
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ
*URVV:HLJKW*URVV0DVV OEVNJ
Sound Pressure Level G%$ 32 32 33 33
5HPRWH&RQWUROOHU2SWLRQ
Wired %5&159 %5&159
Wireless — —
Outdoor Unit RXP09AVJU9 RXP12AVJU9
&DVLQJ&RORU ,YRU\:KLWH ,YRU\:KLWH
+HDW([FKDQJHU )LQ6SHF7XEH
:DႉH)LQ3(I+L;6/7XEH :DႉH)LQ3(I+L;6/7XEH
)DQ0RWRU Drive input A 9.00 11.40
Compressor
Type +HUPHWLFDOO\6HDOHG6ZLQJ7\SH +HUPHWLFDOO\6HDOHG6ZLQJ7\SH
Model <%.%;$ <%.%;$
5HIULJHUDQW2LO
Type FW68DA FW68DA
&KDUJH R]/
5HIULJHUDQW
Type 5 5
&KDUJH OEVNJ
$LUÀRZ5DWH
FIP
(m
3
PLQ
)DQ Type Propeller Propeller
5XQQLQJ&XUUHQW5DWHG A 3.47 - 3.14 4.69 - 4.24 4.74 - 4.28 5.39 - 4.87
3RZHU&RQVXPSWLRQ5DWHG W 715 - 715 969 - 969 972 - 972
3RZHU)DFWRU5DWHG % 99.1 - 99.0 99.3 - 99.4 98.6 - 98.7 99.3 - 99.4
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ
*URVV:HLJKW*URVV0DVV OEVNJ
Sound Pressure Level G%$ 50 52 50 52
&RQGLWLRQV%DVHG
on
Indoor
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
Outdoor
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
3LSLQJ/HQJWK IW IW
'UDZLQJ1R 3D159367 3D159367
1RWHV
6/7KHTXLHWIDQOHYHORIWKHDLUÀRZUDWHVHWWLQJ
([WHUQDOVWDWLFSUHVVXUHLVFKDQJHDEOHLQVWDJHVE\UHPRWHFRQWUROOHU
$LU¿OWHULVQRWVWDQGDUGDFFHVVRU\EXWSOHDVHPRXQWLWLQWKHGXFWV\VWHPRIWKHVXFWLRQVLGH
6HOHFWLWVGXVWFROOHFWLRQHႈFLHQF\JUDYLW\PHWKRGRUPRUH
&RQYHUVLRQ)RUPXODH
NFDOK N:î
%WXK N:î
FIP P
3
PLQî

Specifications SiUS092519E
18 Part 2 Specifications
Model
Indoor Unit FDMA15AVJU9 FDMA18AVJU9
Outdoor Unit
RXP15AVJU9 RXP18AVJU9
Cooling Heating Cooling Heating
3RZHU6XSSO\
1 I9+] 1 I9+]
&DSDFLW\5DWHG0LQ0D[ %WXK a a a a
5XQQLQJ&XUUHQW5DWHG A 6.36 - 5.75 9.03 - 8.17 7.83 - 7.08 10.62 - 9.6
3RZHU&RQVXPSWLRQ5DWHG W
3RZHU)DFWRU5DWHG % 92.2 - 92.3 93.6 - 93.6 93.1 - 93.2 95.5 - 95.6
6((5 18.0 — 18.0 —
HSPF2 — 9.2 — 9.2
((55DWHG %WX:āK 11.8 — 11.6 —
&235DWHG W/W — 3.0 — 3.0
Piping
Connections
Liquid LQPP
I I
*DV LQPP
I I
'UDLQ LQPP
I.D. I2'I I.D. I2'I
+HDW,QVXODWLRQ %RWK/LTXLGDQG*DV3LSHV %RWK/LTXLGDQG*DV3LSHV
0D[,QWHUXQLW3LSLQJ/HQJWK IWP
0D[,QWHUXQLW+HLJKW'LႇHUHQFH IWP
&KDUJHOHVV IWP
$PRXQWRI$GGLWLRQDO&KDUJHRI
5HIULJHUDQW
R]IW
JP
Indoor Unit FDMA15AVJU9 FDMA18AVJU9
+HDW([FKDQJHU
5RZVî6WDJHV)LQSHU,QFK î î
)LQ6SHF7XEH
Multi Slit Fin / I+L;$7XEH Multi Slit Fin / I+L;$7XEH
$LUÀRZ5DWH H / M / L
FIP 471 / 382 / 284 471 / 382 / 284 609 / 498 / 373 609 / 498 / 373
m
3
/min 13.4 / 10.8 / 8.0 13.4 / 10.8 / 8.0 17.3 / 14.1 / 10.6 17.25 / 14.1 / 10.6
)DQ0RWRU
H / M / L rpm
Drive input A 0.87 1.12
)DQ Type 6LURFFR)DQ 6LURFFR)DQ
([WHUQDO6WDWLF3UHVVXUH
inH
2
O 6WDQGDUG 6WDQGDUG
3D 6WDQGDUG 6WDQGDUG
5XQQLQJ&XUUHQW5DWHG A 0.62 - 0.56 0.62 - 0.56 0.75 - 0.68 0.75 - 0.68
3RZHU&RQVXPSWLRQ5DWHG W 115 - 115 115 - 115 148 - 148 148 - 148
3RZHU)DFWRU5DWHG % 89.1 - 89.3 89.1 - 89.3 94.6 - 94.8 94.6 - 94.8
7HPSHUDWXUH&RQWURO Microcomputer Control Microcomputer Control
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ
*URVV:HLJKW*URVV0DVV OEVNJ
Sound Pressure Level G%$ 34 34 35 35
5HPRWH&RQWUROOHU2SWLRQ
Wired %5&159 %5&159
Wireless — —
Outdoor Unit RXP15AVJU9 RXP18AVJU9
&DVLQJ&RORU ,YRU\:KLWH ,YRU\:KLWH
+HDW([FKDQJHU )LQ6SHF7XEH
:DႉH)LQ3(I+L;6/7XEH :DႉH)LQ3(I+L;6/7XEH
)DQ0RWRU Drive input A 12.70 17.40
Compressor
Type +HUPHWLFDOO\6HDOHG6ZLQJ7\SH +HUPHWLFDOO\6HDOHG6ZLQJ7\SH
Model <%3$;$ <%3$;$
5HIULJHUDQW2LO
Type FW68DA FW68DA
&KDUJH R]/
5HIULJHUDQW
Type 5 5
&KDUJH OEVNJ
$LUÀRZ5DWH
FIP
(m
3
PLQ
)DQ Type Propeller Propeller
5XQQLQJ&XUUHQW5DWHG A 5.74 - 5.19 8.41 - 7.61 7.08 - 6.40 9.87 - 8.92
3RZHU&RQVXPSWLRQ5DWHG W
3RZHU)DFWRU5DWHG % 92.6 - 92.6 93.9 - 93.9 93.0 - 93.0 95.6 - 95.6
'LPHQVLRQV+î:î' LQPP îîîî îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî îîîî
:HLJKW0DVV OEVNJ
*URVV:HLJKW*URVV0DVV OEVNJ
Sound Pressure Level G%$ 55 57 55 57
&RQGLWLRQV%DVHG
on
Indoor
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
Outdoor
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
)'%&'%
):%&:%
3LSLQJ/HQJWK IW IW
'UDZLQJ1R 3D159368 3D159368
1RWHV
6/7KHTXLHWIDQOHYHORIWKHDLUÀRZUDWHVHWWLQJ
([WHUQDOVWDWLFSUHVVXUHLVFKDQJHDEOHLQVWDJHVE\UHPRWHFRQWUROOHU
$LU¿OWHULVQRWVWDQGDUGDFFHVVRU\EXWSOHDVHPRXQWLWLQWKHGXFWV\VWHPRIWKHVXFWLRQVLGH
6HOHFWLWVGXVWFROOHFWLRQHႈFLHQF\JUDYLW\PHWKRGRUPRUH
&RQYHUVLRQ)RUPXODH
NFDOK N:î
%WXK N:î
FIP P
3
PLQî

SiUS092519E Specifications
Part 2 Specifications 19
Model
Indoor Unit FDMA24AVJU9
Outdoor Unit
RXP24AVJU9
Cooling Heating
3RZHU6XSSO\
1 I9+]
&DSDFLW\5DWHG0LQ0D[ %WXK a a
5XQQLQJ&XUUHQW5DWHG A 10.32 - 9.33 11.39 - 10.30
3RZHU&RQVXPSWLRQ5DWHG W
3RZHU)DFWRU5DWHG % 98.6 - 98.7 99.0 - 99.0
6((5 18.3 —
HSPF2 — 9.2
((55DWHG %WX:āK 10.3 —
&235DWHG W/W — 3.0
Piping
Connections
Liquid LQPP
I
*DV LQPP
I
'UDLQ LQPP
I.D. I2'I
+HDW,QVXODWLRQ %RWK/LTXLGDQG*DV3LSHV
0D[,QWHUXQLW3LSLQJ/HQJWK IWP
0D[,QWHUXQLW+HLJKW'LႇHUHQFH IWP
&KDUJHOHVV IWP
$PRXQWRI$GGLWLRQDO&KDUJHRI
5HIULJHUDQW
R]IW
JP
Indoor Unit FDMA24AVJU9
+HDW([FKDQJHU
5RZVî6WDJHV)LQSHU,QFK î
)LQ6SHF7XEH
Multi Slit Fin / I+L;$7XEH
$LUÀRZ5DWH H / M / L
FIP 666 / 553 / 426 666 / 553 / 426
m
3
/min 18.9 / 15.7 / 12.1 18.85 / 15.7 / 12.1
)DQ0RWRU
H / M / L rpm
Drive input A 1.24
)DQ Type 6LURFFR)DQ
([WHUQDO6WDWLF3UHVVXUH
inH
2
O 6WDQGDUG
3D 6WDQGDUG
5XQQLQJ&XUUHQW5DWHG A 0.81 - 0.73 0.81 - 0.73
3RZHU&RQVXPSWLRQ5DWHG W 164 - 164 164 - 164
3RZHU)DFWRU5DWHG % 97.5 - 97.2 97.5 - 97.2
7HPSHUDWXUH&RQWURO Microcomputer Control
'LPHQVLRQV+î:î' LQPP îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî
:HLJKW0DVV OEVNJ
*URVV:HLJKW*URVV0DVV OEVNJ
Sound Pressure Level G%$ 40 40
5HPRWH&RQWUROOHU2SWLRQ
Wired %5&159
Wireless —
Outdoor Unit RXP24AVJU9
&DVLQJ&RORU ,YRU\:KLWH
+HDW([FKDQJHU )LQ6SHF7XEH
:DႉH)LQ3(I+L;6/7XEH
)DQ0RWRU Drive input A 17.60
Compressor
Type +HUPHWLFDOO\6HDOHG6ZLQJ7\SH
Model <%3$;$
5HIULJHUDQW2LO
Type FW68DA
&KDUJH R]/
5HIULJHUDQW
Type 5
&KDUJH OEVNJ
$LUÀRZ5DWH
FIP
(m
3
PLQ
)DQ Type Propeller
5XQQLQJ&XUUHQW5DWHG A 9.51 - 8.60 10.58 - 9.57
3RZHU&RQVXPSWLRQ5DWHG W
3RZHU)DFWRU5DWHG % 98.7 - 98.7 99.1 - 99.1
'LPHQVLRQV+î:î' LQPP îîîî
3DFNDJHG'LPHQVLRQV+î:î' LQPP îîîî
:HLJKW0DVV OEVNJ
*URVV:HLJKW*URVV0DVV OEVNJ
Sound Pressure Level G%$ 55 57
&RQGLWLRQV%DVHG
on
Indoor
)'%&'%
):%&:%
)'%&'%
):%&:%
Outdoor
)'%&'%
):%&:%
)'%&'%
):%&:%
3LSLQJ/HQJWK IW
'UDZLQJ1R 3D159368
1RWHV
6/7KHTXLHWIDQOHYHORIWKHDLUÀRZUDWHVHWWLQJ
([WHUQDOVWDWLFSUHVVXUHLVFKDQJHDEOHLQVWDJHVE\UHPRWHFRQWUROOHU
$LU¿OWHULVQRWVWDQGDUGDFFHVVRU\EXWSOHDVHPRXQWLWLQWKHGXFWV\VWHPRIWKHVXFWLRQVLGH
6HOHFWLWVGXVWFROOHFWLRQHႈFLHQF\JUDYLW\PHWKRGRUPRUH
&RQYHUVLRQ)RUPXODH
NFDOK N:î
%WXK N:î
FIP P
3
PLQî

SiUS092519E
20 Part 3 Printed Circuit Board Connector Wiring Diagram
1. Indoor Unit.............................................................................................21
2. Outdoor Unit..........................................................................................23
2.1 RXP09/12AVJU9....................................................................................23
2.2 RXP15/18/24AVJU9...............................................................................24
Part 3
Printed Circuit Board
Connector Wiring Diagram

SiUS092519E Indoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 21
1. Indoor Unit
Control PCB
(A1P)
1) X15A Connector for float switch
2) X16A Connector for room temperature thermistor (suction air thermistor) (R1T)
3) X17A, X18A Connector for indoor heat exchanger thermistor (R2T, R3T)
4) X25A Connector for drain pump motor
5) X27A Connector for terminal block (for power supply)
6) X28A Connector for power supply wiring (option)
7) X30A Connector for terminal block (for wired remote controller)
8) X33A Connector for wiring (option)
9) X35A Connector for wiring adaptor (option)
10) X41A Connector for refrigerant sensor PCB (A3P)
11) X70A Connector for indoor fan PCB (A2P)
12) F1U Fuse (3.15 A, 250 V)
13) HAP LED for service monitor (green)
14) DS1 DIP switch for emergency
X15A
X41A X25A X70AX33AHAP X27A
F1U
X35A X28A
X17A
X16A
X18A
X30A
DS1
2P801582-1

Indoor Unit SiUS092519E
22 Part 3 Printed Circuit Board Connector Wiring Diagram
Indoor Fan PCB
(A2P)
Refrigerant
Sensor PCB
(A3P)
1) X3A Connector for control PCB (A1P)
2) X6A Connector for reactor
3) X8A Connector for DC fan motor
4) X10A Connector for terminal block (for power supply)
5) F2U Fuse (5 A, 250 V)
6) F4U Fuse (6.3 A, 250 V)
7) HAP LED for service monitor (green)
X10A
HAP
F4U X6A
F2U
X3A X8A
2P571965-12
2P571965-13
1) CN1 Connector for control PCB (A1P)
CN1
3S486006-3

SiUS092519E Outdoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram 23
Note
2. Outdoor Unit
2.1 RXP09/12AVJU9
Main PCB (A1P)
The symbols in the parenthesis are the names written on the PCB.
1) LA, N, S Faston tab for terminal strip
2) X10A Connector for ground
3) X21A Connector for electronic expansion valve coil
4) X30A Connector for compressor
5) X40A Connector for overload protector and high pressure switch
6) X70A Connector for DC fan motor
7) X80A Connector for four way valve coil
8) X90A Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
9) F1U Fuse (30 A, 250 V)
10) F31U, F401U Fuse (3.15 A, 250 V)
11) J5 Jumper for warmer airflow setting
Refer to page 150 for details.
12) J7 Jumper for facility setting
Refer to page 149 for details.
13) J9 Jumper for drain pan heater
Refer to page 151 for details.
14) LED LED for service monitor (green)
15) R1V (V1),
R2V (V2),
R3V (V551)
Varistor
X40A
X90A
X30A
LED
X70A
N R1VS
X10A
2P817562-21
R3V
R2V
X80A
X21A LA
F31U
F1U
F401U
J7
J5
J9

Outdoor Unit SiUS092519E
24 Part 3 Printed Circuit Board Connector Wiring Diagram
Note
2.2 RXP15/18/24AVJU9
Main PCB (A1P)
The symbols in the parenthesis are the names written on the PCB.
1) X190A Connector for ground wire
2) X200A Connector for DC fan motor
3) X700A Connector for electric expansion valve coil
4) X800A Connector for four way valve coil
5) X820A Connector for overload protector and high pressure switch
6) X900A Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
7) S, HL1, HN1 Faston tab for terminal strip
8) U, V, W Faston tab for compressor
9) DP1, DP2 Faston tab for drain pan heater
10) F1U (FU1),
F2U (FU2)
Fuse (3.15 A, 250 V)
11) F3U (FU3) Fuse (30 A, 250 V)
12) J5 Jumper for warmer airflow setting
Refer to page 150 for details.
13) J7 Jumper for facility setting
Refer to page 149 for details.
14) J9 Jumper for drain pan heater
Refer to page 151 for details.
15) LED LED for service monitor (green)
2P757473-8
F3U
X800A
F1U
X200A
F2U
U
V
W
X820A
X900A HN1 HL1
J7
J5
J9
DP2
DP1
S
X190A
X700A
LED

SiUS092519E
Part 4 Functions and Control 25
1. Common Functions ...............................................................................26
1.1 Temperature Control ..............................................................................26
1.2 Frequency Principle................................................................................26
1.3 Fan Speed Control for Indoor Unit .........................................................28
1.4 Program Dry Operation ..........................................................................28
1.5 Automatic Cooling/Heating Change-over ...............................................29
1.6 Clock and Calendar Setting (With BRC1NRV71)...................................30
1.7 Schedule Timer Operation (With BRC1NRV71).....................................32
1.8 Drain Pump Control................................................................................36
1.9 Hot Start Control (In Heating Operation Only)........................................38
1.10 Other Functions......................................................................................39
2. Thermistor Functions ............................................................................40
3. Control Specification .............................................................................41
3.1 Mode Hierarchy ......................................................................................41
3.2 Frequency Control..................................................................................41
3.3 Controls at Mode Changing/Start-up......................................................43
3.4 Discharge Pipe Temperature Control.....................................................45
3.5 Input Current Control..............................................................................46
3.6 High Pressure Protection Control...........................................................47
3.7 Freeze-up Protection Control .................................................................47
3.8 Heating Peak-cut Control .......................................................................48
3.9 Outdoor Fan Control...............................................................................49
3.10 Liquid Compression Protection Function................................................49
3.11 Defrost Control .......................................................................................50
3.12 Electronic Expansion Valve Control .......................................................53
3.13 Malfunctions ...........................................................................................56
Part 4
Functions and Control

Common Functions SiUS092519E
26 Part 4 Functions and Control
1. Common Functions
1.1 Temperature Control
Definitions of
Temperatures
The definitions of temperatures are classified as following.
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
R4004275
Temperature
Control
The temperature of the room is detected by the room temperature thermistor. However, there is
a difference between the temperature detected by room temperature thermistor and the
temperature of lower part of the room, depending on the type of the indoor unit or installation
condition. In practice, the temperature control is done by the target temperature appropriately
adjusted for the indoor unit and the temperature detected by room temperature thermistor.
1.2 Frequency Principle
Control
Parameters
The frequency of the compressor is controlled by the following 2 parameters:
The load condition of the operating indoor unit
The difference between the room thermistor temperature and the target temperature
The target frequency is adapted by additional parameters in the following cases:
Frequency restrictions
Initial settings
Forced cooling operation
Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to
control the rotation speed of the compressor. The followings explain the inverter principle:
Phase 1
The supplied AC power source is converted into the DC power source for the present.
Phase 2
The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting in
an increase of refrigerant circulation. This leads to a larger amount of heat exchange per
unit.
When the frequency decreases, the rotation speed of the compressor decreases resulting in
a decrease of refrigerant circulation. This leads to a smaller amount of heat exchange per
unit.
Set temperature
Room temperature
Target temperature
Room thermistor temperature

