Mrcool HAH060FEA ProDirect 3rd Gen 60K BTU, 5 Ton, ECM Air Handler

Product's Documents

Below are documents related to this product, you can read online or download:
Installation Instruction Specification
HAH060FEA photo

Installation Manual

This is the main product document for model HAH060FEA. Additionally, the document applies to other Mrcool models: 840255585781, HAH060FEA, PSC MOTOR

The file format is pdf, 22 pages, you can download this manual here .

background
PRODIRECT™ Series
ECM Air Handler
Installation &
Owner’s Manual
MODELS:
Read this manual carefully before installation and keep it where
the operator can easily nd it for future reference.
Due to updates and constantly improving performance, the
information and instructions within this manual are subject to
change without notice.
Version Date: 09/26/2024
Please visit www.mrcool.com/documentation
to ensure you have the latest version of this manual.
HAH024FEA
HAH036FEA
HAH060FEA
background
mrcool.com1
CONTENTS
SAFETY PRECAUTIONS ..................................................................................................... 2
UNIT OVERVIEW ................................................................................................................ 3
2.1 Location Selection ............................................................................................... 3
2.2 Unit Dimensions .................................................................................................. 5
INSTALLATION .................................................................................................................. 6
3.1 Vertical Upow .................................................................................................... 6
3.2 Vertical Downow ............................................................................................... 6
3.3 Horizontal ............................................................................................................. 6
3.4 Installation in an Unconditioned Space ............................................................ 8
ELECTRICAL WIRING ......................................................................................................... 8
4.1 Power Wiring ........................................................................................................ 8
4.2 Control Wiring ...................................................................................................... 8
4.3 Grounding ............................................................................................................. 9
4.4 Electrical Data ...................................................................................................... 9
4.5 Electric Kit MCA/MOP Data ................................................................................. 9
AIRFLOW PERFORMANCE .............................................................................................. 10
DUCTWORK ..................................................................................................................... 13
REFRIGERANT CONNECTIONS....................................................................................... 14
7.1 Condensate Drain Tubing ................................................................................. 14
AIR FILTER ....................................................................................................................... 15
WIRING DIAGRAMS ........................................................................................................ 17
PISTON/TXV INSTALLATION .......................................................................................... 20
1
2
3
4
5
Contents
8
6
7
9
8
background
mrcool.com 2 2
Incorrect usage may cause serious damage or injury.
The symbols below are used throughout this manual to indicate instructions that should be
followed closely or actions that should be avoided to prevent death, injury, and/or property
damage.
Safety Precautions
CAUTION
Indicates the possibility of personal injury or loss of life.
Indicates the possibility of property damage or serious
consequences.
Read Before Using
WARNING
WARNING
1. These instructions are intended as an aid to qualied licensed service personnel for proper installation,
adjustment, and operation of this unit. Read these instructions thoroughly before attempting installation
or operation. Failure to follow these instructions may result in improper installation, adjustment, service, or
maintenance possibly resulting in re, electrical shock, property damage, personal injury, or death.
2. This appliance is not intended for use by persons (including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person responsible for their safety.
3. Children should be supervised to ensure that they do not play with the appliance.
4. This unit can't be used outdoors.
5. Because of possible damage to equipment or personal injury, installation, service, and maintenance should
be performed by a trained, qualied service personnel. Consumer service is recommended only for lter
cleaning/replacement. Never operate the unit with the access panels removed.
6. The rst 6 inches of supply air plenum and ductwork must be constructed of sheet metal as required by
NFPA 90B. The supply air plenum or duct must have a solid sheet metal bottom directly under the unit
with no openings, registers or exible air ducts located in it. If exible supply air ducts are used, they may
be located only in the vertical walls of rectangular plenum, a minimum of 6 inches from the solid bottom.
Metal plenum of duct may be connected to the combustible oor base, if not, it must be connected to the
unit supply duct exposed to the supply air opening from the downow unit. Exposing combustible (non-
metal) material to the supply opening of a downow unit can cause a re resulting in property damage,
personal injury or death.
7. Exception warning to downow: Installations on concrete oor slab with supply air plenum and ductwork
completely encased must be not less than 2 inches of concrete (See NFPA 90A).
SAFETY
1
ELECTRICAL WARNINGS
1. Disconnect power to the unit before installing or servicing. More than one disconnect switch may be
required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death.
2. If removal of the blower assembly is required, all disconnect switches supplying power to the equipment
must be de-energized and locked (if not in sight of unit) so the eld power wires can be safely removed
from the blower assembly. Failure to do so can cause electrical shock resulting in personal injury or death.
3. The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal
injury or death.
background
mrcool.com3
UNIT OVERVIEW
2
WARNING: PROPOSITION 65
• This appliance contains berglass insulation. Respirable particles of berglass are known to the state of
California to cause cancer.
