Goodman AMVT24BP1300 R-32 AMVT Air Handler 2 Ton R-32 Variable-Speed

Product's Documents

Below are documents related to this product, you can read online or download:
AMVT24BP1300 photo

Specification

This is the main product document for model AMVT24BP1300. Additionally, the document applies to other Goodman models: AMVT24BP1300, STANDARD

The file format is pdf, 12 pages, you can download this manual here .

background
SS-GAMVT-R32 www.goodmanmfg.com 12/24
Superseded 10/24
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited
Warranty, online registraon must be completed within 60 days of installaon. Online registraon and some of the addional
requirements are not required in Florida, California, or Québec. The duraon of warranty coverage in Texas and Florida diers in
some cases. Other limitaons and exclusions apply; refer to complete warranty details for a full list of limitaons and exclusions.
AMVT Series
Contents
Air Handler Nomenclature .................... 2
Heater Kit Nomenclature ...................... 2
Product Specicaons ........................... 3
Dimensions ............................................ 4
Airow Data ........................................... 5
Heat Kit Data .......................................... 6
Wiring Diagram ...................................... 8
Accessories ............................................ 9
R-32 Multi-Position, Variable-Speed,
ECM-Based Air Handler
with Internal TXV
ComfortBridge™ Compatible
1½ to 5 Tons
Product Features
• Internal factory-installed thermal expansion
valves for cooling and heat pump applicaons
• Variable-speed ECM blower motor
• Compable with Goodman smart thermostat and
other Goodman communicang equipment
• Auto conguraon of the airow
and tonnage in communicang mode
• All-aluminum evaporator coil
• Provides constant CFM over a wide range
of stac pressure condions independent
of duct system
• CFM indicator
• Fault recall of six most recent faults
• Provides adjustable low CFM for
ecient fan-only operaon
• Improved humidity and comfort control
• Built-in compability with mul-stage
heat pump and cooling applicaons
• Factory installed R-32 sensor designed for
the lifespan of the coil
• Opmized for the use with R-32 refrigerant
• UL 60335 2-40 Compliant
• AHRI cered; ETL listed
• Cabinet air leakage less than 2.0%
at 1.0 inch H
2
O when tested in
accordance with ASHRAE standard 193
• Cabinet air leakage less than 1.4%
at 0.5 inch H
2
O when tested in
accordance with ASHRAE standard 193
• 3 kW – 25 kW electric heater kits
• Horizontal or vercal conguraon capabilies
• 21” depth for easier ac access
• DecaBDE-free thermoplasc drain
pan with secondary drain connecons
• Screw-less sides and back helps to reduce
condensaon when installed in humid locaons
• Foil-faced insulaon covers the internal
casing to reduce cabinet condensaon
• Galvanized, leather grain-embossed nish
• Glue-less cabinet insulaon retenon
• Tool-less lter access
background
2 www.goodmanmfg.com SS-GAMVT-R32
Nomenclature