SiUS092519E Common Functions
Part 4 Functions and Control 27
The following drawing shows a schematic view of the inverter principle:
Inverter Features The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor
temperature and cooling/heating load.
Quick heating and quick cooling
The rotation speed of the compressor is increased when starting the heating (cooling).
This enables to reach the set temperature quickly.
Even during extreme cold weather, high capacity is achieved. It is maintained even when the
outdoor temperature is 2C (35.6°F).
Comfortable air conditioning
A fine adjustment is integrated to keep the room temperature constant.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency Limits The following functions regulate maximum frequency:
Low frequency
Four way valve operation compensation. Refer to page 43.
High frequency
Compressor protection function. Refer to page 44.
Discharge pipe temperature control. Refer to page 45.
Input current control. Refer to page 46.
Freeze-up protection control. Refer to page 47.
Heating peak-cut control. Refer to page 48.
Defrost control. Refer to page 50.
Forced Cooling
Operation
Refer to page 140 for details.
Refrigerant circulation rate (high)
high f
low f
freq=variable
Refrigerant circulation rate (low)
high speed
low speed
(R2812)
Amount of heat
exchanged air (large)
freq=
constant
50 Hz
50 Hz
60 Hz
60 Hz
capacity=
variable
Amount of heat
exchanged air (small)
AC
power
DC
power
Amount of heat exchanged air
(large)
Amount of heat exchanged air
(small)

Common Functions SiUS092519E
28 Part 4 Functions and Control
1.3 Fan Speed Control for Indoor Unit
With Wired Remote Controller (BRC1NRV71)
To change the fan speed, press Fan Speed button and select the fan speed from
Low/Medium/High/Auto.
Auto cannot be selected if the indoor unit does not have Auto Fan speed function.
The system may change the fan speed automatically for equipment protection purposes.
The system may turn off the fan when the room temperature is satisfied.
It is normal for delays to occur when changing the fan speed.
If the Auto is selected for the fan speed, the fan speed varies automatically based on the
difference between set temperature and room temperature.
R4003380
1.4 Program Dry Operation
Outline Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and FAN setting buttons are inoperable.
Details The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
R4004276
Cool
Return Setting
Set to
74F
Low Medium
High
Auto
A
three fan speeds
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
16.5°C or more
(61.7°F or more)
Room thermistor
temperature at start-up
X – 1.0°C
(X – 1.8°F)
X – 0.5°C
(X – 0.9°F)
16°C or less
(60.8°F or less)
16°C
(60.8°F)
X – 2.0°C
(X – 3.6°F)
X – 1.0°C = 15°C
(X – 1.8°F = 59°F)
Zone A = Thermostat OFF
Target temperature X
Zone B
Room temperature Room temperature
Zone C = Thermostat ON
Y = X – 1.0°C (1.8°F)
Z = X – 0.5°C (0.9°F)
X – 0.5°C (0.9°F)

SiUS092519E Common Functions
Part 4 Functions and Control 29
1.5 Automatic Cooling/Heating Change-over
Outline When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Details Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 17 ~ 32°C (63 ~ 90°F))
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value.
C = 0°C (0°F)
3. Thermostat ON/OFF point and operation mode switching point are as follows.
(1) Heating Cooling switching point:
Tr Tt + 2.5°C (+ 4.5°F)
(2) Cooling Heating switching point:
Tr < Tt – 2.5°C (– 4.5°F)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating
operation.
4. During initial operation
Tr Ts : Cooling operation
Tr < Ts : Heating operation
R4004277
Ex: When the target temperature is 25°C (77°F)
Cooling → 24°C (75.2°F): Thermostat OFF → 22.5°C (72.5°F): Switch to heating
Heating → 26°C (78.8°F): Thermostat OFF → 27.5°C (81.5°F): Switch to cooling
Target temperature + 2.5°C (+4.5°F)
Heating Operation
Target temperature – 2.5°C (–4.5°F)
Cooling Operation
Target temperature – 1.0°C (–1.8°F)
= Thermostat OFF
Target temperature + 1.0°C (+1.8°F)
= Thermostat OFF

Common Functions SiUS092519E
30 Part 4 Functions and Control
1.6 Clock and Calendar Setting (With BRC1NRV71)
R4004248
2
3
4
5
1
Press buttons to select Date & Time
on the clock & calendar screen.
Press Menu/OK button to display the
date & time screen.
Select Y
ear with buttons.
Change the year with buttons.
Holding down the button causes the
number to change continuously.
Press buttons to select
Clock & Calendar on the main menu
screen.
Press Menu/OK button to display the
clock & calendar screen.
Select Month
with buttons.
Change the month with buttons.
Holding down the button causes the
number to change continuously.
Select Day with buttons.
Change the day with buttons.
Holding down the button causes the
number to change continuously.
Days of the week change automatically.
Press Menu/OK button to
display the main menu screen.

SiUS092519E Common Functions
Part 4 Functions and Control 31
R4004249
7
Note:
8
6
Select Hour with buttons.
Change the hour with buttons.
Holding down the button causes the
number to change continuously.
Select Minute with buttons.
Change the minute with buttons.
Holding down the button causes the
number to change continuously.
Press Menu/OK button.
The confirmation screen will appear.
The date can be set between
January 1, 2020 and December 31, 2099.
Press button to select Yes on the
confirmation screen.
Press Menu/OK button to confirm the
clock and return to the basic screen.
* When setting the schedule, the display returns to
the settings screen.

Common Functions SiUS092519E
32 Part 4 Functions and Control
1.7 Schedule Timer Operation (With BRC1NRV71)
Outline Day settings are selected from 4 patterns:
7 Days
Weekday/Sat/Sun
Weekday/Weekend
Everyday
Up to 5 actions can be set for each day.
Details Set the startup time and operation stop time.
Setting the schedule
R4004250
ON: Startup time, cooling and heating temperature setpoints can be configured.
OFF: Operation stop time, cooling and heating setback temperature setpoints can be
configured.
( --: Indicates that the setback function is disabled for this time period. )
__: Indicates that the temperature setpoint and setback temperature setpoint for this time
period is not specified. The last active setpoint will be utilized.
1
Press buttons to select Schedule .
Press Menu/OK button to display the
schedule screen.
The date & time screen will appear.
2
Before setting the schedule, the clock
must be set.
If the clock has not been set, a screen
like the one on the left will appear.
Press buttons to select Yes and
press Menu/OK button.
Set the current year, month, day, and
time.
Press buttons to select the desired
function on the schedule screen and
press Menu/OK button.
Press Menu/OK button to
display the main menu screen.

SiUS092519E Common Functions
Part 4 Functions and Control 33
Daily Patterns
1
The schedule screen will appear.
2
Press buttons to
select Daily Patterns on the schedule
screen.
The daily patterns screen will appear
when Menu/OK b
utton is pressed.
Press buttons to
select 7 Days , Weekday/Sat/Sun ,
Weekday/Weekend or Everyday on
the daily patterns screen.
The confir
mation screen will appear
when Menu/OK button is pressed.
3
Press buttons to select Yes on the
confirmation screen.
Pressing Menu/OK button enters the
daily patterns in the schedule and takes
you back to the main menu screen.
(R24074)

Common Functions SiUS092519E
34 Part 4 Functions and Control
Settings
R4003456
1
The schedule screen will appear.
Press buttons to select Settings
on the schedule screen.
The settings screen will appear when
Menu/OK button is pressed.
2
Press buttons to select the day to
be set.
* It cannot be selected in the case of EVDY .
3
Input the time for the selected day.
Press buttons to move the
highlighted item and press buttons
to input the desired operation start time.
Each press of buttons moves the
numbers by 1 hour or 1 minute.

SiUS092519E Common Functions
Part 4 Functions and Control 35
4
Press buttons to move the
highlighted item and press buttons
to configure ON/OFF/-- settings.
--, ON, or OFF changes in sequence
when buttons are pressed.
ON: The temperature setpoints can be configured.
OFF: The setback temperature setpoints can be
configured.
– –: The temperature setpoints and setback
temperature setpoints become disabled.
The cooling and heating temperature
setpoints for both ON and OFF
(Setback) are configured.
__: Indicates that the temperature setpoint and
setback temperature setpoint for this time
period is not specified. The last active setpoint
will be utilized.
– –: Indicates that the setback function is disabled
for this time period.
5
A maximum of five actions per day can be
set.
Press Menu/OK button when settings
for each day are completed. The
confirmation screen will appear.
To copy the settings for the previous day, press
Mode button so that the existing settings will be
copied.
Example: The contents for Monday are copied by
pressing Mode button after selecting Tuesday.
6
Press buttons to select Yes on the
confirmation screen.
Pressing Menu/OK button confirms the
settings for each day and takes you
back to the basic screen.
(R24075)

Common Functions SiUS092519E
36 Part 4 Functions and Control
Enabling or disabling the schedule
R4003458
1.8 Drain Pump Control
Normal Operation
The float switch is ON in normal operation.
When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
After the thermostat turns OFF, the drain pump continues to operate.
1
2
3
Display the schedule screen.
Press buttons to select
Enable / Disable on the schedule
screen.
Press
Menu/OK button to display the
enab
le/disable screen.
Press buttons to select Enable
or Disable on the enable/disable
screen.
Press Menu/OK button after selecting
the item.
The confirmation screen is
displayed.
Press buttons to select Yes on the
confirmation screen.
Pressing
Menu/OK button confirms the
enable/disable setting for the schedule
and takes you back to the basic screen.
Float switch
Error display
Thermostat
(running)
OFF
OFF
ON
ON
ON
OFF
Drain pump
ON
OFF
(R24037)

SiUS092519E Common Functions
Part 4 Functions and Control 37
If Float Switch is OFF with Thermostat ON in Cooling Operation
When the float switch stays OFF for 5 sec., the thermostat turns OFF.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
If Float Switch is OFF with Thermostat OFF in Cooling Operation
When the float switch stays OFF for 5 sec., the drain pump turns ON.
If the float switch remains OFF even after the residual operation of the drain pump has
ended, the error code A3 is determined.
The drain pump turns OFF once residual operation has ended, then turns ON again after 5
seconds.
1. If the float switch turns ON again during the residual operation of the drain pump, cooling
operation also turns on again (thermostat ON).
2. If the float switch remains OFF even after the residual operation of the drain pump has
ended, the error code A3 is determined.
3. The drain pump turns OFF once residual operation has ended, then turns ON again after
5 seconds.
4. After A3 is determined and the unit comes to an abnormal stop, the thermostat will
remain OFF even if the float switch turns ON again.
OFF
OFF
ON
ON
ON
OFF
ON
OFF
5 min.5 min.
5 sec. 5 sec.
5 min.
5 sec.
(R24610)
Float switch
Error display
Thermostat
(running)
Drain pump
A3
∗1
∗2
∗4
∗3
5 sec.
5 sec.
OFF
OFF
ON
ON
ON
OFF
ON
OFF
5 min.
5 sec.5 sec.
5 min. 5 min.
5 sec.
Float switch
Error display
Thermostat
(running)
Drain pump
(R24611)
A3

Common Functions SiUS092519E
38 Part 4 Functions and Control
If Float Switch Turns ON and OFF Continuously, or Float Switch Turns OFF While AF Displayed
When the float switch stays OFF for 5 sec., the drain pump turns ON.
1.9 Hot Start Control (In Heating Operation Only)
Outline At startup with thermostat ON or after the completion of defrosting in heating operation, the
indoor unit fan is controlled to prevent cold air from blasting out and ensure startup capacity.
Details
R4004278
TH
3
: Temperature detected by the indoor heat exchanger thermistor (R3T)
(R24370)
OFF
Float Switch
ON
ON
Thermostat
(running)
OFF
ON
A3AF
Error Display
OFF
ON
Drain Pump
OFF
1st
5 sec. 5 sec. 5 sec. 5 sec.
4th 5th
5 sec.
5 min. 5 min.
5 sec.
5 min. 5 min.
5 sec.
5 min. 5 min.
5 sec.
5 min. 5 min.
5 sec. 5 sec.
5 min. 5 min.
∗1 ∗2 ∗3
5 sec.
1. If the float switch continues to turn OFF and ON 5 times consecutively, it is judged as a
drain system error and the error code AF is determined.
2. The drain pump continues to turn ON/OFF in accordance with the float switch ON/OFF
even after AF is determined.
3. While the error code AF is displayed, if the float switch remains OFF even after the
residual operation of the drain pump has ended, the error code A3 will be determined.
Defrost ending or oil return ending
or Thermostat ON
The fan is not OFF before initiating the hot start: LL
The fan is OFF before initiating the hot start: OFF
Hot start control
Hot start in progress
Normal operation
Normal operation
H/M/L remote
controller setting
LL
OFF
Remote controller
setting
Level position
FanLouver
Hot start ending conditions
·
Lapse of 3 minutes
·
TH
3
> 34°C (93.2°F)
OR

SiUS092519E Common Functions
Part 4 Functions and Control 39
Note
1.10 Other Functions
1.10.1 Refrigerant Detection System (RDS) Function
Refrigerant Detection System (RDS) is installed in this equipment to detect any refrigerant
leakage in the coil and leak detection sensor failure and conduct safety actions in the following
table to mitigate any risk of ignition/fire.
In case that a leak is detected, the safety actions start when a leak is detected by leak detection
sensor and continue until 5 minutes elapsed after a leak stops being detected.
In case of leak detection sensor failure, the same safety actions are performed.
1.10.2 Auto-restart Function
If a power failure (even a momentary one) occurs during the operation, the system restarts
automatically in the same conditions as before when the power supply is restored to the
conditions prior to the power failure.
It takes 3 minutes to restart the operation because 3-minute standby function is activated.
Item (function) Leak actions
Remote controller Display of error code A0-17, A0-19 or CH-11, CH-14
Fan motor Run at LL or greater tap
Compressor OFF
Leak actions OFF
(Normal operation)
Leak actions ON
OR
• Leak detected (A0-17 or A0-19)
• Leak detection sensor failure (CH-11)
or disconnection (CH-14)
If A0-19
・
5 minutes elapsed after leak stopped being detected
If CH-14
・
Leak detection sensor reconnected
If A0-17 or CH-11
・
Leak detection sensor failure cleared

Thermistor Functions SiUS092519E
40 Part 4 Functions and Control
2. Thermistor Functions
(1) Discharge
Pipe Thermistor
The discharge pipe thermistor is used for controlling discharge pipe temperature. If the
discharge pipe temperature (used in place of the inner temperature of the compressor) rises
abnormally, the operating frequency becomes lower or the operation halts.
The discharge pipe thermistor is used for detecting disconnection of the discharge pipe
thermistor.
(2) Outdoor Heat
Exchanger
Thermistor
The outdoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the
outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the outdoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the outdoor heat exchanger temperature by more than a certain value, the discharge
pipe thermistor is judged as disconnected.
In cooling operation, the outdoor heat exchanger thermistor is used for high pressure
protection.
(3) Outdoor
Temperature
Thermistor
The outdoor temperature thermistor detects the outdoor air temperature and is used for
refrigerant shortage detection, input current control, outdoor fan control, liquid compression
protection function, and so on.
(4) Indoor Heat
Exchanger
Thermistor
The indoor heat exchanger thermistor is used for controlling the target discharge pipe
temperature. The system sets the target discharge pipe temperature according to the
outdoor and indoor heat exchanger temperature, and controls the electronic expansion valve
opening so that the target discharge pipe temperature can be obtained.
In cooling operation, the indoor heat exchanger thermistor is used for freeze-up protection
control. If the indoor heat exchanger temperature drops abnormally, the operating frequency
becomes lower or the operation halts.
In heating operation, the indoor heat exchanger thermistor is used for detecting the
disconnection of the discharge pipe thermistor. When the discharge pipe temperature drops
below the indoor heat exchanger temperature by more than a certain value, the discharge
pipe thermistor is judged as disconnected.
(5) Room
Temperature
Thermistor
The room temperature thermistor detects the room air temperature and is used for
controlling the room air temperature.
Four way valve
Compressor
(R23851)
Expansion valve
(2) Outdoor Heat
Exchanger
Thermistor
(3) Outdoor
Temperature
Thermistor
(5) Room
Temperature
Thermistor
(1) Discharge Pipe
Thermistor
(4) Indoor Heat
Exchanger
Thermistor

SiUS092519E Control Specification
Part 4 Functions and Control 41
3. Control Specification
3.1 Mode Hierarchy
Outline The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Details
Unless specified otherwise, dry operation command is regarded as cooling operation.
3.2 Frequency Control
Outline The compressor frequency is determined according to the difference between the room
thermistor temperature and the target temperature.
Details 1. Determine command frequency
Command frequency is determined in the following order of priority.
(1) Limiting defrost control time
(2) Forced cooling
(3) Indoor frequency command
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Heating
Heating
Defrosting
Stop (indoor unit: OFF)
Preheating control
Discharging from capacitor
Stop
(R22375)
Command frequency
Limit frequency
Skip control
Upper limit function
Compressor protection function
Lower limit function
Four way valve operation compensation, etc.
Target frequency
(R18023)
When the shift of the frequency is less than zero (ΔF<0) by PI control,
the target frequency is used as the command frequency.
Dropping function
Input current control, etc.
Upper limit frequency
FMAX
Lower limit frequency
FMIN
Initial frequency
PI control
Defrost control

Control Specification SiUS092519E
42 Part 4 Functions and Control
2. Determine upper limit frequency
The minimum value is set as an upper limit frequency among the frequency upper limits of
the following functions:
Compressor protection, input current, discharge pipe temperature, heating peak-cut,
freeze-up protection, defrost control.
3. Determine lower limit frequency
The maximum value is set as an lower limit frequency among the frequency lower limits of
the following functions:
Four way valve operation compensation, draft prevention, pressure difference upkeep.
4. Determine prohibited frequency
There is a certain prohibited frequency such as a power supply frequency.
Initial Frequency When starting the compressor, the frequency is initialized according to the D value of the
indoor unit.
D signal: Indoor frequency command
The difference between the room thermistor temperature and the target temperature is taken as
the D value and is used for D signal of frequency command.
OFF = Thermostat OFF
PI Control 1. P control
The D value is calculated in each sampling time (20 seconds), and the frequency is
adjusted according to its difference from the frequency previously calculated.
2. I control
If the operating frequency does not change for more than a certain fixed time, the frequency
is adjusted according to the D value.
When D value is low, the frequency is lowered.
When D value is high, the frequency is increased.
3. Frequency control when other controls are functioning
When frequency is dropping:
Frequency control is carried out only when the frequency drops.
For limiting lower limit:
Frequency control is carried out only when the frequency rises.
4. Upper and lower limit of frequency by PI control
The frequency upper and lower limits are set according to the command of the indoor unit.
When the indoor unit quiet or QUIET OUTDOOR UNIT operation command comes from the
indoor unit, the upper limit frequency is lower than the usual setting.
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
Temperature
difference
D
signal
–1.0°C (–1.8°F) OFF 0°C (0°F) 4 2.0°C (3.6°F) 8 4.0°C (7.2°F) 12
–0.8°C (–1.4°F) 1 0.5°C (0.9°F) 5 2.5°C (4.5°F) 9 4.5°C (8.1°F) 13
–0.5°C (–0.9°F) 2 1.0°C (1.8°F) 6 3.0°C (5.4°F) 10 5.0°C (9.0°F) 14
–0.3°C (–0.5°F) 3 1.5°C (2.7°F) 7 3.5°C (6.3°F) 11 5.5°C (9.9°F) 15

SiUS092519E Control Specification
Part 4 Functions and Control 43
3.3 Controls at Mode Changing/Start-up
3.3.1 Preheating Control
Outline The inverter operation in open phase starts with the conditions of the outdoor temperature, the
discharge pipe temperature, the radiation fin temperature and the preheating command from
the indoor unit.
Details ON condition
Discharge pipe temperature < A
Outdoor temperature < B
Radiation fin temperature < 85°C (185°F)
OFF condition
Discharge pipe temperature > C
Outdoor temperature > D
Radiation fin temperature ≥ 90°C (194°F)
3.3.2 Four Way Valve Switching
Outline The four way valve coil is energized/not energized depending on the operation mode.
(Heating: ON, Cooling/Dry/Defrost: OFF)
In order to eliminate the switching sound as the four way valve coil switches from ON to OFF
when the heating is stopped, the OFF delay switch of the four way valve is carried out.
Details OFF delay switch of four way valve
The four way valve coil is energized for 160* seconds after the operation is stopped.
*10 seconds in heating operation when the outdoor temperature is lower than –9 °C (15.8°F)
3.3.3 Four Way Valve Operation Compensation
Outline At the beginning of operation as the four way valve is switched, the pressure difference to
activate the four way valve is acquired when the output frequency is higher than a certain fixed
frequency, for a certain fixed time.
Details Starting Conditions
1. When the compressor starts and the four way valve switches from OFF to ON
2. When the four way valve switches from ON to OFF during operation
3. When the compressor starts after resetting
4. When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps A Hz for B seconds for any of the conditions above.
When the outdoor temperature is above C in heating, the frequency decreases depending on
the outdoor temperature.
A B C D
(°C) (°F) (°C) (°F) (°C) (°F) (°C) (°F)
09/12 class 10 50 0 32 12 53.6 2 35.6
15/18/24 class 6.5 43.7 5 41 9 48.2 7 44.6
09/12 class 15/18/24 class
Cooling Heating Cooling Heating
A (Hz) 28 34 28 30
B (seconds) 60 70
C (°C) 10 20
(°F) 50 68