• All manufacturer products meet current federal OSHA Guidelines for safety. California Proposition 65 warnings
are not required for certain products, which are not covered by the OSHA standards.
• California's Proposition 65 requires warnings for products sold in California that contain or produce any of
over 600 listed chemicals known to the state of California to cause cancer or birth defects such as berglass
insulation, lead in brass, and combustion products from natural vapor.
• All "new equipment" shipped for sale in California will have labels stating that the product contains and/or
produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all
our products facilitates manufacturing and shipping. We cannot always know when or if products will be sold in
the California market.
• You may receive inquiries from customers about chemicals found in, or produced by, some of our heating
and air conditioning equipment, or found in natural vapor used with some of our products. The following
are those chemicals and substances commonly associated with similar equipment in our industry and other
manufacturers: glass wool (berglass) insulation, carbon monoxide (CO), formaldehyde, benzene
• More details are available on the following websites: www.osha.gov and www.oehha.org
• Consumer education is important since the chemicals and substances on the list are found in our daily lives.
Most consumers are aware that products present safety and health risks, when improperly used, handled, and
maintained.
2.1 Location Selection
The unit can be positioned for bottom return air in the upow position, left and right return in the horizontal
position, top return in downow position.
This Air Handler provides the exibility for installation in any upow or downow horizontal application. The
direct drive motors provide a selection of air volume to match any application. 3-Speed motors provide selections
of air ow to meet desired applications.
Top and side power and control wiring, accessible screw terminals for control wiring all combine to make the
installation easy, and minimize installation cost.
Do not install unit in an area where ammable materials are present due to the risk of an explosion resulting in
serious injury or death.
The unit should be installed in a level position to ensure proper condensation drainage. Up to an additional 1/4"
rise over the width or depth of the unit is allowed to create additional sloping towards the drain. The unit must be
positioned between level and 1/4" rise, sloping toward the drain connections.
Install the indoor and outdoor unit, power supply wiring and connecting wires at least 3.5 ft. away from televisions
or radios in order to prevent image interference or noise.
background
mrcool.com 4
4
WARNING
If the supporting structural members are not strong enough to support the unit's weight, the unit could fall out
of place and cause serious injury.
If a return-air duct is not installed, carefully select the place and method of product installation so that airow
into the product will not be blocked.
When the unit is installed in a hot and humid place, if the humidity inside the installation space might exceed 86°F
(30°C) and RH 80%, it is recommended to insulate the cabinet exterior.
Use glass wood or polyethylene foam as insulation so that the thickness is more than 2 in. and ts inside the
installation space opening.
Respectively, condensation may form on the surface of the insulation.
Be sure to use insulation that is designed for use with HVAC Systems.
Condensation may form on the product during cool operation.
It is also recommended to use the second drain pan and secure the unit rmly to prevent it from falling.
UNIT OVERVIEW
2
background
mrcool.com5
UNIT OVERVIEW
2
2.2 Unit Dimensions
Unit Dimensions
Model
Height
(in. [mm])
Width
(in. [mm])
Length
(in. [mm])
Supply Duct "A"
Unit Weight
(lbs. [kg])
24 41-3/8" [1050] 18-1/8 [460] 20-1/2 [520] 16" [406] 99 [45]
36 46-1/2" [1180] 19-5/8" [500] 21-5/8" [550] 18" [456] 121 [55]
60 54-1/2" [1385] 22" [560] 24" [610] 19-1/2" [496] 152 [69]
background
mrcool.com 6
6
INSTALLATION
3
3.1 Vertical Upow
Vertical Upow conguration is the default factory
setting on all models.
If return air is to be ducted, install the duct ush with
the oor. Use a reproof resilient gasket 1/8 to 1/4 in.
thick between the ducts, unit, and oor. Set the unit on
the oor over the opening.
Torque applied to drain connections should not
exceed 15ft.lbs.
3.2 Vertical Downow
Conversion to Vertical Downow: A vertical upow
unit may be converted to vertical downow. Remove
the door and indoor coil and reinstall 180° from original
position.
IMPORTANT: To comply with certication agencies and
the National Electric Code for downow application, the
circuit breaker(s) on eld-installed electric heater kits
must be re-installed per procedure below so that the
breaker switch's "on" position and marking is up and its
"o" position and marking is down.
• To rotate breaker(s): rotate one breaker set (circuit)
at a time starting with the one on the right. Loosen
both lugs on the load side of the breaker. (Make
sure that wires are identied and are reinstalled
into the proper breaker.) Wires are bundled with
wire ties, one bundle going to the right lug and one
bundle going to the left lug.
• Using a screwdriver or pencil, lift the white plastic
tab with hole away from the breaker until the
breaker releases from the mounting opening.