H K T S D 2 5 D 1
1 2 3 4 5 6 7 8 9
Unit Type
HKTS - Electric heater
Kit for air handlers
Electrical
A - Single phase 208 V
Service Disconnect
B - Single phase 240 V
D - Service disconnect
1 - Single phase 208/240 V
N - No service disconnect 3 - Three phase 208/240 V
Cabinet Size
X - All Cabinets C - C Cabinet
D - D Cabinet
Heang Capacity @ 240 V
3 3.0 kW 10 9.6 kW
5 4.8 kW 15 14.4 kW
6 6.0 kW 19 19.2 kW with 170°F limit
8 8.0 kW 20 19.2 kW with 160°F limit
Note: 20X3 = 18.0 kW with 160°F limit
25 24.0 kW
A M V T 3,6 C P 1 3 0 0 B A
1 2 3 4 5,6 7 8 9 10 11,12 13 14
Minor Revision
Brand
A - Corporate Air Handler
D - Daikin Air Handler
Major Revision
Application
C - Ceiling Mounted
Factory Installed Electric Heat KW
M - Multi-Positional
00 -No Electric Heat
W - Wall Mounted
F - Fit Compatible Multi-Positional
H - Horizontal Discharge Compatible
Multi-Positional
Refrigerant
3 - R32
Motor
S - MS-ECM
V - VS-ECM Communicating
Electrical
Expansion Device
1 208/230 V, 1 Phase, 60 Hz
E - Electronic Expansion Valve
F - Flowrator
T - Thermal Expansion Valve
Cabinet
Nominal Capacity
N - Uncased
12 - 1.0 Ton 36 - 3.0 Tons
P - Painted
18 - 1.5 Tons 42 - 3.5 Tons U - Unpainted
24 - 2.0 Tons 48 - 4.0 Tons
30 - 2.5 Tons 60 - 5.0 Tons
Cabinet Width
AC* Series AM* Series AW* Series
M - 43.25" B - 17.5" S - 20.2"
L - 49.25" C -21.0" L - 24.0"
D - 24.5"
background
SS-GAMVT-R32 www.goodmanmfg.com 3
Product Specifications
AMVT
24BP1300
AMVT
30BP1300
AMVT
36BP1300
AMVT
36CP1300
AMVT
42CP1300
AMVT
48CP1300
AMVT
60DP1300
Nominal Ratings
Cooling (Btu/h) 24,000 30,000 36,000 36,000 42,000 48,000 60,000
Blower
Diameter 10" 10" 10" 10" 10" 10" 11"
Width 6" 6" 6" 8" 8" 10" 10"
Refrigerant Line
Connection Size
Liquid 3/8" 3/8" 3/8" 3/8" 3/8" 3/8" 3/8"
Sucon 3/4" 3/4" 3/4" 3/4" 3/4" 7/8" 7/8"
Coil Drain Connect FPT 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
Electrical Data
Voltage 208/240 208/240 208/240 208/240 208/240 208/240 208/240
Min Circuit Ampacity 4.9/4.9 4.9/4.9 6.5/6.5 6.5/6.5 6.5/6.5 6.5/6.5 8.6/8.6
Max. Overcurrent Device (amps) 15/15 15/15 15/15 15/15 15/15 15/15 15/15
Min. / Max VAC 197 / 253 197 / 253 197 / 253 197 / 253 197 / 253 197 / 253 197 / 253
Blower Motor
Blower Motor (FLA) 3.9 3.9 5.2 5.2 5.2 5.2 6.9
Blower Motor (HP) 1/2 1/2 3/4 3/4 3/4 3/4 1
Ship Weight (lbs) 117 134 134 158 158 158 172
background
4 www.goodmanmfg.com SS-GAMVT-R32
Dimensions
Model A" B" C" D" E" F" G" H" j” k”
AMVT24BP1300 45 16⁵⁄
16
17⁹⁄
16
15¼ 12 12½ 9 12
9
⁄
16
2 13⅝
AMVT30BP1300 53⁷⁄
16
16⁵⁄
16
17⁹⁄
16
23
11
⁄
16
20
1
⁄
16
12½ 9 12¾ 2 13⅝
AMVT36BP1300 53⁷⁄
16
16⁵⁄
16
17⁹⁄
16
23
11
⁄
16
20
1
⁄
16
12½ 9 12¾ 2 13⅝
AMVT36CP1300 49 19
13
⁄
16
21⅛ 21
12
⁄
16
17¾ 16
1
⁄
16
9 12¾ 2 17⅛
AMVT42CP1300 53⁷⁄
16
19
13
⁄
16
21⅛ 21
12
⁄
16
18½ 16
1
⁄
16
9 12¾ 2 17⅛
AMVT48CP1300 58 19
13
⁄
16
21⅛ 26
3
⁄
16
22
15
⁄
16
14
10
⁄
16
10
13
⁄
16
6
13
⁄
16
2 17⅛
AMVT60DP1300 58 23
1
⁄
14
24⅝ 26 22¾ 17
11
⁄
16
12
9
⁄
16
13
13
⁄
16
2 20⅝
background
SS-GAMVT-R32 www.goodmanmfg.com 5
Airflow Data
See notes on page 7.