Control Specification SiUS092519E
44 Part 4 Functions and Control
3.3.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
The function is not used when defrosting.
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
The function is not used when defrosting.
09/12 class 15/18/24 class
A (rps) 36 30
B (rps) 48 48
C (rps) 68 62
D (rps) 80 80
E (rps) 110 —
F (seconds) 94 450
G (seconds) 420 450
H (seconds) 180 300
J (seconds) 180 470
K (seconds) 180 —
(sec.)
Time
(R23251)
(Hz)
Frequency
C
D
E
B
FGHJK
A

SiUS092519E Control Specification
Part 4 Functions and Control 45
3.4 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep the discharge pipe temperature from rising further.
Details
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
09/12 class 15/18/24 class
(°C) (°F) (°C) (°F)
A 118 244.4 118 244.4
B 105 221.0 108 226.4
C 98 208.4 103 217.4
D 91 195.8 97 206.6
E 79 174.2 85 185.0
(R25005)
Discharge pipe
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
E
A
B
C
D

Control Specification SiUS092519E
46 Part 4 Functions and Control
3.5 Input Current Control
Outline The microcomputer calculates the input current while the compressor is running, and sets the
frequency upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of the frequency and takes
priority over the lower limit control of four way valve operation compensation.
Details
Frequency control in each zone
Stop zone
After the input current remains in the stop zone for 2.5 seconds, the compressor is stopped.
Dropping zone
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep
zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level
(depending on the model).
09/12 class 15/18 class 24 class
Cooling Heating Cooling Heating Cooling Heating
A (A) 13 14 20 20
B (A) 8.25 13.25 16.25 19 16.25 19.25
C (A) 7.5 12.5 15.25 18 15.25 18.25
Compressor Stop
Input current
Dropping zone
Stop zone
Keep zone
Reset zone
(R23249)
A
(A)
B
C

SiUS092519E Control Specification
Part 4 Functions and Control 47
3.6 High Pressure Protection Control
Outline In order to prevent abnormal high pressures in the system and hence avoiding activation of the
high pressure safety device the below control function will be activated.
Details
3.7 Freeze-up Protection Control
Details When the freeze-up protection control starts, the compressor stops, the airflow rate is fixed to L
tap, and the drain pump turns ON. Conditions for starting and ending are as below.
Starting conditions
The freeze-up protection control starts when any of the following conditions is satisfied.
The indoor heat exchanger temperature remains at A or lower for 1 minute.
The accumulated time that the indoor heat exchanger temperature remains at B or lower
reaches 40 minutes.
Accumulated timer clearing condition
The indoor heat exchanger temperature remains at C or higher for 20 minutes.
Ending condition
The indoor heat exchanger temperature remains at D or higher for 10 minutes.
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
Pressure
4.15 MPa (602 psi)
High Pressure
Protection
Control
Heating
Peak- cut
control
Condensing
temperature
HPS ≥ 4.15 MPa (602 psi)
Compressor on
Compressor stop
(E3 indication)
Stopped 4 times
in 60 minutes
Abnormal stop
(E3 indication)
Normal operation
(°C) (°F)
A –5 23.0
B –1 30.2
C 4 39.2
D 7 44.6

Control Specification SiUS092519E
48 Part 4 Functions and Control
R4003915
3.8 Heating Peak-cut Control
During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
: The valves might drop when the outdoor temperature is low to protect the compressor.
D
A
B
C
Indoor heat
exchanger
temperature
The control starts.
The control starts.
The control ends
and the accumulated timer is cleared.
The accumulated timer is cleared.
Zone
Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Up zone The upper limit of frequency increases.
Reset zone The upper limit of frequency is canceled.
09/12 class 15/18/24 class
(°C) (°F) (°C) (°F)
A 59 138.2 59 138.2
B 54 129.2 55 131.0
C 51 123.8 52 125.6
D 48 118.4 50 122.0
E 44 111.2 45 113.0
Indoor heat exchanger
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R23928)
D
C
B
A
E

SiUS092519E Control Specification
Part 4 Functions and Control 49
3.9 Outdoor Fan Control
1. Fan ON control to cool down the electrical box
The outdoor fan is turned ON when the electrical box temperature is high while the
compressor is OFF.
2. Fan OFF control during defrosting
The outdoor fan is turned OFF while defrosting.
3. Fan OFF delay when stopped
The outdoor fan is turned OFF 60 ~ 70 seconds after the compressor stops.
4. Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled
as well as normal operation.
5. Fan speed control during forced operation
The outdoor fan is controlled as well as normal operation during forced operation.
6. Fan speed control during indoor unit quiet/QUIET OUTDOOR UNIT operation
The rotation speed of the outdoor fan is reduced by the command of the indoor unit
quiet/QUIET OUTDOOR UNIT operation.
7. Fan ON/OFF control when operation (cooling, heating, dry) starts/stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF
when the operation stops.
3.10 Liquid Compression Protection Function
Outline The compressor stops according to the outdoor temperature for protection.
Details Operation stops depending on the outdoor temperature.
The compressor turns off under the conditions that the system is in cooling operation and the
outdoor temperature is below 0°C (32°F).
However, the cooling operation range can be extended to the lowest temperature of –20°C
(–4°F) by changing facility setting. Refer to page 149 for details of facility setting.

Control Specification SiUS092519E
50 Part 4 Functions and Control
3.11 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than a certain value to finish defrosting.
Details Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature. (For details, refer to the table on the follow pages. (P. 51, 52))
Furthermore, even if the above conditions are not met, if heating operation accumulates for
approximately 6 hours under conditions where the outdoor temperature is below 2°C, the
system start defrosting.
The system is in heating operation.
The compressor operates for 6 minutes.
More than A minutes (depending on the duration of the previous defrost control) of
accumulated time have passed since the start of the operation or ending the previous
defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature (B).
09/12 class 15/18/24 class
A (minute) 20 ~ 25 32
B (°C) 2 ~ 13 4 ~ 12
(°F) 35.6 ~ 55.4 39.2 ~ 53.6
C (Hz) 40 48
D (Hz) 40 62
E (seconds) 40 40
F (seconds) 60 60
G (seconds) 720 460
H (seconds) 50 80
J (seconds) 8 8
K (pulse) 400 288
L (pulse) 350 320
M (pulse) 400 256
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz 0 Hz
C Hz
D Hz
J sec.
PI control
8 sec.
H sec.
(R21661)
E sec.
F sec.
G sec.
L pulse zone
Electronic
expansion valve
opening
Normal
control
K pulse
zone
M pulse
zone
Starting
control

SiUS092519E Control Specification
Part 4 Functions and Control 51
09/12 class
Outdoor heat exchanger temperature of Defrost IN
Outdoor heat exchanger temperature of Defrost OUT
Conpressor
speed
Outdoor temperature (°F)
Outdoor
temperature (°F)
Outdoor
heat exchanger
temperature
(°F)
–13.0 –4.0 5.0 14.0 23.0 32.0 35.6 44.6
14 –14.8 –9.1 –1.6 8.8 13.3 20.7 23.7 24.8
16 –14.8 –9.4 –1.9 8.5 13.0 20.4 23.4 24.8 44.6 55.4
18 –14.8 –9.7 –2.3 8.2 12.6 20.1 23.1 24.8 42.8 55.4
20 –14.8 –10.0 –2.6 7.8 12.3 19.8 22.7 24.8 41.0 55.4
22 –14.8 –10.4 –2.9 7.5 12.0 19.4 22.4 24.8 39.2 55.4
24 –14.8 –10.7 –3.2 7.2 11.7 19.1 22.1 24.8 37.4 55.4
26 –14.8 –11.0 –3.6 6.9 11.3 18.8 21.8 24.8 35.6 55.4
28 –14.8 –11.3 –3.9 6.5 11.0 18.5 21.5 24.8 33.8 55.4
30 –14.8 –11.7 –4.2 6.2 10.7 18.1 21.1 24.8 32.0 55.4
32 –14.8 –12.0 –4.5 5.9 10.4 17.8 20.8 24.8 30.2 55.4
34 –14.8 –12.3 –4.9 5.6 10.0 17.5 20.5 24.8 28.4 55.4
36 –14.8 –12.6 –5.2 5.3 9.7 17.2 20.2 24.8 26.6 55.4
38 –14.8 –13.0 –5.5 4.9 9.4 16.9 19.8 24.8 24.8 55.4
40 –14.8 –13.3 –5.8 4.6 9.1 16.5 19.5 24.8 23.0 55.4
42 –14.8 –13.6 –6.2 4.3 8.8 16.2 19.2 24.8 21.2 55.4
44 –14.8 –13.9 –6.5 4.0 8.4 15.9 18.9 24.8 19.4 55.4
46 –14.8 –14.3 –6.8 3.6 8.1 15.6 18.5 24.8 17.6 55.4
48 –14.8 –14.6 –7.1 3.3 7.8 15.2 18.2 24.8 15.8 55.4
50 –14.8 –14.8 –7.4 3.0 7.5 14.9 17.9 24.8 14.0 55.4
52 –14.8 –14.8 –7.8 2.7 7.1 14.6 17.6 24.8 12.2 55.4
54 –14.8 –14.8 –8.1 2.3 6.8 14.3 17.2 24.7 10.4 55.4
56 –14.8 –14.8 –8.4 2.0 6.5 13.9 16.9 24.4 8.6 55.4
58 –14.8 –14.8 –8.7 1.7 6.2 13.6 16.6 24.1 6.8 55.4
60 –14.8 –14.8 –9.1 1.4 5.8 13.3 16.3 23.7 5.0 55.4
62 –14.8 –14.8 –9.4 1.0 5.5 13.0 16.0 23.4 3.2 55.4
64 –14.8 –14.8 –9.7 0.7 5.2 12.7 15.6 23.1 1.4 55.4
66 –14.8 –14.8 –10.0 0.4 4.9 12.3 15.3 22.8 –0.4 55.4
68 –14.8 –14.8 –10.4 0.1 4.6 12.0 15.0 22.4 –2.2 55.4
70 –14.8 –14.8 –10.7 –0.2 4.2 11.7 14.7 22.1 –4.0 55.4
72 –14.8 –14.8 –11.0 –0.6 3.9 11.4 14.3 21.8 –5.8 55.4
74 –14.8 –14.8 –11.3 –0.9 3.6 11.0 14.0 21.5 –7.6 55.4
76 –14.8 –14.8 –11.7 –1.2 3.3 10.7 13.7 21.1 –9.4 55.4
78 –14.8 –14.8 –12.0 –1.5 2.9 10.4 13.4 20.8 –11.2 55.4
80 –14.8 –14.8 –12.3 –1.9 2.6 10.1 13.0 20.5 –13.0 55.4
82 –14.8 –14.8 –12.6 –2.2
2.3 9.7 12.7 20.2
84 –14.8 –14.8 –12.9 –2.5 2.0 9.4 12.4 19.9
86 –14.8 –14.8 –13.3 –2.8 1.6 9.1 12.1 19.5
88 –14.8 –14.8 –13.6 –3.2 1.3 8.8 11.8 19.2
90 –14.8 –14.8 –13.9 –3.5 1.0 8.4 11.4 18.9
92 –14.8 –14.8 –14.2 –3.8 0.7 8.1 11.1 18.6
94 –14.8 –14.8 –14.6 –4.1 0.3 7.8 10.8 18.2

Control Specification SiUS092519E
52 Part 4 Functions and Control
15/18/24 class
Outdoor heat exchanger temperature of Defrost IN
Outdoor heat exchanger temperature of Defrost OUT
Conpressor
speed
Outdoor temperature (°F)
Outdoor
temperature (°F)
Outdoor
heat exchanger
temperature
(°F)
–13.0 –4.0 5.0 14.0 23.0 32.0 35.6 44.6
14 –13.9 –6.5 1.0 8.4 15.9 23.3 26.3 28.4
16 –14.2 –6.7 0.8 8.2 15.7 23.1 26.1 28.4 44.6 48.3
18 –14.4 –6.9 0.5 8.0 15.4 22.9 25.9 28.4 42.8 49.6
20 –14.6 –7.1 0.3 7.8 15.2 22.7 25.7 28.4 41.0 50.9
22 –14.8 –7.3 0.1 7.6 15.0 22.5 25.5 28.4 39.2 52.1
24 –15.0 –7.5 –0.1 7.4 14.8 22.3 25.3 28.4 37.4 53.4
26 –15.2 –7.8 –0.3 7.2 14.6 22.1 25.0 28.4 35.6 53.6
28 –15.4 –8.0 –0.5 6.9 14.4 21.8 24.8 28.4 33.8 53.6
30 –15.6 –8.2 –0.7 6.7 14.2 21.6 24.6 28.4 32.0 53.6
32 –15.8 –8.4 –0.9 6.5 14.0 21.4 24.4 28.4 30.2 53.6
34 –16.1 –8.6 –1.1 6.3 13.8 21.2 24.2 28.4 28.4 53.6
36 –16.3 –8.8 –1.4 6.1 13.6 21.0 24.0 28.4 26.6 53.6
38 –16.5 –9.0 –1.6 5.9 13.3 20.8 23.8 28.4 24.8 53.6
40 –16.7 –9.2 –1.8 5.7 13.1 20.6 23.6 28.4 23.0 53.6
42 –16.9 –9.4 –2.0 5.5 12.9 20.4 23.4 28.4 21.2 53.6
44 –17.1 –9.7 –2.2 5.3 12.7 20.2 23.1 28.4 19.4 53.6
46 –17.3 –9.9 –2.4 5.0 12.5 19.9 22.9 28.4 17.6 53.6
48 –17.5 –10.1 –2.6 4.8 12.3 19.7 22.7 28.4 15.8 53.6
50 –17.7 –10.3 –2.8 4.6 12.1 19.5 22.5 28.4 14.0 53.6
52 –18.0 –10.5 –3.0 4.4 11.9 19.3 22.3 28.4 12.2 53.6
54 –18.2 –10.7 –3.3 4.2 11.7 19.1 22.1 28.4 10.4 53.6
56 –18.4 –10.9 –3.5 4.0 11.4 18.9 21.9 28.4 8.6 53.6
58 –18.6 –11.1 –3.7 3.8 11.2 18.7 21.7 28.4 6.8 53.6
60 –18.8 –11.3 –3.9 3.6 11.0 18.5 21.5 28.4 5.0 53.6
62 –19.0 –11.6 –4.1 3.4 10.8 18.3 21.2 28.4 3.2 53.6
64 –19.2 –11.8 –4.3 3.1 10.6 18.1 21.0 28.4 1.4 53.6
66 –19.4 –12.0 –4.5 2.9 10.4 17.8 20.8 28.3 –0.4 53.6
68 –19.6 –12.2 –4.7 2.7 10.2 17.6 20.6 28.1 –2.2 53.6
70 –19.8 –12.4 –4.9 2.5 10.0 17.4 20.4 27.9 –4.0 53.6
72 –20.1 –12.6 –5.2 2.3 9.8 17.2 20.2 27.6 –5.8 53.6
74 –20.3 –12.8 –5.4 2.1 9.5 17.0 20.0 27.4 –7.6 53.6
76 –20.5 –13.0 –5.6 1.9 9.3 16.8 19.8 27.2 –9.4 53.6
78 –20.7 –13.2 –5.8 1.7 9.1 16.6 19.6 27.0 –11.2 53.6
80 –20.9 –13.5 –6.0 1.5 8.9 16.4 19.3 26.8 –13.0 53.6
82 –21.1 –13.7 –6.2 1.2
8.7 16.2 19.1 26.6
84 –21.3 –13.9 –6.4 1.0 8.5 15.9 18.9 26.4
86 –21.5 –14.1 –6.6 0.8 8.3 15.7 18.7 26.2
88 –21.7 –14.3 –6.8 0.6 8.1 15.5 18.5 26.0
90 –22.0 –14.5 –7.1 0.4 7.9 15.3 18.3 25.7
92 –22.0 –14.7 –7.3 0.2 7.6 15.1 18.1 25.5
94 –22.0 –14.9 –7.5 0.0 7.4 14.9 17.9 25.3
96 –22.0 –15.1 –7.7 –0.2 7.2 14.7 17.7 25.1
98 –22.0 –15.3 –7.9 –0.4 7.0 14.5 17.4 24.9
100 –22.0 –15.6 –8.1 –0.7 6.8 14.3 17.2 24.7
102 –22.0 –15.8 –8.3 –0.9 6.6 14.0 17.0 24.5

SiUS092519E Control Specification
Part 4 Functions and Control 53
3.12 Electronic Expansion Valve Control
Outline The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Open Control
1. Electronic expansion valve control when starting operation
2. Electronic expansion valve control when the frequency changes
3. Electronic expansion valve control for defrosting
4. Electronic expansion valve control when the discharge pipe temperature is abnormally high
5. Electronic expansion valve control when the discharge pipe thermistor is disconnected
Feedback Control
Target discharge pipe temperature control
Details The followings are the examples of electronic expansion valve control for each operation mode.
R4003560
: Available
: Not available
Control
Status
Starting operation control
Control when the frequency changes
Target discharge pipe temperature control
Discharge pipe thermistor disconnection control
High discharge pipe temperature control
Defrost control (heating only)
Pressure equalizing control
Opening limit control
Power on ; Compressor stop
Operation start
Frequency change under starting control
During target discharge pipe temperature control
Frequency change under target discharge pipe
temperature control
Discharge pipe thermistor disconnection
Frequency change under discharge pipe thermistor
disconnection control
During defrost control

Control Specification SiUS092519E
54 Part 4 Functions and Control
3.12.1 Initialization as Power Supply On
The electronic expansion valve is initialized (fully closed) when the power is turned on. Then,
the valve opening position is set and the pressure is equalized.
3.12.2 Pressure Equalizing Control
When the compressor is stopped, the pressure equalizing control is activated. The electronic
expansion valve opens, and develops the pressure equalization.
3.12.3 Opening Limit Control
The maximum and minimum opening of the electronic expansion valve are limited.
The electronic expansion valve is fully closed when cooling operation stops, and is opened at a
fixed degree during defrosting.
3.12.4 Starting Operation Control
The electronic expansion valve opening is controlled when the operation starts, thus preventing
superheating or liquid compression.
3.12.5 Control when the Frequency Changes
When the target discharge pipe temperature control is active, if the target frequency changes to
a specified value in a certain time period, the target discharge pipe temperature control is
canceled and the target opening of the electronic expansion valve is changed according to the
frequency shift.
3.12.6 High Discharge Pipe Temperature Control
When the compressor is operating, if the discharge pipe temperature exceeds a certain value,
the electronic expansion valve opens and the refrigerant runs to the low pressure side.
This procedure lowers the discharge pipe temperature.
09/12 class 15/18/24 class
Maximum opening (pulse) 470 490
Minimum opening (pulse) 60 40

SiUS092519E Control Specification
Part 4 Functions and Control 55
3.12.7 Discharge Pipe Thermistor Disconnection Control
Outline The disconnection of the discharge pipe thermistor is detected by comparing the discharge pipe
temperature with the condensation temperature. If the discharge pipe thermistor is
disconnected, the electronic expansion valve opens according to the outdoor temperature and
the operation frequency, operates for a specified time, and then stops.
After 3 minutes, the operation restarts and checks if the discharge pipe thermistor is
disconnected. If the discharge pipe thermistor is disconnected, the system stops after operating
for a specified time.
If the disconnection is detected repeatedly, the system is shut down. When the compressor runs
for 60 minutes without any error, the error counter is reset.
Details Determining thermistor disconnection
When the starting control finishes, the detection timer for disconnection of the discharge pipe
thermistor (A seconds) starts. When the timer is over, the following adjustment is made.
1. When the operation mode is cooling
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe temperature +6°C (+10.8°F) < outdoor heat exchanger temperature
2. When the operation mode is heating
When the following condition is fulfilled, the discharge pipe thermistor disconnection is
ascertained.
Discharge pipe temperature +6°C (+10.8°F) < indoor heat exchanger temperature
When the thermistor is disconnected
When the disconnection is ascertained, the compressor continues operation for 9 minutes and
then stops.
If the compressor stops repeatedly, the system is shut down.
A (seconds)
09/12 class 15 class 18/24 class
Other than below 720 540 1020
Heating
(When outdoor temperature
is below –15°C (5°F))
1200 1800 1800