• With breaker held in hand, rotate the breaker so
that its "on" position is up, and its "o" position is
down with the unit in its planned vertical mounting
position. Insert right wire bundle into the top right
breaker lug, ensuring all strands of all wires are
inserted fully into the lug, and no wire insulation is
in the lug.
• Tighten lug as tight as possible while holding the
circuit breaker. Check the wires and ensure each
wire is secure and none are loose. Repeat for left
wire bundle in the left top circuit breaker lug.
• Replace breaker by inserting breaker mounting tab
opposite the white pull tab in the opening. Hook the
mounting tab over the edge in the opening.
• With a screwdriver or pencil, pull the blue tab with
hole away from the breaker while placing that side
of the breaker into the opening. When breaker is in
place, release the tab, locking the circuit breaker into
place in the opening.
• Repeat above operation for remaining breaker(s) (if
more than one is provided).
• Replace the single point wiring jumper bar, if it is
used, on the line side of the breaker and tighten it
securely.
• Double-check all wires and lugs to make sure all are
secure and tight. Check to make sure the unit wiring
and circuit breaker load lugs match what is shown
on the unit wiring diagram.
CAUTION
When using the unit with an electrical heater, the
switch is used only for the electrical heater on the
front of the panel.
3.3 Horizontal
Horizontal right is the default factory conguration for
the units.
Horizontal left is not the default factory conguration
for the units.
Conversion to Horizontal left: A vertical upow unit may
be converted to horizontal left by removing the indoor
coil assembly and reinstalling the coil as shown for a
left-hand air supply.
• Rotate the unit into the downow position, with
the coil compartment on top and the blower
compartment on bottom.
• Reinstall the indoor coil 180° from its original
position. Ensure the retaining channel is fully
engaged with the coil rail.
• Secondary drain pan kits are recommended when
the unit is congured for the horizontal position
over a nished ceiling and/or living space.
background
mrcool.com7
INSTALLATION
3
background
mrcool.com 8
8
CAUTION
Horizontal units must be congured for right hand air
supply or left hand air supply. Horizontal drain pan
must be located under indoor coil. Failure to use the
drain pan can result in property damage.
Conversion in Horizontal Direction: A unit with a
horizontal right-hand supply can be changed to a
horizontal left-hand supply by removing the indoor coil
and reinstalling 180° from the original orientation.
3.4 Installation in an Unconditioned Space
IMPORTANT: There are two pairs of coil rails in the air handler for default and counter-ow application. If the air
handler is installed in an unconditioned space, the two unused coil rails should be removed to minimize sweating
on the air handler's surface. The coil rails can be easily removed by taking o the 6 mounting screws from both
sides of the cabinet.
ELECTRICAL WIRING
4
4 - Electrical Wiring
WARNING
Disconnect all power to the unit before performing any installation or service. More than one disconnect switch
may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death.
Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any applicable local
ordinance.
4.1 Power Wiring
It is important that proper electrical power is available
for connection to the unit model being installed. See
the unit nameplate, wiring diagram, and electrical data
in the installation instructions.
• If required, install a branch circuit disconnect of
adequate size, located within sight of, and readily
available to the unit.
• IMPORTANT: After the Electric Heater is installed,
units may be equipped with one, two, or three 30-
60 amp. circuit breakers. These breaker(s) protect
internal wiring in the event of a short circuit and serve
as a disconnect. Circuit breakers installed within the
unit do not provide over-current protection of the
supply wiring and therefore may be sized larger
than the branch circuit protection.
• Supply circuit power wiring must be 75°C minimum
copper conductors only. See Electrical Data in this
section for ampacity, wire size, and circuit protector
requirement. Supply circuit protective devices may
be either fuses or "HACR" type circuit breakers.
• Power wiring may be connected to either the right
side, left side, or top. Three 7/8", 1-3/8", 1-3/4" dia.
concentric knockouts are provided for connection
of power wiring to unit.
• Power wiring is connected to the power terminal
block in the unit's electrical cabinet.
4.2 Control Wiring
IMPORTANT: Class 2 low voltage control wiring should
not be run in conduit with main power wiring and must
be separated from power wiring, unless class 1 wire of
proper voltage rating is used.
• Low voltage control wiring should be 18 AWG color-
coded. For lengths longer than 100ft., 16 AWG wire
should be used.
• Low voltage control connections are made to low
voltage pigtails extending from the top of the air
handler.
• Connections for control wiring are made with wire
nuts. Control wiring knockouts (5/8" & 7/8") are also
provided on the right and left side of the unit for a
side connection.
• See wiring diagrams attached to indoor and outdoor
sections to be connected.