Model Number Low/ High
Outdoor Tonnage
1.5 2 2.5 3 3.5 4 5
AMVT24BP1300
Low 402 536 - - - - -
High 600 800 - - - - -
AMVT30BP1300
Low 402 536 670 - - - -
High 600 800 1,000 - - - -
AMVT36BP1300
Low - - 670 804 - - -
High - - 1,000 1,200 - - -
AMVT36CP1300
Low - 536 670 804 - - -
High - 800 1,000 1,200 - - -
AMVT42CP1300
Low - - - 804 938 - -
High - - - 1,200 1,400 - -
AMVT48CP1300
Low - - - - 938 1,072 -
High - - - - 1,400 1,600 -
AMVT60DP1300
Low - - - - - 1,072 1,340
High - - - - - 1,600 2,000
Notes
1. Airow data indicated is at 230V without air lter in place.
2. The chart is for informaon only. For sasfactory operaon, external stac pressure must not exceed value shown on rang plate.
3. Use the CFM adjustment factors of 0.98 for horizontal le and 0.96 for horizontal right & downow orientaons
4. When applying a humidistat (normally closed), refer to the installaon and operang instrucons. The humidistat can adjust the cooling airow to 85%.
background
6 www.goodmanmfg.com SS-GAMVT-R32
Heat Kit Data
See Notes on Page 7.
Heater Kit Model
Circuit 1 (208V/240V) Circuit 2 (208V/240V) Single-Point Kit (208V/240V)
Heater Amps MCA¹ MOP² Heater Amps MCA¹ MOP² MCA¹ MOP²
AMVT24BP1300AA 0/0 4.9/4.9 15/15 --- --- --- --- ---
HKTSN03X1 10.8/12.5 18.4/20.5 20/25 --- --- --- --- ---
HKTS*05X1 17.3/20.0 26.5/29.9 30/30 --- --- --- --- ---
HKTSN06X1 21.7/25.0 32.0/36.1 35/40 --- --- --- --- ---
HKTS*08X1 28.9/33.3 41.0/46.5 45/50 --- --- --- --- ---
HKTS*10X1 34.7/40.0 48.2/54.9 50/60 --- --- --- --- ---
HKTSD15XA/B 34.7/40.0 48.2/54.9 50/60 17.3/20.0 21.7/25.0 25/25 69.9/79.9 70/80
AMVT30BP1300AA 0/0 4.9/4.9 15/15 --- --- --- --- ---
HKTSN03X1 10.8/12.5 18.4/20.5 20/25 --- --- --- --- ---
HKTS*05X1 17.3/20.0 26.5/29.9 30/30 --- --- --- --- ---
HKTSN06X1 21.7/25.0 32.0/36.1 35/40 --- --- --- --- ---
HKTS*08X1 28.9/33.3 41.0/46.5 45/50 --- --- --- --- ---
HKTS*10X1 34.7/40.0 48.2/54.9 50/60 --- --- --- --- ---
HKTSD15XA/B 34.7/40.0 48.2/54.9 50/60 17.3/20.0 21.7/25.0 25/25 69.9/79.9 70/80
AMVT36BP1300AA 0/0 6.5/6.5 15/15 --- --- --- --- ---
HKTSN03X1 10.8/12.5 20.0/22.1 25/25 --- --- --- --- ---
HKTS*05X1 17.3/20.0 28.2/31.5 30/35 --- --- --- --- ---
HKTSN06X1 21.7/25.0 33.6/37.8 35/40 --- --- --- --- ---