Control Specification SiUS092519E
56 Part 4 Functions and Control
3.12.8 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual
discharge pipe temperature becomes close to the target discharge pipe temperature. (Indirect
SH (superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every A seconds. The opening degree of the electronic expansion valve is adjusted by the
following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
The time depends on the opening of the electronic expansion valve.
3.13 Malfunctions
3.13.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistor:
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
3.13.2 Detection of Overcurrent and Overload
Outline An excessive output current is detected and the OL temperature is observed to protect the
compressor.
Details If the OL (compressor head) temperature exceeds 120 ~ 130°C (248 ~ 266°F) (depending
on the model), the system shuts down the compressor.
If the inverter current exceeds 12.0 ~ 20.0 A (depending on the model), the system shuts
down the compressor.
The upper limit of the current decreases when the outdoor temperature exceeds a certain
level.
09/12 class 15/18/24 class
A (seconds) 10 ~ 20 20
SC
(Subcooling)
SH
(Superheating)
The target discharge pipe
temperature is set as to become
the target SH.
The inclination does not change
depending on the operating condition.
(R23014)

Applicable Remote Controller SiUS092519E
58 Part 5 Remote Controller
Note
1. Applicable Remote Controller
Refer to the operation manual of applicable model for details. You can download operation
manuals from Daikin Business Portal:
Daikin Business Portal Document Search Item Category Installation/Operation Manual
(URL: https://global1d.daikin.com/business_portal/login/
)
Model Name Wired R/C
Reference
Page
FDMA09AVJU9
BRC1NRV71 59
FDMA12AVJU9
FDMA15AVJU9
FDMA18AVJU9
FDMA24AVJU9

SiUS092519E BRC1NRV71
Part 5 Remote Controller 59
2. BRC1NRV71
R5000499
On/Off
Mode
Fan
Speed
Cancel
Functions other than basic operation items (i.e., On/Off, Operation
Mode, Fan Speed, and Setpoint) are set from the menu screen.
NOTE
• Do not install the remote controller in places exposed to direct sunlight, the LCD
will be damaged.
• Do not pull or twist the remote controller cord, the remote controller may be
damaged.
• Do not use objects with sharp ends to press the buttons on the remote controller,
damage may result.
2. Fan speed control
button
3. Menu/OK button
8. On/Off button
10. Cancel button
9. Operation lamp
11. LCD (with backlight)
4. Up button
5. Down button
6. Right button
7. Left button
1. Operation mode
selector button
B(1B3LQGG

BRC1NRV71 SiUS092519E
60 Part 5 Remote Controller
R5000500
1. Operation mode selector button
• Press this button to select the operation
mode of your preference. (See page 10.)
* Available modes vary with the model of
unit.
2. Fan speed control button
• Press this button to select the fan speed of
your preference. (See page 11.)
* Available fan speeds vary with the model
of unit.
3. Menu/OK button
• Used to enter the main menu.
5GGRCIG|HQTVJGOGPWKVGOU
• Used to enter the selected item.
4. Up button
• Used to raise the setpoint.
• The item above the current selection will be
highlighted.
(The highlighted items will be scrolled
continuously when the button is
continuously pressed.)
• Used to change the selected item.
5. Down button
• Used to lower the setpoint.
• The item below the current selection will be
highlighted.
(The highlighted items will be scrolled
continuously when the button is
continuously pressed.)
• Used to change the selected item.
6. 4KIJVDWVVQP
• Used to highlight the next items on the
right-hand side.
• Each screen is scrolled in the right-hand
direction.
7. .GHVDWVVQP
• Used to highlight the next items on the
left-hand side.
• Each screen is scrolled in the left-hand
direction.
8. 1P1HHDWVVQP
• Press this button and system will start.
• Press this button again to stop the system.
9. Operation lamp
• This lamp illuminates solid green during
normal operation.
• 6JKUNCORƃCUJGUKHCPGTTQTQEEWTU
10. Cancel button
• Used to return to the previous screen.
11. .%&YKVJDCEMNKIJV
• The backlight will be illuminated for
CRRTQZKOCVGN[|UGEQPFUD[RTGUUKPICP[
button.
• If two remote controllers are used to control
a single unit, only the controller accessed
ƂTUVYKNNJCXGDCEMNKIJVHWPEVKQPCNKV[
B(1B3LQGG

SiUS092519E BRC1NRV71
Part 5 Remote Controller 61
R5000501
Liquid Crystal Display
•
Three types of display mode (Standard, Detailed and Simple) are available.
•
Standard display is set by default.
•
Detailed and Simple displays can be selected in the main menu. (See page 44.)
Standard display
Set to
Cool
Heat
74F
70F
Auto
Cool
This function is not available
<Standard display example>
6. Ventilation
2. Fan Speed
1. Operation mode
11.Setback
17.Lockout
7. ( ) Key Lock
3. Setpoint
4.
Stand by for Defrost/
Hot start
/Oil return
5. Message
10. Changeover controlled by
the master indoor unit
9.Under centralized
control
8. ( ) Scheduled or
Override
AUTO
ERV
AIR
PURIFY
CENTRAL
CONTROL
MASTER
CONTROLLED
SETBACK
STANDBY
LOCKOUT
Detailed display
6JGCKTƃQYFKTGEVKQPENQEMCPFUGNGEVCDNGKVGOCRRGCTQP&GVCKNGF
FKURNC[UETGGPKPCFFKVKQPVQVJGKVGOUCRRGCTKPIQP5VCPFCTFFKURNC[
Cool
Heat
74
F
70
F
Room
Fri
11
:
03
A
Set to
74
F
Return Setting
Auto
Cool
14.
Selectable Display
Item
12.
#KTƃQY&KTGEVKQP
(Displayed only when
the indoor unit is
turned on.)
%WTTGPV&C[6KOG
JQWTVKOG
display)
<Detailed display example 1>
AUTO
ERV
AIR
PURIFY
CENTRAL
CONTROL
MASTER
CONTROLLED
SETBACK
STANDBY
Return Setting
Auto
Cool
<Detailed display example 2>
0Q#KTƃQY
Direction display
YKVJPQCKTƃQYFKTGEVKQP
settings)
No Fan speed display
(with no fan speed
EQPVTQNHWPEVKQP
No Selectable
Display Item
YKVJPQUGNGEVCDNG
FKURNC[KVGOUGNGEVGF
No Clock display
YJGPVJGENQEMJCU
PQVDGGPUGV[GV
15. ( ) Unable to
schedule
16.
Optimum Start/Stop
--
:
--
CENTRAL
CONTROL
MASTER
CONTROLLED
OPTIMUM
START
AUTO
ERV
AIR
PURIFY
STANDBY
B(1B3LQGG

BRC1NRV71 SiUS092519E
62 Part 5 Remote Controller
R5000502
Simple display
70F
74
F
74F
Auto
Cool
Room
STANDBY
Set to
Heat Cool
SETBACK
LOCKOUT
<Simple display example>
2. Fan speed
3. Setpoint
1. Operation mode
14.Selectable Display
Item
11.Setback
17.Lockout
4.
Stand by for Defrost/
Hot start/Oil return
Note for all display modes
• &GRGPFKPIQPVJGƂGNFUGVVKPIUYJKNGVJGWPKVKUUVQRRGF1((OC[DGFKURNC[GFKPUVGCFQHVJG
QRGTCVKQPOQFGCPFQTVJGUGVRQKPVOC[PQVDGFKURNC[GF
B(1B3LQGG

SiUS092519E BRC1NRV71
Part 5 Remote Controller 63
R5000503
1. Operation mode
• Used to display the current operation
mode: Cool, Heat, Vent, Fan, Dry or Auto.
• In Auto mode, the actual operation mode
(Cool or Heat) will be also displayed.
• Operation mode cannot be changed when
OFF is displayed.
Operation mode can be changed after
starting operation.
2. Fan Speed
• Used to display the fan speed that is set for
the unit.
• The fan speed will not be displayed if the
connected model does not have fan speed
control functionality.
3. Setpoint
• Used to display the setpoint for the unit.
• Use the Celsius/Fahrenheit item in the
main menu to select the temperature unit
(Celsius or Fahrenheit).
4. Stand by for Defrost/Hot start/
Oil return “
STANDBY
” (See page 12.)
+HXGPVKNCVKQPKEQPKUFKURNC[GFKPVJKUƂGNF
• Indicates that an energy recovery ventilator
(ERV) is connected.
For details, refer to the Operation Manual
of the ERV.
5. Message
The following messages may be
displayed.
“This function is not available”
• Displayed for a few seconds when an
Operation button is pressed and the unit
does not provide the corresponding
function.
• In a remote control group, the message will
not appear if at least one of the units
provides the corresponding function.
p'TTQT2WUJ/GPWDWVVQPq
p9CTPKPI2WUJ/GPWDWVVQPq
• Displayed if an error or warning is detected
(see page 54).
p6KOGVQENGCPƂNVGTq
“Time to clean element”
p6KOGVQENGCPƂNVGTGNGOGPVq
• Displayed as a reminder when it is time to
ENGCPVJGƂNVGTCPFQTGNGOGPV
(see page 52).
6. Ventilation
• Displayed when an energy recovery
ventilator is connected.
• Ventilation Mode icon.“
AUTO
ERV
ERV
BYPASS
”
These icons indicate the current ventilation
mode (ERV only) (AUTO, ERV, BYPASS).
• #KT2WTKH[+%10p
AIR
PURIFY
”
This icon indicates that the air purifying unit
(Optional) is in operation.
7. Key Lock (See page 19.)
• Displayed when the key lock is set.
8. Scheduled or Override
(See page 33, 38.)
• Displayed if the Schedule or Override is
enabled.
• For Schedule, see page 33, for override,
see page 38.
• When the Override is active, the icon will
ƃCUJp
”
9. 7PFGT%GPVTCNK\GFEQPVTQNp
CENTRAL
CONTROL
”
• Displayed if the system is under the
management of a multi-zone controller
(Optional) and the operation of the system
through the remote controller is limited.
10. %JCPIGQXGTEQPVTQNNGFD[VJG
master indoor unit “
MASTER
CONTROLLED
”
(VRV only)
• Displayed when another indoor unit on the
system has the authority to change the
operation mode between cool and heat.
B(1B3LQGG

BRC1NRV71 SiUS092519E
64 Part 5 Remote Controller
R5000504
11. Setback “
SETBACK
” (See page 14.)
• 6JGUGVDCEMKEQPƃCUJGUYJGPVJGWPKVKU
VWTPGFQPD[VJGUGVDCEMEQPVTQN
12. #KTƃQY&KTGEVKQPp ”
• &KURNC[GFYJGPVJGCKTƃQYFKTGEVKQPCPF
UYKPICTGUGV(see page 26)
• +HVJGEQPPGEVGFOQFGNFQGUPQVKPENWFG
QUEKNNCVKPINQWXGTUVJKUKVGOYKNNPQVDG
FKURNC[GF
13. %WTTGPV&C[6KOG|JQWT
VKOGFKURNC[
• &KURNC[GFKHVJGENQEMKUUGV(see page 46)
• +HVJGENQEMKUPQVUGVpqYKNNDG
FKURNC[GF
• JQWTVKOGHQTOCVKUFKURNC[GFD[FGHCWNV
• 5GNGEVJQWTVKOGFKURNC[QRVKQPKPVJG
OCKPOGPWWPFGTp%NQEM%CNGPFCTq
14. 5GNGEVCDNG&KURNC[+VGO
• 4QQOVGORGTCVWTGKUUGNGEVGFD[FGHCWNV
• (QTQVJGTEJQKEGUUGGRCIG
15. 7PCDNGVQUEJGFWNG
• &KURNC[GFYJGPVJGENQEMPGGFUVQDGUGV
• 6JGUEJGFWNGHWPEVKQPYKNNPQVYQTMWPNGUU
VJGENQEMKUUGV
16. 1RVKOWO5VCTV5VQR
“
OPTIMUM
START
” “
OPTIMUM
STOP
” (See page 40.)
• &KURNC[GFYJGPVJG1RVKOWOUVCTVQT
1RVKOWOUVQRKUGPCDNGF
• “
OPTIMUM
START
qQTp
OPTIMUM
STOP
qKUƃCUJKPIYJGPVJG
1RVKOWOUVCTVQT1RVKOWOUVQRKUCEVKXG
17. .QEMQWVp
LOCKOUT
”
4QQHVQRWPKVQPN[
• “
LOCKOUT
qKUƃCUJKPIYJGPVJGNQEMQWVKU
CEVKXG
B(1B3LQGG

SiUS092519E
Part 6 Service Diagnosis 65
1. General Problem Symptoms and Check Items .....................................67
2. Troubleshooting with LED .....................................................................68
2.1 Indoor Unit..............................................................................................68
2.2 Outdoor Unit ...........................................................................................68
3. Service Diagnosis .................................................................................69
3.1 BRC1NRV71 ..........................................................................................69
4. Error Codes and Description.................................................................71
5. Troubleshooting for Indoor Unit.............................................................72
5.1 External Protection Device Abnormality .................................................72
5.2 Refrigerant Leak Detection (Confirmed).................................................73
5.3 Refrigerant Leak Detection (Monitoring) ................................................75
5.4 Indoor Unit PCB Abnormality .................................................................76
5.5 Drain Level Control System Abnormality................................................77
5.6 Indoor Fan Motor (DC Motor) or Related Abnormality ...........................78
5.7 Indoor Fan PCB Abnormality..................................................................80
5.8 Humidifier or Related Abnormality..........................................................81
5.9 Defective Capacity Setting .....................................................................82
5.10 Transmission Abnormality between Indoor Unit Control PCB and
Fan PCB.................................................................................................83
5.11 Thermistor or Related Abnormality.........................................................85
5.12 Refrigerant Leak Detection Sensor Failure ............................................86
5.13 Refrigerant Leak Detection Sensor Disconnection.................................87
5.14 Remote Controller Thermistor Abnormality ............................................88
5.15 Low-voltage Detection or Over-voltage Detection..................................89
5.16 Signal Transmission Error (Between Indoor Unit and Outdoor Unit)......91
5.17 Signal Transmission Error (Between Indoor Unit and Remote
Controller)...............................................................................................93
5.18 Signal Transmission Error (Between MAIN/SUB Remote Controllers) ..94
5.19 Unspecified Voltage (Between Indoor Unit and Outdoor Unit) ...............95
5.20 Address Duplication of Centralized Controller........................................96
6. Troubleshooting for Outdoor Unit..........................................................97
6.1 Outdoor Unit PCB Abnormality...............................................................97
6.2 Actuation of High Pressure Switch .........................................................98
6.3 OL Activation (Compressor Overload) ...................................................99
6.4 Compressor Lock .................................................................................101
6.5 DC Fan Lock ........................................................................................102
6.6 Input Overcurrent Detection .................................................................103
6.7 Electronic Expansion Valve Coil Abnormality.......................................104
6.8 Four Way Valve Abnormality................................................................105
6.9 Discharge Pipe Temperature Control...................................................107
6.10 High Pressure Control in Cooling .........................................................108
6.11 System Shutdown due to Temperature Abnormality in the
Part 6
Service Diagnosis

SiUS092519E
66 Part 6 Service Diagnosis
Compressor..........................................................................................110
6.12 Compressor Sensor System Abnormality ............................................111
6.13 High Pressure Switch System Abnormality ..........................................112
6.14 Position Sensor Abnormality ................................................................113
6.15 Fan IPM temperature error...................................................................116
6.16 DC Voltage/Current Sensor Abnormality..............................................117
6.17 Thermistor or Related Abnormality (Outdoor Unit)...............................118
6.18 Electrical Box Temperature Rise..........................................................120
6.19 Radiation Fin Temperature Rise ..........................................................121
6.20 Output Overcurrent Detection ..............................................................122
6.21 IGBT temperature error ........................................................................124
6.22 Signal Transmission Error on Outdoor Unit PCB .................................125
7. Check ..................................................................................................126
7.1 Thermistor Resistance Check ..............................................................126
7.2 Indoor Fan Motor Connector Check .....................................................127
7.3 Power Supply Waveform Check...........................................................127
7.4 Electronic Expansion Valve Check.......................................................128
7.5 Four Way Valve Performance Check ...................................................129
7.6 Inverter Unit Refrigerant System Check...............................................129
7.7 Inverter Analyzer Check .......................................................................130
7.8 Outdoor Fan Motor Check....................................................................132
7.9 Installation Condition Check.................................................................132
7.10 Discharge Pressure Check...................................................................133
7.11 Outdoor Fan System Check .................................................................133
7.12 Main Circuit Short Check......................................................................134
7.13 Power Module Check ...........................................................................136

SiUS092519E General Problem Symptoms and Check Items
Part 6 Service Diagnosis 67
1. General Problem Symptoms and Check Items
Symptom Check Item Measures
Reference
Page
The unit does not
operate.
Check the power supply. Check if the rated voltage is supplied. —
Check the type of the indoor unit. Check if the indoor unit type is compatible with the
outdoor unit.
—
Check the outdoor temperature. Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
159
Diagnose with remote controller
indication.
— 71
Check the remote controller
addresses.
Check if address settings for the remote controller
and indoor unit are correct.
67
Operation sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles stops air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor temperature. Heating/cooling operations are not available when
the outdoor temperature is out of the operation
limit. Check the reference page for the operation
limit.
159
Diagnose with remote controller
indication.
— 71
The unit operates but
does not cool, or does
not heat.
Check for wiring and piping errors in
the connection between the indoor
unit and outdoor unit.
— —
Check for thermistor detection errors. Check if the thermistor is mounted securely. —
Check for faulty operation of the
electronic expansion valve.
Set the unit to cooling operation, and check the
temperature of the liquid pipe to see if the
electronic expansion valve works.
—
Diagnose with remote controller
indication.
— 71
Diagnose by service port pressure
and operating current.
Check for refrigerant shortage.
—
Large operating noise
and vibrations
Check the resistance between the
terminals of the power module.
— 136
Check the power module. — —
Check the installation condition. Check if the required spaces for installation
(specified in the installation manual) are provided.
—

Troubleshooting with LED SiUS092519E
68 Part 6 Service Diagnosis
2. Troubleshooting with LED
2.1 Indoor Unit
Operation Lamp Check the interval time between blinks of the OPERATION lamp.
FDMA Series with BRC1NRV71 Wired Remote Controller
The operation lamp blinks when any of the following errors are detected.
1. When a protection device of the indoor or outdoor unit is activated, or when the thermistor
malfunctions.
2. When a signal transmission error occurs between the indoor and outdoor units.
In either case, conduct the diagnostic procedure described in the following pages.
R4003516
Service Monitor The indoor unit has a green LED (HAP) on the control PCB. When the microcomputer works in
order, the LED blinks. (Refer to page 21 for the location of LED.)
2.2 Outdoor Unit
The outdoor unit has one green LED (LED A) on the PCB. When the microcomputer works in
order, the LED A blinks. However, the LED A turns OFF while the standby electricity saving
function is activated and the power supply is OFF.
Refer to page 23, 24 for the location of LED A.
Operation lamp (green)
#The error or warning message also blinks on the basic screen.
#

SiUS092519E Service Diagnosis
Part 6 Service Diagnosis 69
3. Service Diagnosis
3.1 BRC1NRV71
Relations
Between Modes
On power-up, the message “Checking the connection. Please standby.” will be displayed on
the remote controller screen temporarily and then the basic screen will be displayed. To access
a mode from the basic screen, refer to the figure below.
When any of the operation buttons is pressed, the backlight will come on and remain lit for about
30 seconds. Be sure to press a button while the backlight is on.
R6001318
Basic screen
Main Menu screen
Service Settings screen
Maintenance Menu screen
Main Menu
• Override
• Optimum Start/Stop
• Celsius / Fahrenheit
• Filter Auto Clean
• Maintenance Information
• Configuration
• Current Settings
• Clock & Calendar
• Daylight Saving Time
• Language
Press Cancel
button once.
Press
Menu/OK
button once.
Basic Screen
• Operation mode changeover
• Fan speed control
• Menu display
• Confirmation of each setting
• On
• Off
• Cancel
• Operation lamp
Press Cancel button
for 4 seconds or more.
Press Cancel
button once.
Press Cancel button
for 4 seconds or more.
Press Cancel
button once.
Maintenance Menu
• Model Name
• Operation Hours
• Indoor Unit Status
• Outdoor Unit Status
• Forced Defrost
• Error Display
• Swap Unit No.
• Addressed Sensor Value
Service Settings
• Test Operation
• Maintenance Contact
• Blower Speed
• Field Settings
• Energy Saving Options
• Prohibit Function
• Min Setpoints Differential
• Outdoor unit AirNet Address
• Unit Operation Hours
• Error History
• Indoor Unit Status
• Outdoor Unit Status
• Unit Status
• Forced Fan ON
• Switch Main Sub Controller
• Filter Indicator
• Brush/Filter Ind.
• Disable Filter Auto Clean
# The items shown on the remote controller are
different depending on the connected indoor unit.
Cool
Return Setting
Set to
74
F
Setting
Main Menu
CO2 Monitoring
Humidity
Airflow Direction
Individual Airflow Direction
Ventilation
Schedule
1/3
Setting
Service Settings
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
1/3
Test Operation
Setting
Maintenance Menu
Operation Hours
Indoor Unit Status
Outdoor Unit Status
Forced Defrost
Error Display
1/2
Model Name

Service Diagnosis SiUS092519E
70 Part 6 Service Diagnosis
Service
Diagnosis
The following message is displayed on the screen when an error (or a warning) occurs during
operation.
Check the error code and take the corrective action specified for the particular model.
(R18817)
Screen
Operation lamp
Menu/OK button
Operation
1
Cool
Set to
Error : Push Menu button
74F
Error: Push Menu button
Warning: Push Menu button
Operation
lamp
2
Error Code: A1
Contact Info
0123-456-7890
Indoor Model ---/000
Outdoor Model ---/000
If an error occurs, either one of the following
items will flash in the basic screen.
* The Operation lamp will flash.
* For Simple display, the message is not
displayed, and only the Operation lamp
flashes.
* The Operation lamp will not flash.
* For Simple display, the message is not
displayed, and the Operation lamp does not
flash, either.
Press Menu/OK button.
The error code will flash and the service
contact and model name or code may
be displayed.
Notify your Daikin dealer of the Error
code and model name or code.