• Make sure, after installation, separation of control
wiring and power wiring has been maintained.
background
mrcool.com9
ELECTRICAL WIRING
4
4.3 Grounding
WARNING
The unit must
be permanently
grounded. Failure
to do so can result
in electrical shock
causing personal
injury or death.
• Grounding may be accomplished by grounding metal conduit when installed in
accordance with electrical codes to the unit cabinet.
• Grounding may also be accomplished by attaching the ground wire(s) to the ground
lug(s) provided in the unit wiring compartment.
• Ground lug(s) are located close to the wire entrance on the left side of the unit (upow).
Lug(s) may be moved to marked locations near the wire entrance on the right side of the
unit (upow), if an alternate location is more convenient.
• Use of multiple supply circuits require grounding of each circuit to the lug(s) provided in
the unit.
Model Voltage Hertz HP Speeds Circuit Amps. Maximum Circuit Protector
24 208/230 60 1/3 5 2.6 15(A)
36 208/230 60 1/2 5 3.0 15(A)
60 208/230 60 3/4 5 4.5 15(A)
4.4 Electrical Data
4.5 Electric Kit MCA/MOP Data
Heater Kit
Model Used
Air Handler
Model
Electric
Heat (kW)
Minimum Circuit Ampacity Max. Fuse or Breaker (HACR) Ampacity
Fan Speed (AC/HP)
240V 208V 240V 208V 1 2 3 4 5
HHK-05
24
5 29 25.5 30 30
HHK-08 7.5 42 36.8 45 40 X X
HHK-10 10 55 48.1 60 50 X X
HHK-05
36
5 29.4 25.9 30 30
HHK-08 7.5 42.4 37.2 45 40 X
HHK-10 10 55.4 48.5 60 50 X X
HHK-15 15 55.4/26.1 48.5/22.6 60/30 50/25 X X
HHK-20 20 55.4/52.1 48.5/45.2 60/60 60/50 X X X
HHK-05
60
5 31.8 28.3 35 30 X X
HHK-08 7.5 44.8 39.6 45 40 X X
HHK-10 10 57.8 50.9 60 60 X X
HHK-15 15 57.8/26.1 50.9/22.6 60/30 60/25 X X
HHK-20 20 57.8/52.1 50.9/45.2 60/60 60/50 X X X
• Heat pump systems require a specied air ow. Each ton of
cooling requires between 350 and 450 cubic feet of air per
minute (CFM), or 400 CFM nominally.
• Heat kit suitable for AHU 4-way installation.
• Ampacities for MCA and Fuse/breaker including the blower motor.
No. Kit Description Ref. Air Handler Use
1 HHK-05 5kW Heat Strip 24/36/60
2 HHK-08 7.5kW Heat Strip 24/36/60
3 HHK-10 10kW Heat Strip 24/36/60
4 HHK-15 15kW Heat Strip, double breaker panel 36/60
5 HHK-20 20kW Heat Strip, double breaker panel 36/60
Electric Heater Kits
background
mrcool.com 10
10
AIRFLOW PERFORMANCE
5
Airow performance data is based on cooling performance with a coil and no lter in place. Select performance
table for appropriate unit size.
External static applied to unit allows operation within the minimum and maximum limits shown in the table below
for both cooling and electric heat operation.
Airow Performance Data
Air Handler
Model Size
Outdoor
Unit Size
(Tons)
Motor
Speed
CFM Wet Coil Without Filter and Electric Heat
External Static Pressure-Inches W.C. [kPa]
0[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]
24 1.5
1
SCFM 590 544 511 447 404 345 311 273 239
Power/W 49 57 64 70 75 82 91 97 102
Current/A 0.77 0.81 0.84 0.87 0.91 0.94 0.99 1.02 1.11
2
SCFM 681 633 591 535 490 446 388 354 313
Power/W 63 69 77 83 90 96 103 111 118
Current/A 0.84 0.87 0.93 0.96 0.99 1.03 1.07 1.13 1.16
3
(Recommended)
SCFM 788 736 687 648 597 558 511 473 429
Power/W 86 91 100 108 114 121 128 133 142
Current/A 0.95 0.99 1.11 1.14 1.18 1.21 1.26 1.31 1.37
4
(Factory
Default)
SCFM 883 842 796 758 717 681 642 599 524
Power/W 121 128 135 144 151 159 165 173 181
Current/A 1.21 1.28 1.32 1.38 1.43 1.47 1.54 1.59 1.64
5
SCFM 1103 1073 1036 998 967 934 896 855 814
Power/W 233 241 249 259 265 275 281 286 291