HKTS*08X1 28.9/33.3 42.6/48.2 45/50 --- --- --- --- ---
HKTS*10X1 34.7/40.0 49.8/56.5 50/60 --- --- --- --- ---
HKTSD15XA/B 34.7/40.0 49.9/56.5 50/60 17.3/20.0 21.7/25.0 25/25 71.5/81.5 80/90
AMVT36CP1300AA 0/0 6.5/6.5 15/15 --- --- --- --- ---
HKTSN03X1 10.8/12.5 20.0/22.1 20/25 --- --- --- --- ---
HKTS*05X1 17.3/20.0 28.2/31.5 30/35 --- --- --- --- ---
HKTSN06X1 21.7/25.0 33.6/37.8 35/40 --- --- --- --- ---
HKTS*08X1 28.9/33.3 42.6/48.2 45/50 --- --- --- --- ---
HKTS*10X1 34.7/40.0 49.8/56.5 50/60 --- --- --- --- ---
HKTS*15X3 ^ 0/0 6.5/6.5 15/15 30.0/34.6 37.5/43.3 40/45 --- ---
HKTSD15XA/B 34.7/40.0 49.8/56.5 50/60 17.3/20.0 21.7/25.0 25/25 71.5/81.5 80/90
HKTSD19CA/B 34.7/40.0 49.8/56.5 50/60 34.7/40.0 43.3/50.0 45/50 93.2/107 100/110
AMVT42CP1300AA 0/0 6.5/6.5 15/15 --- --- --- --- ---
HKTS*05X1 17.3/20.0 28.2/31.5 30/35 --- --- --- --- ---
HKTSN06X1 21.7/25.0 33.6/37.8 35/40 --- --- --- --- ---
HKTS*08X1 28.9/33.3 42.6/48.2 45/50 --- --- --- --- ---
HKTS*10X1 34.7/40.0 49.8/56.5 50/60 --- --- --- --- ---
HKTS*15X3 ^ 0/0 6.5/6.5 15/15 30.0/34.6 37.5/43.3 40/45 --- ---
HKTSD15XA/B 34.7/40.0 49.9/56.5 50/60 17.3/20.0 21.7/25.0 25/25 71.5/81.5 80/90
HKTSD19CA/B 34.7/40.0 49.9/56.5 50/60 34.7/40.0 43.3/50.0 45/50 93.2/107 100/110
background
SS-GAMVT-R32 www.goodmanmfg.com 7
Heat Kit Data (cont.)
Heater Kit Model
Circuit 1 (208V/240V) Circuit 2 (208V/240V) Single-Point Kit (208V/240V)
Heater Amps MCA¹ MOP² Heater Amps MCA¹ MOP² MCA¹ MOP²
AMVT48CP1300AA 0/0 6.5/6.5 15/15 --- --- --- --- ---
HKTS*05X1 17.3/20.0 28.2/31.5 30/35 --- --- --- --- ---
HKTSN06X1 21.7/25.0 33.6/37.8 35/40 --- --- --- --- ---
HKTS*08X1 28.9/33.3 42.6/48.2 45/50 --- --- --- --- ---
HKTS*10X1 34.7/40.0 49.8/56.5 50/60 --- --- --- --- ---
HKTS*15X3 ^ 0/0 6.5/6.5 15/15 30.0/34.6 37.5/43.3 40/45 --- ---
HKTSD15XA/B 34.7/40.0 49.8/56.5 50/60 17.3/20.0 21.7/25.0 25/25 71.5/81.5 80/90
HKTSD19CA/B 34.7/40.0 49.8/56.5 50/60 34.7/40.0 43.3/50.0 45/50 93.2/107 100/110
AMVT60DP1300AA 0/0 8.6/8.6 15/15 --- --- --- --- ---
HKTS*05X1 17.3/20.0 30.3/33.6 35/35 --- --- --- --- ---
HKTSN06X1 21.7/25.0 35.7/39.9 40/40 --- --- --- --- ---
HKTS*08X1 28.9/33.3 44.7/50.3 45/60 --- --- --- --- ---
HKTS*10X1 34.7/40.0 52.0/58.6 60/60 --- --- --- --- ---