SiUS092519E Error Codes and Description
Part 6 Service Diagnosis 71
4. Error Codes and Description
Error
Codes
Description
Reference
Page
System 00 Normal —
U0 Refrigerant shortage —
U2 Low-voltage detection or over-voltage detection 89
U4 Signal transmission error
(between indoor unit and outdoor unit)
91
U5 Signal transmission error
(between indoor unit and remote controller)
93
U8 Signal transmission error
(between MAIN/SUB remote controller)
94
UA Unspecified voltage
(between indoor unit and outdoor unit)
95
UC Address duplication of centralized controller 96
UF Wrong wiring check error —
Indoor
Unit
A0-01 External protection device abnormality 72
A0-17, 19 Refrigerant leak detection 73, 75
A1 Indoor unit PCB abnormality 76
A3 Drain level control system abnormality 77
A6 Indoor fan motor (DC motor) or related abnormality 78
A8 Indoor fan PCB abnormality 80
AF Humidifier or related abnormality 81
AJ Capacity setting error 82
C1 Transmission abnormality between indoor unit PCB and fan PCB 83
C4, C5 Indoor heat exchanger thermistor or related abnormality 85
C9 Room temperature thermistor or related abnormality 85
CH-11 Refrigerant leak detection sensor failure 86
CH-14 Refrigerant leak detection sensor disconnection 87
CJ Remote controller thermistor abnormality 88
Outdoor
Unit
E1 Outdoor unit PCB abnormality 97
E3 Actuation of high pressure switch 98
E5 OL activation (compressor overload) 99
E6 Compressor lock 101
E7 DC fan lock 102
E8 Input overcurrent detection 103
E9 Electronic expansion valve abnormality 104
EA Four way valve abnormality 105
F3 Discharge pipe temperature control 107
F6 High pressure control in cooling 108
F8 System shutdown due to temperature abnormality in the
compressor
110
H0 Compressor system sensor abnormality 111
H3 High pressure switch system abnormality 112
H6 Position sensor abnormality 113
H7 Fan IPM temperature error 116
H8 DC Voltage/Current Sensor Abnormality 117
H9 Outdoor temperature thermistor or related abnormality 118
J3 Discharge pipe thermistor or related abnormality 118
J6 Outdoor heat exchanger thermistor or related abnormality 118
L3 Electrical box temperature rise 120
L4 Radiation fin temperature rise 121
L5 Output overcurrent detection 122
LA IGBT temperature error 124
P4 Radiation fin thermistor or related abnormality 118
U7 Signal transmission error on outdoor unit PCB 125

Troubleshooting for Indoor Unit SiUS092519E
72 Part 6 Service Diagnosis
5. Troubleshooting for Indoor Unit
5.1 External Protection Device Abnormality
Error Code A0-01
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
When an open circuit occurs between external input terminals.
Supposed
Causes
Open external input terminals (TB4-TB5)
Activation of external protection device
Defective indoor unit PCB
Indoor unit fuse blown
24 VAC power is not supplied to TH2 and TR2 terminals on the indoor unit PCB.
Troubleshooting
R6001347
Fuse (F1U) is
blown.
24 VAC power
is supplied to TH2
and TR2 terminals.
External
protection device
is connected to TB4 and
TB5 of the indoor unit
terminal.
The
external protection
device is opened.
Is the external
terminals TB4 and TB5
opened?
Replace the indoor unit PCB.
Confirm that wiring follows
the wiring diagram and then
supply power to each
terminal.
Actuation of external protection
device.
Replace the fuse (F1U).
YES YES
NO NO
NO
NO
YES
YES
Close the terminals TB4 and
TB5.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 73
5.2 Refrigerant Leak Detection (Confirmed)
Error Code A0-17
Method of Error
Detection
Refrigerant leak detection sensor detects a refrigerant leak for a long period of time.
Error Decision
Conditions
When the A0-19 error detection status has occurred multiple times within a short period or
continuously for a certain duration
Supposed
Causes
Refrigerant leak from system piping
Refrigerant leak detection sensor deterioration/failure
Defective A1P control PCB
Troubleshooting
R6001341
Replacing the refrigerant sensor
1. Remove the 5 screws and then the service cover.
R6001348
Caution
▪ Be sure to turn off the power switch before connecting or disconnecting connectors,
or parts may be damaged.
▪ Refrigerant may be leaking.
▪ Please check the refrigerant leaking in a well-ventilated environment to prevent
accumulation.
▪ Be careful to avoid generating fire or sparks.
▪ While this error is being detected, the unit will operate the fan to disperse the
refrigerant. Be sufficiently careful not to injure yourself.
YES
Repair the leak, replace the
leak detection sensor, and
change the field setting 15
(25)-14 to 02 and turn the
power back on.
Refrigerant is
leaking from the system
piping.
Replace A1P PCB.
NO
Service cover

Troubleshooting for Indoor Unit SiUS092519E
74 Part 6 Service Diagnosis
2. Remove the screw and then the cover.
R6001349
3. Cut the 2 clamps.
Disconnect the relay connector.
Remove the screw and then the refrigerant sensor.
R6001350
Cover
Relay connector
Clamp
Refrigerant sensor

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 75
5.3 Refrigerant Leak Detection (Monitoring)
Error Code A0-19
Method of Error
Detection
Refrigerant leak detection sensor detects a refrigerant leak.
Error Decision
Conditions
When refrigerant concentrations exceeding the specified level are detected continuously during
short-term sampling checks
Supposed
Causes
Refrigerant leak from system piping
Troubleshooting
R6001342
Caution
▪ Be sure to turn off the power switch before connecting or disconnecting connectors,
or parts may be damaged.
▪ Refrigerant may be leaking.
▪ Please check the refrigerant leaking in a well-ventilated environment to prevent
accumulation.
▪ Be careful to avoid generating fire or sparks.
▪ While this error is being detected, the unit will operate the fan to disperse the
refrigerant. Be sufficiently careful not to injure yourself.
▪ Even if no refrigerant is confirmed after detection, the leak detection function will
continue for 5 minutes.
YES
NO
Repair the leak.
Refrigerant is
leaking from the system
piping.
YES
Follow the procedure
of A0-17.
Is
A0-19 not cleared after
approximately 10~15 minutes and
it switch to A0-17?
Normal
NO

Troubleshooting for Indoor Unit SiUS092519E
76 Part 6 Service Diagnosis
5.4 Indoor Unit PCB Abnormality
Error Code A1
Method of Error
Detection
The system checks the data from EEPROM.
Error Decision
Conditions
When the data from the EEPROM is not received correctly
EEPROM (Electrically Erasable Programmable Read Only Memory): A memory chip that holds
its content without power. It can be erased, either within the computer or externally and usually
requires more voltage for erasure than the common +5 volts used in logic circuits. It functions
like non-volatile RAM, but writing to EEPROM is slower than writing to RAM.
Supposed
Causes
Defective indoor unit PCB
External factor (noise etc.)
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R22247)
Normal?
Turn off the power. Then, turn on
the power to restart the system.
NO
YES
External factor other than malfunction
(for example, noise etc.)
Replace the indoor unit PCB
(control PCB).

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 77
5.5 Drain Level Control System Abnormality
Error Code A3
Method of Error
Detection
The float switch detects error.
Error Decision
Conditions
When the water level reaches its upper limit and when the float switch turns OFF
Supposed
Causes
Defective drain pump
Improper drain piping work
Clogged drain piping
Defective float switch
Defective indoor unit PCB
Defective short circuit connector X15A, X25A on indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connect the drain pump.
Replace the indoor unit
PCB (control PCB).
Replace the drain pump.
There is a drain system
abnormality.
Connect the float switch.
Replace the float switch.
Replace the indoor unit
PCB (control PCB).
(R25079)
NO
YES
NO
NO
YES
YES
Is the drain
pump connected to X25A on
the indoor unit
PCB?
NO
Is the drain water level
abnormally high?
YES
YES
Is the float switch
connected to X15A?
NO
Does the drain
pump work after the power
supply is on?
Is the voltage of
connector X25A 13 VDC?
YES
Remove the float switch from
X15A, short circuit X15A, and
restart operation.
NO
Does A3
appear on the remote
controller display?

Troubleshooting for Indoor Unit SiUS092519E
78 Part 6 Service Diagnosis
5.6 Indoor Fan Motor (DC Motor) or Related Abnormality
Error Code A6
Method of Error
Detection
Detection from the current flow on the fan PCB
Detection from the rotation speed of the fan motor in operation
Error Decision
Conditions
The rotation speed is less than a certain level for 6 seconds.
Supposed
Causes
Clogged foreign matter
Disconnection of fan motor connectors
Disconnection of the connector between the indoor unit PCB and the fan PCB
Defective fan PCB
Defective fan motor
No fuse continuity
Trouble Shooting
R6000547
Connect the connector
correctly.
Turn OFF the power supply
and wait for 10 minutes.
NO
YES
NO
Connect the connector
correctly.
NO
YES
YES
Replace the fuse.
There is a
continuity in the fuse
(∗2) on the fan PCB or fan
motor harness.
NO
The fan motor
connector (∗1) is
connected to the fan
PCB.
Remove the foreign matter.
YES
There is a foreign
matter around the fan.
The connector
between the indoor unit
control PCB and the fan
PCB is connected.
A
Go to the next page
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 79
Note
Reference
R6000961
Connector and indoor unit PCB
Check No.02 Refer to P.127
Continued from the
previous page
Turn OFF the power supply
and wait for 10 minutes.
Turn OFF the power supply
and wait for 10 minutes.
NO
NO
Replace the fan motor.
Each resistance
between the pins is equal to or
lower than 1
:
.
Replace the fan motor.
Replace the fan PCB (A2P).
The HAP
lamp on the indoor
unit control PCB is blinking
while the HAP lamp on the
fan PCB is not
blinking.
YES
YES
Check the fan motor connectors.
Check No.02
Replace the fan PCB (A2P).
p
When A6 abnormality still
reoccurs, replace the fan
motor.
A
Turn ON the power supply while
the fan motor connector (1) is
disconnected.
*1
Fan motor connector
*2
Fuse
X8A F2U

Troubleshooting for Indoor Unit SiUS092519E
80 Part 6 Service Diagnosis
5.7 Indoor Fan PCB Abnormality
Error Code A8
Method of Error
Detection
Microcomputer checks the voltage state of the fan PCB.
Error Decision
Conditions
Overvoltage or voltage drop is detected on the fan PCB.
Supposed
Causes
Defective fan PCB
External factor such as noise
Troubleshooting
R6000549
Caution
Be sure to turn off the power switch before connecting
or disconnecting connectors, or parts may be damaged.
Check for the indoor unit control
PCB (A1P) and the fan PCB
(A2P).
Connect the connector correctly.
NO
YES
YES
Is the
connector X3A on
the fan PCB connected
correctly?
Connect the connector correctly.
NO
YES
Is the
connector X70A on
the indoor unit control PCB
connected correctly?
Replace the harness.
YES
Is the harness
connecting X3A and X70A
broken?
NO
NO
Remove the external factor.
YES
Is there any external
factor such as noise?
Normal.
NO
Error is displayed
again.
Turn OFF the power supply
and then turn it ON again.
Start operation with the
remote controller.

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 81
Note
5.8 Humidifier or Related Abnormality
Error Code AF
Method of Error
Detection
Water leakage from humidifier(s) is detected based on the float switch ON/OFF changeover
while the system is not operating.
Error Decision
Conditions
The float switch changes from ON to OFF while the system is OFF
Supposed
Causes
Defective float switch
Error in water drain system of humidifier(s)
Clogged electric expansion value in humidifier(s)
Defective indoor unit PCB
Troubleshooting
The system continues to operate with the thermostat OFF even while the error code is
displayed.
YES
YES
NO
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
The float switch may be
defective. Check if the
drain-up height and the
horizontal pipe length
exceed the specifications.
Clogged water drain
system, clogged drain
pump, or faulty float switch
Replace the indoor unit
PCB (control PCB).
(R24055)
Humidifier(s)
connected to the system?
Is the water
drain system of the
humidifier normal?

Troubleshooting for Indoor Unit SiUS092519E
82 Part 6 Service Diagnosis
5.9 Defective Capacity Setting
Error Code AJ
Method of Error
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit control PCB, and whether the value is normal or
abnormal is determined.
Error Decision
Conditions
When the capacity code is not saved to the PCB, and the capacity setting adaptor is not
connected. When a capacity that does not exist for that unit is set.
Supposed
Causes
The capacity setting adaptor was not installed.
Defective indoor unit control PCB
Troubleshooting
R6001344
NO
NO
YES
The
indoor unit
control PCB was
replaced with a
spare PCB.
YES
The
capacity
setting adaptor need
to be installed when
replacing the
PCB.
Install a capacity setting
adaptor.
Replace the indoor unit control
PCB (A1P).
Replace the indoor unit control
PCB (A1P).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 83
Note(s)
5.10 Transmission Abnormality between Indoor Unit Control
PCB and Fan PCB
Error Code C1
Method of Error
Detection
Transmission conditions between the indoor unit control PCB (A1P) and fan PCB (A3P) are
checked via microcomputer.
Error Decision
Conditions
When normal transmission is not carried out for a certain duration.
Supposed
Causes
Defective connection of the connector between indoor unit control PCB (A1P) and fan PCB
(A2P)
Defective indoor unit control PCB (A1P)
Defective fan PCB (A2P)
External factor, such as instantaneous power failure
Troubleshooting
R6001345
1. Pull out and insert the connector once and check if it is absolutely connected.
2. Method to check transmission part of indoor unit control PCB.
(1) Turn OFF the power and remove the connector X70A of indoor unit control PCB (A1P).
(2) Short circuit X70A.
(3) After turning ON the power, check below numbers under field setting from remote controller.
(Confirmation: Second code No. at the condition of first code No. 21 on mode No. 41)
NO
NO
YES
Replace the fan PCB (A2P).
YES
YES
Is the connector
between indoor unit
control PCB (A1P) and fan
PCB (A2P) accurately
connected?
(1)
NO
C1 is displayed again.
Confirm the condition of
transmission on indoor unit control
PCB using field setting mode. (2)
Connect the connector X70A and
turn ON the power again.
Connect it and continue the
operation (It is possible to have
a cause, such as instantaneous
power failure).
Connect the connector
accurately.
Replace the indoor unit control
PCB (A1P).
Under above field
setting mode, second code
No. is 01.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Determination 01: Normal
Other than 01: Transmission error on indoor unit control PCB

Troubleshooting for Indoor Unit SiUS092519E
84 Part 6 Service Diagnosis
After confirmation, turn OFF the power, take off the short circuit and connect X70A back to
original condition.

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 85
Reference
5.11 Thermistor or Related Abnormality
Error Code C4, C5, C9
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The thermistor is disconnected or shorted while the unit is running.
Supposed
Causes
Disconnection of connector
Defective thermistor(s)
Breaking of wires
Defective indoor unit PCB
Troubleshooting If the cause of the problem is related to the thermistors, the thermistors should be checked prior
to changing the indoor unit PCB.
To check the thermistors, proceed as follows:
1. Disconnect the thermistor from the indoor unit PCB.
2. Read the temperature and the resistance value.
3. Check if the measured values correspond with the values in the table of thermistor
resistance check.
C4: Indoor heat exchanger thermistor 1 (liquid pipe) (R2T)
C5: Indoor heat exchanger thermistor 2 (R3T)
C9: Room temperature thermistor (R1T)
Check No.01 Refer to P.126
YES
(R24056)
NO
Check No. 01
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the defective
thermistor(s).
Replace the indoor unit PCB
(control PCB).
Normal?
Normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Troubleshooting for Indoor Unit SiUS092519E
86 Part 6 Service Diagnosis
5.12 Refrigerant Leak Detection Sensor Failure
Error Code CH-11
Method of Error
Detection
Error is issued when control PCB receives fault status from leak detection sensor during
operation.
Error Decision
Conditions
When leak detection sensor sends fault status information to control PCB for a certain set
timeframe.
Supposed
Causes
Broken leak detection sensor
Degraded leak detection sensor
Troubleshooting Replace the leak detection sensor.
Change the field setting 15 (25)-14 to 02 and turn the power back on.

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 87
5.13 Refrigerant Leak Detection Sensor Disconnection
Error Code CH-14
Method of Error
Detection
Error is issued when leak detection sensor is not connected to A1P control PCB when powered
up.
Error Decision
Conditions
When A1P control PCB does not have a connection with leak detection sensor at startup.
Supposed
Causes
Disconnected leak detection sensor
Broken wires in, short circuit of, or disconnection of connector of leak detection sensor
Incorrect wiring
Defective A1P control PCB
Troubleshooting
R6001346
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace A1P PCB.
Disconnect the leak detection
sensor from the wire harness,
then the power ON and wait for 2
minutes.
YES
Replace the leak detection
sensor.
Measure
the voltage between
pins 1 and 6 of the connector
(sensor side) of wire harness with
a multimeter. Is 5 VDC
supplied?
NO
NO
Connect the leak detection
sensor.
Is leak
detection sensor
connected to X41A on
A1P PCB?
YES
NO
Turn OFF the power and
disconnect the wire harness from
A1P PCB, then turn ON the
power and wait for 2 minutes.
YES
Replace the wire harness.
Measure
the voltage
between pins 1 and 4 of the
connector (X41A) on A1P PCB
with a multimeter. Is 5
VDC supplied?