Current/A 1.97 2.03 2.09 2.16 2.22 2.29 2.34 2.37 2.41
24 2
1
CFM 590 54 511 447 404 345 311 273 239
Power/W 49 57 64 70 75 82 91 97 102
Current/A 0.77 0.81 0.84 0.87 0.91 0.94 0.99 1.02 1.11
2
CFM 681 633 591 535 490 446 388 354 313
Power/W 63 69 77 83 90 96 103 111 118
Current/A 0.84 0.87 0.93 0.96 0.99 1.03 1.07 1.13 1.16
3
CFM 788 736 687 648 597 558 511 473 429
Power/W 86 91 100 108 114 121 128 133 142
Current/A 0.95 0.99 1.11 1.14 1.18 1.21 1.26 1.31 1.37
4
(Factory
Default)
CFM 883 842 796 758 717 681 642 599 524
Power/W 121 128 135 144 151 159 165 173 181
Current/A 1.21 1.28 1.32 1.38 1.43 1.47 1.54 1.59 1.64
5
CFM 1103 1073 1036 988 967 934 896 855 814
Power/W 233 241 249 258 265 275 281 286 291
Current/A 1.97 2.03 2.09 2.16 2.22 2.29 2.34 2.37 2.41
5 - Airow Performance
background
mrcool.com11
AIRFLOW PERFORMANCE
5
Air Handler
Model Size
Outdoor
Unit Size
(Tons)
Motor
Speed
CFM Wet Coil Without Filter and Electric Heat
External Static Pressure-Inches W.C. [kPa]
0[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]
36 2.5
1
SCFM 898 752 603 511 405 360 301 259 203
Power/W 78 72 65 60 54 48 41 38 36
Current/A 0.68 0.64 0.59 0.52 0.46 0.42 0.36 0.29 0.28
2
SCFM 1026 902 810 694 630 544 490 406 366
Power/W 109 99 106 111 120 126 135 140 148
Current/A 0.94 0.86 0.91 0.95 1.03 1.07 1.14 1.18 1.24
3
SCFM 1161 1114 1052 992 893 825 768 694 646
Power/W 148 158 164 175 187 193 203 209 219
Current/A 1.26 1.34 1.39 1.48 1.57 1.61 1.69 1.73 1.81
4
(Recommended)
SCFM 1287 1244 1186 1142 1078 969 914 892 893
Power/W 194 205 211 221 233 241 252 253 253
Current/A 1.62 1.69 1.75 1.83 1.93 1.98 2.07 2.08 2.11
5
(Factory
Default)
SCFM 1491 1442 1396 1348 1302 1243 1150 1088 1029
Power/W 290 298 307 318 325 337 351 362 367
Current/A 2.35 2.42 2.49 2.58 2.64 2.73 2.83 2.92 2.96
36 3
1
SCFM 898 752 603 511 405 360 301 259 203
Power/W 78 72 65 60 54 48 41 38 36
Current/A 0.68 0.64 0.59 0.52 0.46 0.42 0.36 0.29 0.28
2
SCFM 1026 902 810 694 630 544 490 409 366
Power/W 109 99 106 111 120 126 135 140 148
Current/A 0.94 0.86 0.91 0.95 1.03 1.07 1.14 1.18 1.24
3
SCFM 1161 1114 1052 992 893 825 768 694 646
Power/W 148 158 164 175 187 193 203 209 219
Current/A 1.26 1.34 1.39 1.48 1.57 1.61 1.69 1.73 1.81
4
SCFM 1287 1244 1186 1142 1078 969 914 892 893
Power/W 194 205 211 221 233 241 252 253 253
Current/A 1.62 1.69 1.75 1.83 1.93 1.98 2.07 2.08 2.11
5
(Factory
Default)
SCFM 1491 1442 1396 1348 1302 1243 1150 1088 1029
Power/W 290 298 307 318 325 337 351 362 367
Current/A 2.35 2.42 2.49 2.58 2.64 2.73 2.83 2.92 2.96
60 3.5
1
SCFM 1344 1284 1226 1151 1076 946 904 893 869
Power/W 143 151 159 168 177 191 197 195 194
Current/A 1.23 1.26 1.33 1.41 1.5 1.61 1.63 1.61 1.62
1.62
SCFM 1531 1477 1418 1366 1299 1239 1138 1064 1001
Power/W 200 211 222 231 239 250 266 277 291
Current/A 1.73 1.74 1.81 1.89 2.02 2.14 2.22 2.31 2.38
3
(Recommended)
SCFM 1647 1592 1538 1490 1436 1378 1315 1215 1140
Power/W 244 254 263 273 283 300 305 325 336
Current/A 2.03 2.11 2.14 2.19 2.31 2.38 2.53 2.64 2.72
4
(Factory
Default)
SCFM 1875 1822 1774 1729 1677 1629 1581 1533 1473
Power/W 340 353 365 375 388 399 412 423 437
Current/A 2.73 2.79 2.86 3.02 3.12 3.21 3.29 2.38 3.51
5
SCFM 2021 1967 1924 1879 1828 1785 1742 1694 1641
Power/W 409 416 429 447 461 471 487 500 513
Current/A 3.21 3.29 3.38 3.52 3.61 3.73 3.766 3.86 4.04
background
mrcool.com 12
12
AIRFLOW PERFORMANCE
5
-- Shaded boxes represent airow outside the required 300-450 cfm/ton, which are not recommended.