HKTS*15X3 ^ 0/0 8.6/8.6 15/15 30.0/34.6 37.5/43.3 40/45 --- ---
HKTSD15XA/B 34.7/40.0 52.0/58.6 60/60 17.3/20.0 21.6/25.0 25/25 73.6/83.6 80/90
HKTS*20X3 ^ 0/0 8.6/8.6 15/15 37.5/43.3 46.9/54.1 50/60 --- ---
HKTSD20DA/B 34.7/40.0 52.0/58.6 60/60 34.7/40.0 43.4/50.0 45/50 95.3/109 100/110
HKTSD25DA/B 34.7/40.0 52.0/58.6 80/90 34.7/40.0 43.4/50.0 45/50 117/134 125/150
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protecon = 2.25 X Motor Amps + Heater Amps
^ Three-phase Heater Kits (Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for Heater Kits)
* D - Service disconnect, N - No service disconnect
--- indicates Not Required
Note: The 208 or 240 in the heat kit part number eld is for claricaon of the nominal voltage for this model.
background
8 www.goodmanmfg.com SS-GAMVT-R32
Air Handler Wiring Diagram AMVT**P1400** (1.5T-5T)
Wiring is subject to change. Always
refer to the wiring diagram on the
unit for the most up-to-date wiring.
⚠ Warning
High Voltage: Disconnect all power before servicing or installing this unit. Mulple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
0140A01462-A
TO BLOWER SHELL
TO
CONTROL
DECK
CONT FAN
4 CIRCUIT HEATER
CONNECTOR
COM
R
4 CIRCUIT MOTOR
CONNECTOR
LEARN
DIP SWITCHES
2
3
1
2
G
O
4
3
1
W2
2
Y2
1
TH
4
24 V 3 A
W1
Y1
FAULT
RECALL
C
DEHUM
TWO-STAGE INTEGRATED CONTROL MODULE
24 V THERMOSTAT CONNECTIONS
TR
FUSE
CAS
CFM LED
STATUS
LED
RX LED
HTR KIT(KW)
COOL AF PROFILE
DEHUM ENABLE
TRIM ENABLE
TRIM %
AF SELECT
S1
S2
S3
S4
S5
S6
S7
S8
S9
S10
S11 S12 S13
C
W2
W1
7 SEGMENT
DIAGNOSTI
C
DISPLAY
REF
PLM
EEV_IN
EEV_OUT
CTM_OUT
R_OUT
C
C
R
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
PORT
NOT USED
REF PCB
5V
21
C
PORT
A2L SENSOR
SENSOR IN
COIL TUBING
ASSEMBLY
INPUT VOLTAGE
208 ~ 240V
1 PHASE
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS
ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.
USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
2. FOR SPEED CHANGE, SEE INSTALLATION INSTRUCTIONS FOR FURTHER
DETAILS ON ADJUSTING DIP SWITCHES.
3. DISCARD CONNECTOR EHK PLM WHEN INSTALLING OPTIONAL HEAT KIT.
4. RED WIRE CONNECTED TO 240V TAP AT THE FACTORY AND BLACK WIRE
TO COM TERMINAL FOR 208V SUPPLY POWER, MOVE RED WIRE
FROM 240 TAP TO THE 208V TAP.