Troubleshooting for Indoor Unit SiUS092519E
88 Part 6 Service Diagnosis
Note
5.14 Remote Controller Thermistor Abnormality
Error Code CJ
Method of Error
Detection
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by the temperature detected by the remote controller
thermistor.
Error Decision
Conditions
The remote controller thermistor is disconnected or shorted while the unit is running.
Supposed
Causes
Defective room temperature thermistor in the wired remote controller
Defective wired remote controller PCB
External factor such as noise
Troubleshooting
To delete the record of error codes, press ON/OFF button on the remote controller for 4
seconds or more while the error code is displayed in the inspection mode.
Replace the remote
controller.
External factor other than
equipment malfunction.
(for example, noise etc.)
NO
YES
(R23951)
Is
CJ displayed on
the remote controller
again?
Delete the record of error
codes. (Refer to Note)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 89
5.15 Low-voltage Detection or Over-voltage Detection
Error Code U2
Method of Error
Detection
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Conditions
Low-voltage detection:
The voltage detected by the DC voltage detection circuit is below 170 V (depending on the
model).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Over-voltage detection:
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer
(over 458 ~ 478 V, depending on the model).
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Supposed
Causes
Power supply voltage out of specification
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary drop of voltage
Momentary power failure
Defective outdoor unit PCB

Troubleshooting for Indoor Unit SiUS092519E
90 Part 6 Service Diagnosis
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB (main PCB).
Check for such factors for a
long term.
(R22445)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Disturbance factors
Noise
Power supply distortion
Turn on
the power. System
restarted? (Repeat a few
times.)
Loose or disconnected?
NO
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Does the
outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 91
5.16 Signal Transmission Error (Between Indoor Unit and
Outdoor Unit)
Error Code U4
Method of Error
Detection
The signal transmission data received from the outdoor unit is checked whether it is normal.
Error Decision
Conditions
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Supposed
Causes
Power supply voltage not as specified
Reduction of power supply voltage
Wiring error
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
Defective outdoor unit PCB
Short circuit inside the fan motor winding
Defective indoor unit PCB
Disturbed power supply waveform

Troubleshooting for Indoor Unit SiUS092519E
92 Part 6 Service Diagnosis
Reference
Troubleshooting
Check No.11 Refer to P.127
Check No.11
Check the power supply
waveform.
Check the voltage of the
connection wires on the indoor
terminal board between No. 1
and No. 3, and between No. 2
and No. 3.
YES
Blink
Replace the indoor unit PCB
(control PCB).
Locate the cause of the
disturbance of the power
supply waveform, and correct
it.
NO
(R21189)
Continuously ON or OFF
NO
YES
YES
NO
Caution
Correct the indoor unit -
outdoor unit connection wires.
Replace the outdoor unit PCB
(main PCB).
Replace the connection wires
between the indoor unit and
outdoor unit.
Is LED A blinking?
Properly insulated?
Is there any disturbance?
Is there any wiring error?
Check the indoor unit - outdoor
unit connection wires.
Check the LED A on the outdoor
unit PCB.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Before you check the LED A, cancel
the standby electricity saving
function by starting fan operation
with the remote controller.
Wait at least for 7 sec. after turning
on the power.
NO
YES
Check the power supply voltage.
Correct the power supply.
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Rotate the
outdoor fan by hand.
Does the outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 93
Note
5.17 Signal Transmission Error (Between Indoor Unit and
Remote Controller)
Error Code U5
Method of Error
Detection
In case of controlling 1 indoor unit with 2 remote controllers, check the system using
microcomputer if signal transmission between indoor unit and remote controller (main and sub)
is normal.
Error Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Connection of 2 main remote controllers (when using 2 remote controllers)
Defective indoor unit PCB
Defective remote controller
Transmission error caused by noise
Troubleshooting
For the way to change MAIN/SUB setting of remote controllers, refer to pages 148.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are both
remote controllers set to
MAIN?
Do(es) the
indoor unit service
monitor(s) blink?
Does
operation return to
normal when the power is
turned off
momentarily?
NO
NO
YES
YES
NO
Replace the indoor unit
PCB (control PCB).
Set 1 remote controller to
SUB; turn the power supply
off once and then back on.
When using both wired and
wireless remote controllers for
1 indoor unit, make sure to set
the wireless remote controller
to SUB.
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
There is possibility of
malfunction caused by noise.
Check the surrounding area
and turn on again.
Normal
Normal
NO
NO
Using
2 remote controllers
for 1 indoor unit?
YES
YES
YES
Replace the remote controller.
Return to normal?
Return to normal?
NO
Replace the indoor unit PCB.
YES
(R24590)

Troubleshooting for Indoor Unit SiUS092519E
94 Part 6 Service Diagnosis
Note
5.18 Signal Transmission Error (Between MAIN/SUB Remote
Controllers)
Error Code U8
Method of Error
Detection
In case of controlling 1 indoor unit with 2 remote controllers, check the system using
microcomputer if signal transmission between MAIN remote controller and SUB remote
controller is normal.
Error Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Remote controller is set to SUB when using 1 remote controller
Connection of 2 SUB remote controllers (when using 2 remote controllers)
Defective remote controller PCB
Troubleshooting
For the way to change MAIN/SUB setting of remote controllers, refer to pages 148.
Turn the power off and then
back on. If a malfunction occurs,
replace the remote controller.
Turn the power off and then
back on. If a malfunction occurs,
replace the remote controller.
Set one remote controller to
MAIN; turn the power supply off
once and then back on.
Set the remote controller to
MAIN; turn the power supply off
and then back on.
YES
NO
YES
NO NO
YES
(R24058)
Using 2 remote
controllers for 1
indoor unit?
Are both remote
controllers set to
SUB?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the
remote controller set to
MAIN?

SiUS092519E Troubleshooting for Indoor Unit
Part 6 Service Diagnosis 95
5.19 Unspecified Voltage (Between Indoor Unit and Outdoor
Unit)
Error Code UA
Error Decision
Conditions
Improper combination of indoor and outdoor units
Supposed
Causes
Defective indoor unit PCB
Indoor-outdoor unit transmission wiring error
Defective optional unit(s) wirings
Improper power supply wiring of indoor unit
Improper wiring of connecting wires between indoor/outdoor units
Troubleshooting
Connect the wirings correctly.
Replace the indoor unit PCB
(control PCB).
Normal
Connect the wirings correctly.
Check the power supply system
inside the indoor unit.
Could be incorrect wiring.
Check again.
YES
YES
NO
NO
Connect the indoor/outdoor
units correctly.
YES
YES
YES
YES
NO
NO
NO
Blink
(R24591)
Is the combination
of indoor/outdoor
units correct?
Do(es) the indoor
unit service monitor(s)
blink?
Are the wirings
between indoor unit and
outdoor unit correctly
connected?
Connect the wirings correctly.
NO
Is the optional
units power supply
connected from the
indoor unit terminal
block No.1 and
No.2?
Does the system conduct
normal operation?
Are the wirings
between indoor unit and
outdoor unit correctly
connected?
Turn off the power supply.
Then, turn on the power
supply to restart the system.
Continuously
ON or OFF
Is the voltage
between No.1 and
No.2 on the indoor
unit terminal block
208 - 230
VAC?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Troubleshooting for Indoor Unit SiUS092519E
96 Part 6 Service Diagnosis
5.20 Address Duplication of Centralized Controller
Error Code UC
Method of Error
Detection
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Error Decision
Conditions
The error decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Address duplication of centralized controller
Defective indoor unit PCB
Troubleshooting
R6001343
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Does the optional
remote controller for
centralized controller connect to
the indoor unit?
Address duplication on the
centralized controller. Change
the setting to avoid centralized
controller address duplication.
Replace the indoor unit PCB.
YES
NO

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 97
6. Troubleshooting for Outdoor Unit
6.1 Outdoor Unit PCB Abnormality
Error Code E1
Method of Error
Detection
The system checks if the microprocessor is working in order.
The system checks if the zero-cross signal comes in properly.
Error Decision
Conditions
The microprocessor program runs out of control.
The zero-cross signal is not detected.
Supposed
Causes
Defective outdoor unit PCB
Defective electronic expansion valve driver
Defective IGBT temperature detection thermistor circuit (15-24 class only)
Defective Fan IPM temperature detection thermistor circuit (15-24 class only)
Noise
Momentary drop of voltage
Momentary power failure
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Continuously ON, OFF
Blink
YES
(R24717)
NO
Replace the outdoor unit
PCB (main PCB).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (main PCB).
Check if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
Turn on the power again.

Troubleshooting for Outdoor Unit SiUS092519E
98 Part 6 Service Diagnosis
6.2 Actuation of High Pressure Switch
Error Code E3
Method of Error
Detection
Abnormality is detected when the contact of the high pressure switch opens.
Error Decision
Conditions
High pressure switch (S1PH) activating pressure: 4.15 MPa (602 psi)
High pressure switch (S1PH) recovery pressure: 3.2 MPa (464 psi)
Supposed
Causes
Actuation of high pressure switch (S1PH)
Closed stop valve
Disconnection of connector X40A or X820A
Disconnection of 2 terminals of high pressure switch (S1PH)
Defective outdoor unit PCB
Broken S1PH harness
Defective high pressure switch (S1PH)
Troubleshooting
R6001215
NO
YES
Nearly 0 :
Resistance f
Check
the resistance
between the pins 1 - 2
on the connector
X40A or
X820A.
Stop valve open?
Open the stop valve.
Nearly 0 :
Resistance f
Replace the harness for the high
pressure switch.
Replace the high pressure switch
(S1PH).
Disconnect the connector
X40A or
X820A from the PCB.
Replace the outdoor unit PCB
(main PCB).
Disconnect the 2 terminals of
the high pressure switch
(S1PH).
NO
YES
Reconnect the connector.
Check
the resistance
between the 2
terminals of the high
pressure switch
(S1PH).
High
pressure switch
connector X40A or X820A
properly connected?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 99
6.3 OL Activation (Compressor Overload)
Error Code E5
Method of Error
Detection
A compressor overload is detected through compressor OL.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of discharge pipe thermistor
Defective discharge pipe thermistor
Disconnection of connector X40A or X820A
Disconnection of 2 terminals of OL (Q1M)
Defective OL (Q1M)
Broken OL harness
Defective electronic expansion valve or coil
Defective four way valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve

Troubleshooting for Outdoor Unit SiUS092519E
100 Part 6 Service Diagnosis
Notes
Reference
Reference
Reference
Reference
Troubleshooting
R6001216
OL (Q1M) activating temperature: 120 ~ 130°C (248 ~ 266°F)
OL (Q1M) activating temperature: 110°C (230°F)
Check No.01 Refer to P.126
Check No.12 Refer to P.128
Check No.13 Refer to P.129
Check No.14 Refer to P.129
Caution
YES
NG
NO
OK
OK
NG
NG
OK
YES
NO
NG
OK
Refrigerant shortage
Water mixed
Stop valve
Disconnect the connector
X40A or X820A from the PCB.
Disconnect the 2 terminals of
the OL (Q1M).
Resistance
f
Resistance
f
Nearly 0 :
Nearly 0 :
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB (main PCB).
Discharge pipe
thermistor disconnected?
Check No. 01
Check the discharge pipe
thermistor.
Check No. 13
Check the four way valve.
Check No. 14
Check the refrigerant line.
Check No. 12
Check the electronic
expansion valve.
Replace the OL (Q1M).
Replace the OL harness.
Connect the connector
X40A or X820A properly.
Check the
resistance between the 2
terminals of the OL
(Q1M).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the
resistance between
the 2 terminals on connector
X40A or X820A.
Is the connector
X40A RUX820A properly
connected?

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 101
Reference
Reference
6.4 Compressor Lock
Error Code E6
Method of Error
Detection
A compressor lock is detected by the current waveform generated when applying
high-frequency voltage to the motor.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Closed stop valve
Compressor locked
Disconnection of compressor harness
Defective electronic expansion valve
Troubleshooting
Check No.12 Refer to P.128
Check No.15 Refer to P.130
Turn off the power. Disconnect the
harnesses U, V, and W.
(R21067)
Caution
NO
YES
YES
NO
NO
YES
NO
YES
Check No.15
Check with the inverter analyzer.
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Open the stop valve.
∗ Inverter analyzer:
RSUK0917C
Replace the compressor.
Replace the compressor.
Check the electronic
expansion valve coil.
Go to Check No. 12.
Any LED off?
Stop valve
closed?
Emergency stop
without compressor running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Troubleshooting for Outdoor Unit SiUS092519E
102 Part 6 Service Diagnosis
Reference
6.5 DC Fan Lock
Error Code E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in 15 ~ 30 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
R6001210
Check No.16 Refer to P.132
Caution
YES
YES
NO
YES
NO
NO
YES
NO
NO
Turn on the power.
Rotate the fan.
YES
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the fuse.
Replace the outdoor unit
PCB (main PCB).
Fan motor
connector disconnected?
Foreign matters
in or around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal
generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the fuse (#) for the
fan motor blown?
# FU2, F401U

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 103
Reference
Reference
Reference
6.6 Input Overcurrent Detection
Error Code E8
Method of Error
Detection
An input overcurrent is detected by checking the input current value with the compressor
running.
Error Decision
Conditions
The current exceeds about 12.0 ~ 20.0 A (depending on the model) for 2.5 seconds with the
compressor running.
The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
Supposed
Causes
Outdoor temperature is out of operation range.
Defective compressor
Defective power module
Defective outdoor unit PCB
Short circuit
Troubleshooting
Check No.15 Refer to P.130
Check No.17 Refer to P.132
Check No.18 Refer to P.133
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
* An input overcurrent may result from wrong internal wiring. If the system is interrupted by an input
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
(R21863)
NO
YES
YES
NO
Start operation and measure the
input current.
Check No. 18
Check the discharge pressure.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Any LED off?
Input current
flowing above its stop level?
* Inverter analyzer:
RSUK0917C

Troubleshooting for Outdoor Unit SiUS092519E
104 Part 6 Service Diagnosis
Reference
6.7 Electronic Expansion Valve Coil Abnormality
Error Code E9
Method of Error
Detection
Detect errors based on check of continuity of the electronic expansion valve.
Error Decision
Conditions
High input voltage from electronic expansion valve to the microcomputer due to overcurrent.
Low input voltage from electronic expansion valve to the microcomputer due to
disconnected connectors.
Supposed
Causes
Defective electronic expansion coil
Broken harness of electronic expansion coil
Defective connection of electronic expansion coil connector
Defective outdoor unit main PCB
Troubleshooting
R6001235
Check No.12 Refer to P.128
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
NO
YES
YES
Restart operation.
Turn OFF the power supply once
and turn ON again.
Check the connection of
connectors.
NO
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
Replace the electronic
expansion valve.
Replace the outdoor unit
PCB (PDLQ PCB).
Normal?
The cause can be external
factors other than malfunction.
Investigate the cause of noise.
E9 error again?
E9 error again?
Check No. 12
Is the coil resistance of
the electronic expansion
valve normal?
NO
YES
Correct the connection.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 105
6.8 Four Way Valve Abnormality
Error Code EA
Method of Error
Detection
The room temperature thermistor and the indoor heat exchanger thermistor are checked if they
function within their normal ranges in each operation mode.
Error Decision
Conditions
The following condition continues over C seconds after operating for 5 minutes.
Cooling/Dry
A – B < –5°C (A – B < –9°F)
Heating
B – A < –5°C (B – A < –9°F)
A: Room thermistor temperature
B: Indoor heat exchanger temperature
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor(s)
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Outdoor temperature
C (seconds)
09 class 12 class 15 class 18 class 24 class
–15°C (5°F) or higher 300 300 300 300 300
Lower than –15°C (5°F) 600 300 1400 1400 1400

Troubleshooting for Outdoor Unit SiUS092519E
106 Part 6 Service Diagnosis
Reference
Reference
Reference
Troubleshooting
R6001164
Check No.01 Refer to P.126
Check No.13 Refer to P.129
Check No.14 Refer to P.129
NG
OK
NO
OK
NG
OK
YES
NG
Correct the four way valve
coil.
Reconnect the harness.
YES
YES
YES
NO
NO
Replace the outdoor
unit PCB (main PCB).
Replace the defective
thermistor(s).
Refer to the refrigerant line
check procedure.
Replace the four way valve
(defective or dust-clogged).
Reconnect the
thermistor(s).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Refrigerant shortage
Water mixed
Stop valve
Four way valve
coil disconnected (loose)?
Harness
disconnected?
Any thermistor
disconnected?
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.
Check No. 13
Check the four way valve
switching output.
Check the continuity of the four way
valve coil and harness.
Replace the four way
valve coil.
NO
Resistance
between harnesses
about 556 ~ 614 :?
Disconnect the harness from the
connector.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 107
Reference
Reference
Reference
6.9 Discharge Pipe Temperature Control
Error Code F3
Method of Error
Detection
An error is determined with the temperature detected by the discharge pipe thermistor.
Error Decision
Conditions
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
stops.
The error is cleared when the discharge pipe temperature has dropped below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
If the frequency drops, the temperature is lowered in compensation.
Supposed
Causes
Defective discharge pipe thermistor
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Check No.01 Refer to P.126
Check No.12 Refer to P.128
Check No.14 Refer to P.129
A B
°C °F °C °F
09 class 110 230 88 190.4
12 class 118 244.4 79 174.2
15/18/24 class 118 244.4 85 185
(R20417)
Caution
NG
OK
OK
OK
NG
NG
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger thermistor
∗ Outdoor temperature thermistor
∗ Refrigerant shortage
∗ Four way valve
∗ Water mixed
∗ Stop valve
Check No. 12
Check the electronic
expansion valve.
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
Check No. 14
Check the refrigerant line.

Troubleshooting for Outdoor Unit SiUS092519E
108 Part 6 Service Diagnosis
6.10 High Pressure Control in Cooling
Error Code F6
Method of Error
Detection
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if
the temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Error Decision
Conditions
The temperature sensed by the outdoor heat exchanger thermistor rises above 60 ~ 62°C
(140 ~ 143.6°F) (depending on the model).
The error is cleared when the temperature drops below 48.5 ~ 52°C (119.3 ~ 125.6°F)
(depending on the model).
Supposed
Causes
Installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 109
Reference
Reference
Reference
Reference
Reference
Troubleshooting
Check No.01 Refer to P.126
Check No.12 Refer to P.128
Check No.17 Refer to P.132
Check No.18 Refer to P.133
Check No.19 Refer to P.133
(R20418)
Caution
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB (main PCB).
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Check the installation space.
NG
OK
OK
NG
NG
OK
OK
OK
NG
NG
Check No. 19
Check the outdoor fan.
Check No. 18
Check the discharge
pressure.
Check No. 12
Check the electronic
expansion valve.
Check No. 01
Check the outdoor heat
exchanger thermistor.
Check No. 17
Check the installation
condition.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Troubleshooting for Outdoor Unit SiUS092519E
110 Part 6 Service Diagnosis
Reference
6.11 System Shutdown due to Temperature Abnormality in
the Compressor
Error Code F8
Method of Error
Detection
Operation is halted when the temperature detected by the discharge pipe thermistor exceeds
the determined limit.
Error Decision
Conditions
Temperature exceeds the detection threshold of 127.5°C (261.5°F) during forced cooling
operation.
Supposed
Causes
Abnormal operation due to air intrusion
Defective discharge pipe thermistor
Troubleshooting
Check No.01 Refer to P.126
YES
(R23655)
NO
OK
NG
Caution
Replace the outdoor unit. #
Replace both the discharge pipe
thermistor and the outdoor unit
PCB (main PCB).
Replace the outdoor unit.
#
Abnormal
deformation of piping in the
outdoor unit
Check No. 01
Check the discharge pipe
thermistor
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
#
Replace the unit as directed in the installation manual, making sure that air does not intrude
into the refrigerant piping.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 111
6.12 Compressor Sensor System Abnormality
Error Code H0
Method of Error
Detection
The system checks the DC current before the compressor starts.
Error Decision
Conditions
The voltage converted from the DC current before compressor start-up is out of the range
0.5 ~ 4.5 V.
The DC voltage before compressor start-up is below 50 V.
Supposed
Causes
Broken or disconnected harness
Defective outdoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
(R24613)
YES
Turn off the power. Then, turn on
the power to restart the system.
YES
NO
Replace the harness.
Replace the outdoor unit
PCB (main PCB).
Is the harness broken?
Restart
operation and error displayed
again?
Check the (relay) harness for the
compressor.
Not a malfunction.
Keep observing.