• Airow based on cooling performance at 230V with no electric heat and no lter.
• Airow at 208V is approximately the same as 230V because the multi-tap ECM motor is a constant torque motor. The torque doesn't drop o at the
speeds at which the motor operates.
• The air distribution system has the greatest eect on airow. The duct system is totally controlled by the contractor. For this reason, the contractor
should use only industry-recognized procedures.
• Heat pump systems require a specied airow for electric heating to operate. Each ton of cooling requires between 350 and 450 cubic feet of air per
minute (CFM), or 400 CFM nominally.
• Duct design and construction should be carefully completed. System performance can be lowered dramatically through bad planning or workmanship.
• Air supply diusers must be selected and located carefully. They must be sized and positioned to deliver treated air along the perimeter of the space. If
they are too small for their intended airow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly
sized to carry air back to the blower. If they are too small, they also cause noise.
• The installers should balance the air distribution system to ensure proper quiet airow to all rooms in the home. This ensures a comfortable living space.
• An air velocity meter or airow hood can be used to balance and verify branch and system airow (CFM).
Air Handler
Model Size
Outdoor
Unit Size
(Tons)
Motor
Speed
CFM Wet Coil Without Filter and Electric Heat
External Static Pressure-Inches W.C. [kPa]
0[0] 0.1[.025] 0.2[.050] 0.3[.075] 0.4[0.100] 0.5[0.125] 0.6[0.150] 0.7[0.175] 0.8[0.200]
60 4
1
SCFM 1344 1284 1226 1151 1076 976 904 893 869
Power/W 143 151 159 168 177 191 197 195 194
Current/A 1.23 1.26 1.33 1.41 1.5 1.61 1.63 1.61 1.62
2
SCFM 1531 1477 1418 1366 1299 1239 1138 1064 1001
Power/W 200 211 222 231 239 250 266 277 291
Current/A 1.73 1.74 1.81 1.89 2.02 2.14 2.22 2.31 2.38
3
(Recommended)
SCFM 1647 1592 1538 1490 1436 1378 1315 1215 1140
Power/W 244 254 263 273 283 300 305 325 336
Current/A 2.03 2.11 2.14 2.19 2.31 2.38 2.53 2.64 2.72
4
(Factory
Default)
SCFM 1875 1822 1774 1729 1677 1629 1581 1533 1473
Power/W 340 353 365 375 388 399 412 423 437
Current/A 2.73 2.79 2.86 3.02 3.12 3.21 3.29 2.38 3.51
5
SCFM 2021 1967 1924 1879 1828 1785 1742 1694 1641
Power/W 409 416 429 447 461 471 487 500 513
Current/A 3.21 3.29 3.38 3.52 3.61 3.73 3.76 3.86 4.04
60 5
1
SCFM 1344 1284 1226 1151 1076 946 904 893 869
Power/W 143 151 159 168 177 191 197 195 194
Current/A 1.23 1.26 1.33 1.41 1.5 1.61 1.63 1.61 1.62
2
SCFM 1531 1477 1417 1366 1299 1239 1138 1064 1001
Power/W 200 211 222 231 239 250 266 277 291
Current/A 1.73 1.74 1.81 1.89 2.02 2.14 2.22 2.31 2.38
3
SCFM 1647 1592 1538 1490 1436 1378 1315 1215 1140
Power/W 244 254 263 23 283 300 305 325 336
Current/A 2.03 2.11 2.15 2.19 2.31 2.38 2.53 2.64 2.72
4
(Factory
Default)
SCFM 1875 1822 1774 1729 1677 1629 1581 1533 1473
Power/W 340 353 365 375 388 399 412 423 437
Current/A 2.73 2.79 2.86 3 3.12 3.21 3.29 2.38 3.51
5
SCFM 2021 1967 1924 1879 1828 1785 1742 1694 1641
Power/W 409 416 429 447 461 471 487 500 513
Current/A 3.21 3.29 3.38 3.52 3.61 3.73 3.76 3.86 4.04
background
mrcool.com13
DUCTWORK
6
Field ductwork must comply with the National Fire Protection Association NFPA 90A, NFPA90B, and any applicable
local ordinance.
WARNING
• Do not, under any circumstances, connect return ductwork to any other heat producing device such as a
replace insert, stove, etc.
• Unauthorized use of such devices may result in re, carbon monoxide poisoning, explosion, personal
injury, or property damage.