5. LOW VOLTAGE TRANSFORMER RATED 24VAC OUTPUT 75VA @ 3.125 AMP.
NOTES
CB CIRCUIT BREAKER
CR CONTROL RELAY
EHK ELECTRIC HEATER KIT
EM EVAPORATOR MOTOR
GND GROUND
PCB CONTROL BOARD
PLF FEMALE PLUG
PLM MALE PLUG
REF REFRIGERANT
TB TERMINAL BOARD
TR TRANSFORMER
COMPONENT LEGEND
HIGH VOLTAGE
OPTIONAL HIGH VOLTAGE
LOW VOLTAGE
OPTIONAL LOW VOLTAGE
CHASSIS GROUND
FACTORY WIRING
READ THE INSTRUCTIONS
CLASS |||
III
9
8
7
6
5
4
3
2
1
1
2
3
4
5
6
7
8
9
EHK
PLF
EHK
PLM
BK
RD
SEE NOTE 3
PLM
PLF
4
3
2
1
4
3
2
1
INDOOR
AIR
CIRCULATIOR
BLWR
BK
BL
GY
BK
RD
PLF
PLM
5
4
3
2
1
5
4
3
2
1
24VAC
COM
208
VAC
240
VAC
TR1
(SEE NOTE 4)
BK
RD
BL
BR
WH
RD
BK
WH
BR
BL
WH
BR
BL
BK
RD
RD
BK
GR
BL
RD
GR
PK
BL
RD
BK BLACK
BL BLUE
BR BROWN
GR GREEN
PU PURPLE
RD RED
WH WHITE
YL YELLOW
PK PINK
WIRE CODE
SEE NOTE 1 & 5
SEE NOTE 2
PK
BL
BL
PK
BL
BL
background
SS-GAMVT-R32 www.goodmanmfg.com 9
Downflow Kits
DFKE-02 DFKE-03
DMVT24BP1300** DMVT48CP1300**
DMVT30BP1300** DMVT60DP1300**
DMVT36BP1300**
DMVT36CP1300**
DMVT42CP1300**
R32 ZONING ACCESSORY KIT
KIT NUMBER Models
0230K00007 All AMVT Models
Condensate Management Kit
CMK0018 CMK0019 CMK0020
DMVT24BP1300** DMVT30BP1300** DMVT48CP1300**
DMVT36CP1300** DMVT36BP1300** DMVT60DP1300**
DMVT42CP1300**
High Humidity Kit
HHK0004 HHK0005 HHK0007
DMVT24BP1300** DMVT36CP1300**
DMVT60DP1300**
DMVT30BP1300** DMVT42CP1300**
DMVT36BP1300** DMVT48CP1300**
Single Point Wiring Kit (SPW-01)
HEATER KIT MODEL SPWK-B SPWK-C SPWK-D
HKTSD15XA
DMVT24BP1300**
DMVT30BP1300**
DMVT36BU1300**
DMVT36CU1300**
DMVT42CU1300**
DMVT48CU1300**
DMVT60DU1300**
HKTSD15XB
HKTSD19CA
HKTSD19CB
HKTSD20DA
DMVT60DU1300**
HKTSD20DB
HKTSD25DA
DMVT60DU1300**
HKTSD25DB
Filters
Chassis Part # Size
B ALFH16201E 16.0” x 20.0”
C ALFH1912201E 19.5” x 20.0”
D ALFH20231E 23.0” x 20.0”
Ultraviolet Drain Pan Kit
Model Size Kit # Parts
DMVT24B UVPK01
DRAIN PAN MAIN
DRAIN PAN
SIDE
NA
CONDENSATE
COLLECTOR,
BACK
CONDENSATE
COLLECTOR,
BACK
DMVT30B
DMVT36B
UVPK02
CONDENSATE
COLLECTOR,
BACK
DMVT36C UVPK03
DMVT42C UVPK04
DMVT48C UVPK05
DMVT60D UVPK07
Accessories
background
10 www.goodmanmfg.com SS-GAMVT-R32
Notes
background
SS-GAMVT-R32 www.goodmanmfg.com 11
Notes
background
12 www.goodmanmfg.com SS-GAMVT-R32
Our connuing commitment to quality products may mean a change in specicaons without noce.
©2024 • Houston, Texas • Printed in the USA
Notes

Specifications

Indexed Terms: Air Handler, Variable-Speed

Goodman AMVT24BP1300 Questions and Answers

Questions and Answers