Troubleshooting for Outdoor Unit SiUS092519E
112 Part 6 Service Diagnosis
Note(s)
6.13 High Pressure Switch System Abnormality
Error Code H3
Method of Error
Detection
The protection device circuit cheeks continuity in the high pressure switch.
Error Decision
Conditions
There is no continuity in the high pressure switch when the compressor stops operating.
Supposed
Causes
Defective high pressure switch
Defective connection of high pressure switch connector
Defective outdoor unit main PCB
Disconnected lead wire
Troubleshooting
R6001112
1. Connector and high pressure switch
Connect the connector
correctly.
Is high
pressure switch
connector (1) correctly
connected to outdoor unit
PCB?
Replace the outdoor unit
main PCB (A1P).
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Wait for 10 minutes after the unit
stops operating, then check the
following.
YES
Replace the high pressure
switch with no continuity.
Resistance in normal
operation: 10 : or less
Is there
continuity in each high
pressure switch?
NO
YES
Replace the lead wire.
Is there continuity in
lead wire?
NO
YES
High pressure switch Connector for high pressure switch Activation pressure
S1PH X40A or X820A 4.15 MPa (602 psi)

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 113
6.14 Position Sensor Abnormality
Error Code H6
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage outside the specified range

Troubleshooting for Outdoor Unit SiUS092519E
114 Part 6 Service Diagnosis
Reference
Reference
Troubleshooting
Check No.15 Refer to P.130
Check No.18 Refer to P.133
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the connection.
Check the power supply voltage.
Correct the power supply.
(R22764)
NO
NO
NO
NO
YES
YES
YES
YES
Check No. 20
Check the short circuit of the
diode bridge.
Check No.15
Check with the inverter analyzer.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power. Check the
electrolytic capacitor voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB (main PCB).
Inverter analyzer:
RSUK0917C
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
Within 320 VDC?
Any LED off?
+ 100
– 50
Is the
power supply
voltage fluctuation within
±10% from the rated
value?

Troubleshooting for Outdoor Unit SiUS092519E
116 Part 6 Service Diagnosis
Reference
Reference
6.15 Fan IPM temperature error
Applicable
Models
RXP15/18/24AVJU9
Error Code H7
Method of Error
Detection
A radiation fin temperature rise is detected by checking the radiation fin temperature with the
compressor on.
Error Decision
Conditions
The radiation fin temperature with the compressor on is above A.
The error is cleared when the temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
Troubleshooting
R6001182
Check No.17 Refer to P.132
Check No.19 Refer to P.133
°C °F
A 100 212
B 90 194
Caution
Turn off the power. Then, turn on
the power to restart the system.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NG
OK
NO
YES
YES
Check No. 19
Check the outdoor fan.
Error displayed
again?
Has the PCB
been replaced?
Check if silicone grease is
applied properly on the
radiation fin. If not, apply
the silicone grease.
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB (main PCB).
YES
NO
Radiation fin
dirty?
Clean up the radiation fin.
Check the installation
condition.
Go to Check No. 17.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 117
6.16 DC Voltage/Current Sensor Abnormality
Error Code H8
Method of Error
Detection
DC voltage or DC current sensor abnormality is identified based on the compressor running
frequency and the input current.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor unit PCB
Troubleshooting
Replace the outdoor unit PCB (main PCB).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Troubleshooting for Outdoor Unit SiUS092519E
118 Part 6 Service Diagnosis
6.17 Thermistor or Related Abnormality (Outdoor Unit)
Error Code H9, J3, J6, P4
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or
less with the power on.
J3 error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Supposed
Causes
Disconnection of the connector for the thermistor
Defective thermistor(s)
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting In case of P4
Replace the outdoor unit PCB (main PCB).
P4 : Radiation fin thermistor
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 119
Reference
Troubleshooting In case of H9, J3, J6
H9 : Outdoor temperature thermistor
J3 : Discharge pipe thermistor
J6 : Outdoor heat exchanger thermistor
Check No.01 Refer to P.126
(R20406)
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connectors
or thermistors.
J3 error: the discharge
pipe temperature is
lower than the heat
exchanger temperature.
Replace the defective
thermistor(s) of the following
thermistors.
∗ Outdoor temperature
thermistor
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger
thermistor
Cooling: Outdoor heat
exchanger
temperature
Heating: Indoor heat
exchanger
temperature
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
Error displayed
again on remote
controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Troubleshooting for Outdoor Unit SiUS092519E
120 Part 6 Service Diagnosis
Reference
Reference
6.18 Electrical Box Temperature Rise
Error Code L3
Method of Error
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Error Decision
Conditions
With the compressor off, the radiation fin temperature is above A.
The error is cleared when the radiation fin temperature drops below B.
To cool the electrical components, the outdoor fan starts when the radiation fin temperature
rises above C and stops when the radiation fin temperature drops below B.
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Troubleshooting
Check No.17 Refer to P.132
Check No.19 Refer to P.133
A B C
(°C) (°F) (°C) (°F) (°C) (°F)
09 class 82 179.6 65 149 70 158
12 class 90 194 75 167 81 177.8
15/18/24 class 100 212 70 158 77 170.6
Caution
WARNING
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C and stops when the radiation
fin temperature drops below B.
(R22998)
YES
NO
YES
NG
NO
OK
NO
YES
Turn off the power. Then, turn on
the power to restart the system.
Check the radiation fin
temperature.
Radiation fin dirty?
Check No. 19
Check the outdoor fan.
Error again or
outdoor fan activated?
Replace the outdoor unit
PCB (main PCB).
Clean up the radiation fin.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Above A?
Check the installation
condition.
Go to Check No. 17.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 121
Note
Reference
Reference
6.19 Radiation Fin Temperature Rise
Error Code L4
Method of Error
Detection
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
compressor on.
Error Decision
Conditions
If the radiation fin temperature with the compressor on is above A.
The error is cleared when the radiation fin temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
Troubleshooting
Refer to Silicone Grease on Power Transistor/Diode Bridge on page 152 for details.
Check No.17 Refer to P.132
Check No.19 Refer to P.133
A B
(°C) (°F) (°C) (°F)
09 class 99 210.2 70 158
12 class 90 194 84 183.2
15/18/24 class 95 203 85 185
Caution
Turn off the power. Then, turn on
the power to restart the system.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
(R23953)
NO
NG
OK
NO
YES
Check the radiation fin
temperature.
NO
YES
YES
Above A?
Check No. 19
Check the outdoor fan.
Error displayed
again?
Has the PCB
been replaced?
Check if silicone grease is
applied properly on the
radiation fin. If not, apply
the silicone grease.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB (main PCB).
YES
NO
Radiation fin
dirty?
Clean up the radiation fin.
Check the installation
condition.
Go to Check No. 17.

Troubleshooting for Outdoor Unit SiUS092519E
122 Part 6 Service Diagnosis
6.20 Output Overcurrent Detection
Error Code L5
Method of Error
Detection
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Error Decision
Conditions
A position signal error occurs while the compressor is running.
A rotation speed error occurs while the compressor is running.
An output overcurrent signal is fed from the output overcurrent detection circuit to the
microcomputer.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Poor installation condition
Closed stop valve
Defective power module
Wrong internal wiring
Abnormal power supply voltage
Defective outdoor unit PCB
Power supply voltage out of specification
Defective compressor
Troubleshooting
(R24911)
Caution
NO
YES
NO
YES
* An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output
overcurrent after the wires have been disconnected and reconnected for part replacement, check the
wiring again.
Check No. 17
Check No.15
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power. Then, turn on
the power to restart the system.
See if the same error occurs.
Monitor the power supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
* Momentary drop of power supply
voltage
* Compressor overload
* Short circuit
Check the installation condition.
Check with the inverter analyzer.
Not a malfunction.
Keep observing.
Check the connectors and
other components.
Fully open the stop valve.
Error again?
Stop valve fully open?
* Inverter analyzer:
RSUK0917C
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A Go to the next page

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 123
Reference
Reference
Reference
Reference
Check No.15 Refer to P.130
Check No.17 Refer to P.132
Check No.18 Refer to P.133
Check No.22 Refer to P.136
(R24912)
NO
YES
NO
YES
NO
YES
YES
NO
Check No. 22
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Check the power supply voltage.
Check the power module.
Correct the power supply.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB (main PCB).
Replace the outdoor unit
PCB (main PCB).
Any LED off?
Normal?
Short circuit
or wire breakage
between compressor's coil
phases?
Check the discharge
pressure.
Go to Check No. 18.
A Continued from the
previous page
Is the voltage
fluctuation within
±10% from the rated
value?

Troubleshooting for Outdoor Unit SiUS092519E
124 Part 6 Service Diagnosis
Reference
Reference
6.21 IGBT temperature error
Applicable
Models
RXP15/18/24AVJU9
Error Code LA
Method of Error
Detection
A radiation fin temperature rise is detected by checking the radiation fin temperature with the
compressor on.
Error Decision
Conditions
The radiation fin temperature with the compressor on is above A.
The error is cleared when the temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
Troubleshooting
R6001154
Check No.17 Refer to P.132
Check No.19 Refer to P.133
°C °F
A 90 194
B 85 185
Caution
Turn off the power. Then, turn on
the power to restart the system.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NG
OK
NO
YES
Check the IGBT temperature.
NO
YES
YES
Above A?
Check No. 19
Check the outdoor fan.
Error displayed
again?
Has the PCB
been replaced?
Check if silicone grease is
applied properly on the
radiation fin. If not, apply
the silicone grease.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB (main PCB).
YES
NO
Radiation fin
dirty?
Clean up the radiation fin.
Check the installation
condition.
Go to Check No. 17.

SiUS092519E Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis 125
6.22 Signal Transmission Error on Outdoor Unit PCB
Error Code U7
Method of Error
Detection
Communication error between microcomputer mounted on the main PCB and PM1.
Error Decision
Conditions
The abnormality is determined when the data sent from the PM1 cannot be received for 9
seconds.
The error counter is reset when the data from the PM1 can be successfully received.
Supposed
Causes
Defective outdoor unit PCB
Troubleshooting
(R21808)
Caution
YES
NO
Turn off the power. Then, turn on
the power to restart the system.
Error again?
The cause can be an
external factor other than
the malfunction.
Observe the operating
condition in long term.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Replace the outdoor unit
PCB (main PCB).

Check SiUS092519E
126 Part 6 Service Diagnosis
Note(s)
7. Check
7.1 Thermistor Resistance Check
Check No.01 Measure the resistance of each thermistor using multimeter.
The resistance values are defined by below table.
If the measured resistance value does not match the listed value, the thermistor must be
replaced.
Disconnect the connector of thermistor ASSY from the PCB to measure the resistance
between the pins using multimeter.
To check the thermistor soldered on a PCB, disconnect the PCB from other PCB/parts, and
measure the resistance between the both ends of soldered thermistor.
R6001195
When replacing the defective thermistor(s), replace the thermistor as ASSY.
Multimeter
Resistance range
Thermistor ASSY Soldered thermistor
Multimeter
R(25°C / 77°F) = 20 k:, B = 3950 K
Thermistor
temperature
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
R(25°C / 77°F) = 20 k:
B = 3950 K
Resistance (k:)
197.8
148.2
112.1
85.60
65.93
51.14
39.99
31.52
25.02
20.00
16.10
13.04
10.62
8.707
7.17650
–4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
°C °F
(˚C)
(k:)
–15
0
15 30
45
150
100
50
(˚F)
5 32 59 86 113

SiUS092519E Check
Part 6 Service Diagnosis 127
7.2 Indoor Fan Motor Connector Check
Check No.02 1. Turn the power supply OFF.
2. With the fan motor connector disconnected, measure the resistance between each pin, then
make sure that the resistance is more than the value mentioned in the following table.
7.3 Power Supply Waveform Check
Check No.11 Measure the power supply waveform between No. 1 and No. 2 on the terminal strip, and check
the waveform disturbance.
Check if the power supply waveform is a sine wave (Fig.1).
Check if there is waveform disturbance near the zero-cross (sections circled in Fig.2).
Measuring points Judgement
White - Blue 1 MΩ or more
Orange - Blue 100 kΩ or more
Brown - Blue 100 Ω or more
Red - Blue 100 kΩ or more
White
Orange
Brown
Blue
—
—
Red
FG
Vsp
Vcc
GND
—
—
Vdc/Vm
X8A
(R25080)
[Fig.1] [Fig.2]
(R1736)
(R1444)

Check SiUS092519E
128 Part 6 Service Diagnosis
7.4 Electronic Expansion Valve Check
Check No.12 Conduct the following to check the electronic expansion valve (EV).
1. Check if the EV connector is correctly connected to the PCB.
2. Turn the power off and on again, and check if the EV generates a latching sound.
3. If the EV does not generate a latching sound in step 2, disconnect the connector and check
the continuity using a multimeter.
4. Check the continuity between the pins 5 - 1, 5 - 2, 5 - 3, 5 - 4. If there is no continuity
between the pins, the EV coil is faulty.
5. If the continuity is confirmed in step 3, the outdoor unit PCB (main PCB) is faulty.
R6000952 R6001211
Harness 5P
5P Connector
Check
X700A
5 - 1
5 - 2
5 - 3
5 - 4
1 2 3 4 5
Harness 5P
5P Connector
Check
X21A
5 - 1
5 - 2
5 - 3
5 - 4
1 2 3 4 5

SiUS092519E Check
Part 6 Service Diagnosis 129
7.5 Four Way Valve Performance Check
Check No.13
R6001212
7.6 Inverter Unit Refrigerant System Check
Check No.14
R6000874
Start heating operation.
NO
YES
YES
Four way valve
coil resistance at
556 ~ 614 :?
NO
Turn off the power and turn it on
again.
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the four way valve
coil.
Replace the four way valve.
NO
YES
X80A or X800A
voltage at 0 VDC with
compressor on?
X80A or
X800A voltage at
120 ~ 380 VDC for 3 sec.
after compressor starts, and
then at about 10
VDC? (Fig. 1)
Disconnect the four way valve coil
from the connector and check the
continuity.
(Fig. 1)
Voltage at X80A or X800A
120 ~ 380 VDC
10 VDC
Time
Compressor
ON
3 sec.
< Caution on resetting the power supply >
Be sure to wait for 30 sec. or more after turning off the power.
Four way valve coil
Cooling / Dry : No continuity
Heating : Continuity
Refrigerant system check
Is the discharge pipe
thermistor disconnected from
the holder?
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (U0).
YES
NO
Reconnect the thermistor.
Replace the refrigerant.

Check SiUS092519E
130 Part 6 Service Diagnosis
Note
7.7 Inverter Analyzer Check
Check No.15 Characteristics
Inverter analyzer: RSUK0917C
If an abnormal stop occurs due to compressor startup failure or overcurrent output when using
an inverter unit, it is difficult to judge whether the stop is caused by the compressor failure or
some other failure (main PCB, power module, etc.). The inverter analyzer makes it possible to
judge the cause of trouble easily and securely. Connect an inverter analyzer as a
quasi-compressor instead of compressor and check the output of the inverter.
Operation Method
Step 1
Be sure to turn the power off.
Step 2
Install an inverter analyzer instead of a compressor.
Note:
Make sure the charged voltage of the built-in smoothing electrolytic capacitor drops to 10 VDC
or below before carrying out the service work.
Reference:
If the terminals of the compressor are not FASTON terminals (difficult to remove the wire on the
terminals), it is possible to connect wires available on site to the outdoor unit from output side of
PCB. Do not connect them to the compressor at the same time, otherwise it may result in
incorrect detection.
Step 3
Activate the power transistor test operation from the outdoor unit.
Power transistor test operation can be activated only once after turning on the power supply.
If reactivation of the power supply transistor operation is needed, turn the power supply off and
then on again.
(
R22731
)
(1) Remove the terminals from
the compressor.
(2) Connect the terminals to the
terminals of the inverter
analyzer.
Compressor
Inverter analyzer
Be careful not to let the terminals (U,V,W)
touch each other. Otherwise, high voltage
is applied.
Compressor

SiUS092519E Check
Part 6 Service Diagnosis 131
Caution
Diagnose method (Diagnose according to 6 LEDs lighting status.)
1. If all the LEDs are lit uniformly, the compressor is defective.
Replace the compressor.
2. If the LEDs are not lit uniformly, check the power module.
Refer to Check No.22.
3. If NG in Check No.22, replace the power module.
(Replace the main PCB. The power module (IPM1) is united with the main PCB.)
If OK in Check No.22, check if there is any solder cracking on the PCB.
4. If any solder cracking is found, replace the PCB or repair the soldered section.
If there is no solder cracking, replace the PCB.
1. When the output frequency is low, the LEDs blink slowly. As the output frequency increases,
the LEDs blink quicker. (The LEDs look like they are lit.)
2. On completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, the terminals may be burned due to loosening.
Wired Remote Controller (BRC1NRV71)
1. Turn the power on.
2. Set FAN operation using the remote controller.
3. Press and hold Cancel button for 4 seconds or
longer.
• Test operation will stop automatically after
about 30 minutes.
To stop the operation, press On/Off button.
4. Select Test Operation in the service settings
menu, then press Menu/OK button.
Basic screen returns and “Test Operation”
is displayed at the bottom.
5. Press On/Off button within 10 seconds.
3 minutes after pressing On/Off button,
power transistor test operation will start.
Basic screen
2.
3.
4.
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Press Menu/OK button.
5.
Fan
Test Operation
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit
Press On/Off button
(within 10 seconds).
(R15292)
Direction of crimp
FASTON terminal
This size is shortened
by the crimp.

Check SiUS092519E
132 Part 6 Service Diagnosis
7.8 Outdoor Fan Motor Check
Check No.16 Outdoor fan motor
Check if the sinusoidal voltage is generated between pins 1 - 3 and 3 - 5 when the fan motor is
manually rotated once.
7.9 Installation Condition Check
Check No.17
■ 09/12 class ■ 15/18/24 class
R6001180 R6001127
5
3
1 Phase U
Phase V
Phase W
X70A
PCB
5
3
1 Phase U
Phase V
Phase W
X200A
PCB
Installation condition check
OK
Check the allowable
dimensions of the air
suction and
discharge area.
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
(R19394)
NG
YES
YES
NO
Is the discharged air
short-circuited?
NO
NO
YES
Is the outdoor heat
exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be within the operation
range.)

SiUS092519E Check
Part 6 Service Diagnosis 133
7.10 Discharge Pressure Check
Check No.18
7.11 Outdoor Fan System Check
Check No.19 DC motor
(R21121)
YES
YES
YES
NO
NO
NO
NO
YES
Is the air filter or
indoor/outdoor heat
exchanger dirty?
Is the
connection pipe deformed?
Is the stop valve
open?
High?
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty air filter or
indoor/outdoor heat exchanger.
Replace the compressor.
Discharge pressure check
(R21195)
YES
NO
NO
YES
Outdoor fan system is functioning.
Check the outdoor fan system.
Reconnect the connector.
Is
the outdoor fan
running?
Fan motor lead
wire connector
disconnected?
Go to Check No. 16.