Sheet metal ductwork in unconditioned spaces must be insulated and covered with a vapor barrier. Fibrous
ductwork may be used if constructed and installed in accordance with SMACNA Construction Standard on Fibrous
Glass Ducts. Ductwork must comply with National Fire Protection Association as tested by UL Standard 181 for
Class I Air Ducts. Check local codes for requirements on ductwork and insulation.
• The duct system must be designed within the range of external static pressure that the unit is designed to
operate against. It is important that the system has adequate airow. Make sure all supply and return ductwork,
grills, special lters, accessories, etc. are accounted for in total resistance. See airow performance tables in
this manual.
• Design the duct system in accordance with "ACCA" Manual "D" Design for Residential Winter and Summer Air
Conditioning Equipment Selection. Latest editions are available from: "ACCA" Air Conditioning Contractors of
America, 1513 16th Street, N.W., Washington, D.C. 20036. If duct system incorporates exible air duct, be sure
pressure drop information (straight length plus all turns) shown in "ACCA" Manual "D" is accounted for in the
system.
• Supply plenum is attached to the 3/4" duct anges supplied with the unit. Attach anges around the blower
outlet.
IMPORTANT: If an elbow is included in the plenum close to the unit, it cannot be smaller than the dimensions of
the supply duct ange on the unit.
IMPORTANT: The front ange on the return duct if connected to the blower casing must not be screwed into the
area where the power wiring is located. Drills or sharp screw points can damage insulation on wires located inside
the unit.
• Secure the supply and return air ductwork to the unit anges, using proper fasteners for the type of duct used
and tape the duct-to-unit joint as required to prevent air leaks.
6 - Ductwork
background
mrcool.com 14
14
REFRIGERANT CONNECTIONS
7
Keep the coil connections sealed until refrigerant
connections are made. See the installation instructions
for the outdoor unit for details on the line sizing, tubing
installation, and charging information.
Coil is shipped with nitrogen. Evacuate the system
before charging with refrigerant.
Install refrigerant tubing so that it does not block service
access to the front of the unit.
Nitrogen should ow through the refrigerant lines
while brazing.
Use a brazing shield to protect the cabinet's paint and a
wet rag to protect the rubber grommet and input pipe's
piston seal ring from being damaged by torch ames.
After the refrigerant connections are made, seal the
gap around the connections with a pressure sensitive
gasket.
After the work is nished, make sure to check that there
is no vapor leak. After checking for vapor leaks, be sure
to insulate the piping connections.
WARNING
Use a wet rag to protect the two seal rings in the
input pipe from being damaged by torch ames
while brazing.
7.1 Condensate Drain Tubing
Consult local codes for specic requirements.
IMPORTANT:
1. When making drain tting connections to the drain
pan, use a thin layer of Teon paste, silicone, or Teon
tape and install. Hand tighten.
2. When making drain tting connections to the drain
pan, do not over-tighten. Over-tightening ttings can
split the pipe connections on the drain pan.
• Install drain lines so they do not block service access
to the front of the unit. Minimum clearance of 24
inches is requires for lter, coil, or blower removal
and service access.
• Make sure the unit is level or pitched slightly toward
the primary drain connection so that water will drain
completely from the pan.
• Do not reduce drain line size less than the connection
size provided on the condensate drain pan. Use 3/4"
PVC piping for drain piping connections.
• All drain lines must be pitched downward away from
the unit a minimum of 1/8" per foot of line to ensure
proper drainage.
7 - Refrigerant Connections
background
mrcool.com15
AIR FILTER
8
• Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an open drain or run
the line to a safe outdoor area.
• The drain line should be insulated where necessary to prevent sweating and damage due to condensate
forming on the outside surface of the line.
• Make provisions for disconnecting and cleaning of the primary drain line, should it become necessary. Install a
3 inch trap in the primary drain line as close to the unit as possible. Make sure that the top of the trap is below
the connection to the drain pan to allow complete drainage of the pan.
• The auxiliary drain line should be run to a place where it will be noticeable if it becomes operational. The
homeowner should be warned that a problem exists if water should begin running from the auxiliary drain
line.
• Plug the unused drain connection with the plugs provided in the parts bag, using a thin layer of Teon paste,
silicone, or Teon tape to form a water tight seal.
• Test condensate drain pan and drain line after installation is complete. Pour water into the drain pan, enough
to ll the drain trap and line. Check to make sure the drain pan is draining completely, no leaks are found in
the drain line ttings, and water is draining from the termination of the primary drain line.
• Be sure to insulate the drain piping and drain socket since condensation may cause water leakage.
• Be sure to install a drain trap at the drain outlet since the inside of the unit is at negative pressure to atmospheric
pressure during operation.