Check SiUS092519E
134 Part 6 Service Diagnosis
7.12 Main Circuit Short Check
Check No.20 Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about
0 V before checking
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is or less than 1 k, short circuit occurs on the main circuit.
09/12 class
R6001208
Positive terminal (+) of
digital multimeter
~ (2, 3) + (4) ~ (2, 3) – (1)
Negative terminal (–) of
digital multimeter
+ (4) ~ (2, 3) – (1) ~ (2, 3)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
Multimeter
–
+
123
4
–~~+

SiUS092519E Check
Part 6 Service Diagnosis 135
15/18/24 class
R6001213
1234
Multimeter
–
~~+
–
+

Check SiUS092519E
136 Part 6 Service Diagnosis
7.13 Power Module Check
Check No.22 Check to make sure that the voltage between (+) and (–) of the power module is about 0 V
before checking.
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the terminals of the power
module and the terminals of the compressor with a multimeter. Evaluate the measurement
results referring to the following table.
09/12 class
R6001209
Positive terminal (+) of
digital multimeter
Power module
(+)
UVW
Power module
(–)
UVW
Negative terminal (–) of
digital multimeter
UVW
Power module
(+)
UVW
Power module
(–)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
Pin 27: +
Pin 26: U
Pin 25: V
Pin 24: W
Pin 23: –

SiUS092519E Check
Part 6 Service Diagnosis 137
15/18/24 class
R6001214
DC+
W
V
U
DC–

SiUS092519E
138 Part 7 Trial Operation and Field Settings
1. Pump Down Operation........................................................................139
2. Forced Cooling Operation ...................................................................140
3. Trial Operation ....................................................................................141
4. Field Settings ......................................................................................143
4.1 How to Change the Field Settings........................................................143
4.2 Overview of Field Settings....................................................................145
4.3 MAIN/SUB Setting when Using 2 Wired Remote Controllers...............148
5. Field Settings for Outdoor Unit............................................................149
5.1 Facility Setting (cooling at low outdoor temperature) ...........................149
5.2 Warmer Airflow Setting.........................................................................150
5.3 Drain Pan Heater..................................................................................151
6. Silicone Grease on Power Transistor/Diode Bridge............................152
Part 7
Trial Operation and
Field Settings

SiUS092519E Pump Down Operation
Part 7 Trial Operation and Field Settings 139
Reference
1. Pump Down Operation
Outline In order to protect the environment, be sure to conduct pump down operation when relocating or
disposing of the unit.
Details 1. Remove the valve caps from the liquid stop valve and the gas stop valve.
2. Carry out forced cooling operation.
3. After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4. After 2 to 3 minutes, close the gas stop valve and stop the forced cooling operation.
5. Attach the valve cap once procedures are complete.
Refer to Forced Cooling Operation on page 140 for details.
Gas stop valve
Valve cap
Close
Liquid stop valve
Service port
(R13628)
Hexagonal
wrench

Forced Cooling Operation SiUS092519E
140 Part 7 Trial Operation and Field Settings
2. Forced Cooling Operation
R7000500
With Wired Remote Controller (BRC1NRV71)
1. Set to COOL or HEAT operation using
the remote controller.
2. Press and hold Cancel button for 4 seconds
or longer. Service settings menu is
displayed.
3. Select in the service
settings menu, and press Menu/OK button.
Basic screen returns and “Test Operation”
is displayed at the bottom.
4. Press On/Off button within 10 seconds, and
the forced cooling operation starts.
Forced cooling operation will stop
automatically after about 15 minutes.
To stop the operation, press On/Off button.
Test Operation
Basic screen
1.
2.
3.
4.
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).

SiUS092519E Trial Operation
Part 7 Trial Operation and Field Settings 141
3. Trial Operation
Outline Trial operation should be carried out in either cooling or heating operation.
1. Measure the supply voltage and make sure that it is within the specified range.
2. In cooling operation, select the lowest programmable temperature;
in heating operation, select the highest programmable temperature.
3. Carry out the trial operation following the instructions in the operation manual to ensure that
all functions and parts, such as the movement of the flaps, are working properly.
To protect the air conditioner, restart operation is disabled for 3 minutes after the system
has been turned off.
4. After trial operation is complete, set the temperature to a normal level (26°C to 28°C (78°F to
82°F) in cooling operation, 20°C to 24°C (68°F to 75°F) in heating operation).
Procedure When operating the air conditioner in cooling operation in winter, or heating operation in
summer, set it to the trial operation mode using the following method.
R7000501
With Wired Remote Controller (BRC1NRV71)
1. Set to COOL or HEAT operation using the
remote controller.
2. Press and hold Cancel button for 4 seconds
or longer. Service settings menu is
displayed.
3. In the case of a model having airflow
direction function, select
in the service settings menu, and press
Menu/OK button. Basic screen returns and
“Test Operation” is displayed at the bottom.
4. Press On/Off button within 10 seconds, and
the test operation starts.
Monitor the operation of the indoor unit for a
minimum of 10 minutes. During test
operation, the indoor unit will continue to
cool/heat regardless of the temperature
setpoint and room temperature.
In the case of above-mentioned
procedures 3 and 4 in reverse order, test
operation can start as well.
5. Press and hold Cancel button for 4 seconds
or longer in the basic screen.
Service settings menu is displayed.
6. Select in the service
settings menu, and press Menu/OK button.
Basic screen returns and normal operation
is conducted.
Test operation will stop automatically
after 15 ~ 30 minutes. To stop the
operation, press On/Off button.
Test Operation
Test Operation
Basic screen
1.
2.
3.
4.
5.
6.
Basic screen
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.

Trial Operation SiUS092519E
142 Part 7 Trial Operation and Field Settings
Test Items
Test items Symptoms
Indoor and outdoor units are installed securely. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/heating
function
Refrigerant gas and liquid pipes and indoor drain hose
extension are thermally insulated.
Water leakage
Draining line is properly installed. Water leakage
The power supply voltage corresponds to that shown on the
name plate.
No operation or burn damage
System is properly grounded. Electrical leakage
Only specified wires are used for all wiring, and all wires are
connected correctly.
No operation or burn damage
Indoor or outdoor unit's air inlet or air outlet are
unobstructed.
Incomplete cooling/heating
function
Refrigerant piping length and additional refrigerant charge
are noted down.
The refrigerant charge in the
system is not clear
Pipes and wires are connected to the corresponding
connection ports / terminal blocks for the connected unit.
No cooling/heating
Stop valves are opened. Incomplete cooling/heating
function
The external static pressure is set correctly. Incomplete cooling/heating
function or water leakage

SiUS092519E Field Settings
Part 7 Trial Operation and Field Settings 143
Note
4. Field Settings
4.1 How to Change the Field Settings
Outline If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
When using 2 remote controllers for 1 indoor unit, change the field settings from MAIN remote
controller. Note that the field settings cannot be set from SUB remote controller.
Procedure BRC1NRV71 Wired Remote Controller
a Unit No.
b First code No.
c Second code No.
d Mode
a
b
c
d
(R18831)
1. Press and hold Cancel button for 4 seconds or longer.
Service settings menu is displayed.
2. Select in the Service Settings menu, and press Menu/OK button.
Field settings screen is displayed.
<Basic screen>
1
Fan
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Field Settings
<Service settings menu screen>
2
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
Press Menu/OK button.

Field Settings SiUS092519E
144 Part 7 Trial Operation and Field Settings
Highlight the mode, and select desired “Mode No.” by using (Up/Down) button.
In the case of setting per indoor unit during group control (When Mode No. such as , ,
, are selected), highlight the unit No. and select “Indoor unit No.” to be set by using
(Up/Down) button. (In the case of group setting, this operation is not needed.)
In the case of individual setting per indoor unit, current settings are displayed. And, SECOND
CODE NO. “ - ” means no function.
Highlight SECOND CODE NO. of the FIRST CODE NO. to be changed, and select desired
“SECOND CODE NO.” by using
(Up/Down) button. Multiple identical mode number
settings are available.
In the case of setting for all indoor units in the remote control group, available SECOND CODE
NO. is displayed as “ ” which means it can be changed. When SECOND CODE NO. is
displayed as “ - ”, there is no function.
Press Menu/OK button. Setting confirmation screen is displayed.
Select and press Menu/OK button. Setting details are determined and field settings screen
returns.
In the case of multiple setting changes, repeat 3 to 7.
After all setting changes are completed, press Cancel button twice.
0.Backlight goes out, and [Checking the connection. Please stand by.] is displayed for
initialization. After the initialization, the basic screen returns.
20 22
23 25
<Service settings screen>
3
4
5
0
–
–
–
–
3
5
0
SECOND CODE NO.
In the case of individual
setting per indoor unit
In the case of group total
setting
Field Settings
Unit No Mode
20
Setting
0
4
8
12
01 1 01
–––
–––
–––
–––
–––
–––
–––
––––––
–––
–––
–––
5
9
13
2
6
10
14
02
301
7
11
15
–
1
–––
–––
–––
5
9
13
–
–––
–––
–––
2
6
10
14
–
–––
–––
–––
3
7
11
15
–
0
4
8
12
01
–––
–––
–––
Unit No Mode
10
Field Settings
Setting
FIRST CODE (SW) NO.
Press Menu/OK button.
Yes
<Setting confirmation screen>
6
7
No
Setting confirmation
Field Settings
Save the settings?
Yes
Setting
Press Menu/OK button.

SiUS092519E Field Settings
Part 7 Trial Operation and Field Settings 145
Note(s)
4.2 Overview of Field Settings
Factory Setting
Do not use any settings not listed in the table.
For group control, refer to the installation manual attached to the indoor unit for group
control.
4.2.1 Remote Controller Thermistor
Select a thermistor to control the room temperature.
When the unit is not equipped with an infrared floor sensor:
Factory Setting
When the Second Code No. is set to 01, room temperature is controlled by the suction air
thermistor and remote controller thermistor. When the Second Code No. is set to 02, room
temperature is controlled by the suction air thermistor. When the Second Code No. is set to 03,
room temperature is controlled by the remote controller thermistor.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01 02 03 04 05 06
10
(20)
0
Filter cleaning
sign interval
(used to change
filter cleaning
display interval
according to filter
contamination)
Longlife
filter
Light
Approx.
2,500
hrs.
Heavy
Approx.
1,250
hrs.
— — — —
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
— — — —
2 Remote controller thermistor Refer to the table below.
3
Filter cleaning sign (used to
set filter cleaning display ON/
OFF)
Display No display — — — —
6
Remote controller thermistor
control during group control
Not
permitted
Permitted — — — —
11
(21)
7
Air volume adjustment
OFF
Air volume
adjustment
completion
Air volume
adjustment
start
— — —
8
Room temperature adjustment
(Cooling)
Refer to the table below.
9
Room temperature adjustment
(Heating)
Refer to the table below.
13
(23)
6
External static pressure
Refer to the table below.
15
(25)
13 Refrigerant leak sensor setting Disabled Enabled — — — —
14
Refrigerant leak sensor
replacement Normal
Completion
of
replacement
— — — —
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20) 2
01 Remote controller thermistor and suction air thermistor
02
Suction air thermistor only
03 Remote controller thermistor only

Field Settings SiUS092519E
146 Part 7 Trial Operation and Field Settings
Room temperature adjustment (Cooling/Heating)
Factory Setting
Mode
No.
First
Code
No.
Second Code No. Adjustment temperature
11
(21)
8.9
1 –3.5°C (–6.3°F)
2 –3.0°C (–5.4°F)
3 –2.5°C (–4.5°F)
4 –2.0°C (–3.6°F)
5 –1.5°C (–2.7°F)
6 –1.0°C (–1.8°F)
7 –0.5°C (–0.9°F)
8 0.0°C (0.0°F)
9 +0.5°C (+0.9°F)
10 +1.0°C (+1.8°F)
11 +1.5°C (+2.7°F)
12 +2.0°C (+3.6°F)
13 +2.5°C (+4.5°F)
14 +3.0°C (+5.4°F)
15 +3.5°C (+6.3°F)
20
22
24
26
28
30
32
34
36
211917 23 25 27 29 31 33 35 37 (°C)
(°C)
68
71.6
75.2
78.8
82.4
86
89.6
93.2
96.8
(°F)
66.262.6 69.8 73.4 77 80.6 84.2 87.8 91.4 95 98.6 (°F)
In cooling
Suction air temperature
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Remote controller
thermistor
Remote controller
thermistor
Set temperature
(°C)
14
16
18
20
22
24
26
28
30
32
(°C)
57.2
60.8
64.4
68
71.6
75.2
78.8
82.4
86
89.6
(°F)
14 16 18 20 22 24 26 28 30 32 34
(°F)57.2 60.8 64.4 68 71.6 75.2 78.8 82.4 86 89.6 93.2
In heating
Suction air temperature
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Suction air
thermistor
Remote controller
thermistor
Remote controller
thermistor
Set temperature

SiUS092519E Field Settings
Part 7 Trial Operation and Field Settings 147
External Static Pressure Settings
Factory Setting
4.2.2 Refrigerant Leak Sensor Setting
This is used when safety measures for refrigerant leak activated by the sensor is not required by
the local and national codes based on the installation conditions such as refrigerant charge and
room area.
: Factory setting
4.2.3 Refrigerant Leak Sensor Replacement
After completion of replacement with a new sensor, change the Second Code No. to 02 to clear
the error message on the remote controller. A reset of the power supply is also required to
enable the setting.
: Factory setting
Mode
No.
First
Code
No.
Second Code No.
External static pressure
09/12
Class
15/18/24
Class
13
(23)
6
03
—
30 Pa (0.12 inH
2
O)
04
—
40 Pa (0.16 inH
2
O)
05 05 50 Pa (0.20 inH
2
O)
06 06 60 Pa (0.24 inH
2
O)
07 07 70 Pa (0.28 inH
2
O)
08 08 80 Pa (0.32 inH
2
O)
09 09 90 Pa (0.36 inH
2
O)
10 10 100 Pa (0.40 inH
2
O)
11 11 110 Pa (0.44 inH
2
O)
12 12 120 Pa (0.48 inH
2
O)
13 13 130 Pa (0.52 inH
2
O)
14 14 140 Pa (0.56 inH
2
O)
15 15 150 Pa (0.60 inH
2
O)
Mode
No.
First Code
No.
Second
Code No.
Contents
15 (25) 13
01 Disabled
02
Enabled
Mode
No.
First Code
No.
Second
Code No.
Contents
15 (25) 14
01
Normal
02 Completion of replacement

Field Settings SiUS092519E
148 Part 7 Trial Operation and Field Settings
4.3 MAIN/SUB Setting when Using 2 Wired Remote
Controllers
Outline The MAIN/SUB setting is necessary when 1 indoor unit is controlled by 2 remote controllers.
When you use 2 remote controllers, set one to MAIN and the other to SUB.
Details 1. The following message is displayed after power-on.
Checking the connection.
Please stand by.
When the above message is displayed, the backlight will not be ON.
[In the case that 1 indoor unit is controlled by 2 remote controllers:]
Make sure to set the sub remote controller when the above message is displayed.
Hold Mode button for 4 seconds or longer to set.
When the display is changed from “Main RC” to “Sub RC”, the setting is completed.
2. Basic screen is displayed.
<Sub remote controller>
1 1
<Basic screen>
2
<Basic screen>
2
Set temperature
Fan
Set temperature
Fan
<Main remote controller>
Off reminder Timer
Checking the connection.
Please stand by.
Main RC
Off reminder Timer
Checking the connection.
Please stand by.
Main RC
Error Code U5
Checking the connection.
Please stand by.
Main RC
Error Code U5
Checking the connection.
Please stand by.
Main RC
28°C
Return Press the menu button
Press and hold 4 seconds
or longer Mode Selection
button of sub remote
Off reminder Timer
Checking the connection.
Please stand by.
Sub RC
28°C
Return Press the menu button

SiUS092519E Field Settings for Outdoor Unit
Part 7 Trial Operation and Field Settings 149
Reference
Caution
5. Field Settings for Outdoor Unit
5.1 Facility Setting (cooling at low outdoor temperature)
Outline This function is limited only for facilities (the target of air conditioning is equipment such as
computers). Never use it in a residence or office (the space where there is a human).
Details 09/12 class
Cutting the Jumper 7 (J7) on the circuit board will expand the operation range down to 14°F
(–10°C). Installing an air direction adjustment grille (sold separately) will further extend the
operation range to –4°F (–20°C). In these cases, the unit will stop operating if the outdoor
temperature falls below –4°F (–20°C), restarting once the temperature rises above this level.
(1) Remove the top plate of the outdoor unit. (4 screws)
(2) Remove the front plate. (5 screws)
(3) Cut the Jumper 7 (J7) of the PCB inside.
R7000502
15/18/24 class
Cutting jumper 7 (J7) on the PCB will extend the operation range to 14°F (–10°C). Installing
an air direction adjustment grille (sold separately) will further extend the operation range to
–4°F (–20°C). In these cases, the unit will stop operating if the outdoor temperature falls
below –4°F (–20°C), restarting once the temperature rises above this level.
(1) Remove the top plate of the outdoor unit. (6 screws)
(2) Remove the front plate. (10 screws)
(3) Remove the anti-drip cover.
(4) Cut the jumper (J7) of the PCB inside.
R7000456
For the location of the jumper, refer to pages 23, 24.
If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
provide a windbreak wall.
Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
Cut jumper (J7).
J12
J8
J7
J5
J9
Cut jumper J7.
J12
J8
J7
J5
J9
J4

Field Settings for Outdoor Unit SiUS092519E
150 Part 7 Trial Operation and Field Settings
Caution
Reference
Note(s)
Activating the facility setting sets the indoor fan tap to the highest position. Notify the user
about this.
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
5.2 Warmer Airflow Setting
Outline The temperature of discharge airflow in heating operation can be adjusted warmer.
The room temperature will be high when getting close to the set temperature.
The discharge airflow does not become warmer in other than heating operation.
Procedure Warmer airflow can be enabled/disabled from remote controller or outdoor unit.
Cut the jumper (J5) of the PCB inside.
09/12 class
R7000503
15/18/24 class
R7000458
For the location of the jumper, refer to page 23, 24.
Warmer airflow can be enabled from either indoor or outdoor unit.
Warmer airflow becomes available when either one of the RC or outdoor unit setting is enabled.
For example, if the outdoor unit has the switch for warmer airflow, it can be set even when it is
disabled on the indoor unit.
Also, for the wireless remote controller with field setting function, warmer airflow is enabled
when set on indoor unit with the remote controller field setting, even when it is disabled on
outdoor unit.
Cut jumper (J5).
J12
J8
J7
J5
J9
Cut jumper J5.
J12
J8
J7
J5
J9
J4

SiUS092519E Field Settings for Outdoor Unit
Part 7 Trial Operation and Field Settings 151
Reference
5.3 Drain Pan Heater
In high humidity areas or heavy snow areas, it is recommended to attach a drain pan
heater to prevent ice build-up from the bottom frame.
1. Attach the drain pan heater in accordance with the installation manual included with the
drain pan heater.
2. Cut the jumper (J9) of the PCB inside.
09/12 class
R7000504
15/18/24 class
R7000460
For the location of the jumper, refer to page 23, 24.
Cut jumper (J9).
J12
J8
J7
J5
J9
Cut jumper J9.
J12
J8
J7
J5
J9
J4

Silicone Grease on Power Transistor/Diode Bridge SiUS092519E
152 Part 7 Trial Operation and Field Settings
6. Silicone Grease on Power Transistor/Diode
Bridge
Outline Apply the specified silicone grease to the heat generation part of a power transistor/diode bridge
when you replace an outdoor unit PCB. The silicone grease encourages the heat dissipation of
a power transistor/diode bridge.
Details 1. Wipe off the old silicone grease completely.
2. Apply the silicone grease evenly. See the illustrations below for examples of application.
3. Tighten the screws of the power transistor/diode bridge.
4. Make sure that the heat generation parts are firmly contacted to the radiation fin.
Note: Smoke emission may be caused by bad heat radiation when the silicone grease is not
appropriately applied.
OK: Evenly applied
NG: Not evenly applied
NG: Foreign matter is stuck.
(R22541)
Power transistor
(or diode bridge)
Silicone grease
Radiation
fin
PCB
(R21866)
Foreign matter
(R21867)

SiUS092519E
Part 8 Appendix 153
1. Piping Diagrams..................................................................................154
1.1 Indoor Unit............................................................................................154
1.2 Outdoor Unit .........................................................................................154
2. Wiring Diagrams..................................................................................156
2.1 Indoor Unit............................................................................................156
2.2 Outdoor Unit .........................................................................................157
3. Operation Limit....................................................................................159
Part 8
Appendix

Piping Diagrams SiUS092519E
154 Part 8 Appendix
1. Piping Diagrams
1.1 Indoor Unit
FDMA09/12/15/18/24AVJU9
1.2 Outdoor Unit
RXP09/12AVJU9
C: 4D112974C
FDMA09
•
12
FDMA15
•
18
FDMA24
1/4 (6.4)
MODEL
1/4 (6.4)
1/4 (6.4)
3/8 (9.5)
1/2 (12.7)
5/8 (15.9)
3D150947

SiUS092519E Piping Diagrams
Part 8 Appendix 155
RXP15/18AVJU9
RXP24AVJU9
3D150095
3D150096

SiUS092519E Operation Limit
Part 8 Appendix 159
3. Operation Limit
RXP09/12/15/18/24AVJU9
3D158354

Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
©
All rights reserved
Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorized importer, distributor and/or retailer whether this
product conforms to the applicable standards, and is suitable for use, in the region where the product
will be used. This statement does not purport to exclude, restrict or modify the application of any local
legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
Specifications, designs and other content appearing in this brochure are current as of October 2025 but subject to change without notice.
SiUS092519E
10/2025 AK.K