External lter or other means of ltration is required. Units should be sized for a maximum of 300 feet/min air
velocity or what is recommended for the type of lter installed.
Filter application and placement are critical to airow, which may aect the heating and cooling system performance.
Reduced airow can shorten the life of the system's major components, such as motor, limits, elements, heat
relays, evaporator coil or compressor. Consequently, we recommend that the return air duct system have only
one lter location. Systems with a return air lter grill or multiple lter grills can have a lter installed at each of
the return air openings.
If adding high eciency lters or electronic air ltration systems, it is very important that the air ow is not
reduced. If air ow is reduced, the overall performance and eciency of the unit will also be reduced. It is strongly
recommended that a professional installation technician is contacted to ensure installation of these such ltration
systems is performed correctly.
IMPORTANT: Do not double lter the return air duct system. Do not lter the supply air duct system. This will
change the performance of the unit and reduce airow.
WARNING
Do not operate the system without lters. A portion of the dust entrained in the air may temporarily lodge in
the duct and run at the supply registers. Any circulated dust particles could be heated and charred by contact
with the air handler elements. This residue could soil ceilings, walls, drapes, carpets, and other articles in the
house.
Soot damage may occur with lters in place, when certain types of candles, oil lamps, or standing pilots are
burned.
8 - Air Filter
background
mrcool.com 16
16
Filter Installation Dimensions
Model
Filter Size
in (mm)
"W"
in (mm)
"D"
in (mm)
"H"
in (mm)
Return Width "A"
in (mm)
Return Length "B"
in (mm)
24K 16X20 [406X508] 16.8[426] 20.4[518] 1[25.4] 19.6 14.8
36K 18X20[457X508] 18.3[466] 21.6[548] 1[25.4] 20.8 16.3
60K 20X22[508X559] 20.7[526] 23.9[608] 1[25.4] 23 18.8
Air Filter Removal
1. Remove the bolts manually, and remove the air lter cover.
2. Hold the edge of the air lter and extract out.
3. Clean the air lter (A vacuum cleaner or plain water may be used to clean the air lter. If the dust accumulation
is too heavy, use a soft brush and mild detergent to clean it and allow it to dry in a cool place.)
4. Install the new lter so that the arrow on the lter is in the same direction as airow.
AIR FILTER
8
background
mrcool.com17
WIRING DIAGRAMS
9
9 - Wiring Diagrams
background
mrcool.com 18
18
WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES
MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.
WIRING DIAGRAMS
9
background
mrcool.com19
Note: When the unit does not contain PCB boards, the short lines in the accessory bag are not needed.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up to date wiring.
WIRING DIAGRAM
9
background
mrcool.com 20
20
PISTON/TXV INSTALLATION
10
The coil comes with a factory-installed piston metering device. Some system combinations will require a dierent
sized piston to be eld-installed.
• Contact MRCOOL support at 270-366-0457 to order the appropriate piston kit for your system combination.
A TXV may be required to achieve minimum eciency ratings or for long refrigerant line set applications. Reference
AHRI for system combination ratings.
The following table shows the factory-installed piston size for each model. Additional piston sizes are provided
with the included accessories as necessary.
Model 50 52 56 58 64 73 75 80 83 90
24K X* X
36K X X X X*
60K X X X X*
* means that this piston is pre-installed
WARNING
Failure to install the proper piston can lead to poor
system performance and possible compressor damage.
The following table shows the optional TXV kit part numbers. Some combinations may require a TXV. See AHRI for
system combination ratings.
Outdoor Unit Capacity (Tons) R410a TXV Kit
1.5-3 MHTXV1836
3.5-4 MHTXV4248
5 MHTXV6000
Charge the system by superheat when using a piston. Reference the outdoor unit installation guide to charge the
system by subcooling when using a TXV.
Outdoor Temp
(°F)
Indoor Temperature (°F) Dry Bulb/Wet Bulb
95/79 90/75 85/71 80/67 75/63 70/58
Superheat (°F)
115 23 16 7 6 5 5
110 24 17 9 6 5 5
105 26 19 11 6 5 5
100 27 21 13 7 6 5
95 29 23 14 9 6 5
90 30 25 18 12 7 5
85 32 26 20 15 9 6
80 34 28 22 17 11 6
75 35 30 24 19 13 7
70 37 32 26 21 16 10
65 38 34 29 24 19 13
60 40 36 31 27 22 17
55 41 37 34 30 26 21
NOTE: Due to continuing product and product data improvement, if the system combination you are looking
for is not listed, check the latest version of this document at MRCOOL.com.
11 - Piston/TXV Installation
background
PRODIRECT™ Series
PSC Air Handler
The design and specications of this product and/or manual are subject to change without prior notice.
Consult with the sales agency or manufacturer for details.

Specifications

Indexed Terms: Air Handler, ECM