MRCOOL
®
Signature Series
TruInverter™
Split System Heat Pump
INSTALLATION & OWNER’S MANUAL
Read this manual carefully before installation and keep it where
the operator can easily nd it for future reference.
Due to updates and constantly improving performance, the
information and instructions within this manual are subject to
change without notice.
Version Date: February 12, 2026
Please visit www.mrcool.com/documentation
to ensure you have the latest version of this manual.
This product utilizes R-454B refrigerant
MODELS:
MCAESHV*T*21BA

mrcool.com1
CONTENTS
SAFETY ................................................................................................................... 2
UNIT OVERVIEW .................................................................................................... 8
2.1 Nomenclature .......................................................................................... 8
2.2 Suggested Tools ....................................................................................... 9
2.3 Inspection ................................................................................................. 9
2.4 Unit Size .................................................................................................... 9
2.5 Location Restrictions ............................................................................. 10
2.6 Refrigerant Charge & Room Area Limitations .................................... 11
Installation .......................................................................................................... 15
3.1 Refrigerant Line ...................................................................................... 15
3.2 Refrigerant Line Routing ....................................................................... 17
3.3 Refrigerant Line Connection ................................................................. 18
3.4 Leakage Check ........................................................................................ 20
3.5 Evacuation .............................................................................................. 20
3.6 Open the Service Valves ........................................................................ 21
3.7 Low Voltage Connections ...................................................................... 21
3.8 High Voltage Connections ..................................................................... 23
3.9 System Startup ....................................................................................... 25
POST-INSTALLATION .......................................................................................... 26
4.1 System Display ....................................................................................... 26
4.2 Error Codes ............................................................................................. 27
4.3 Components ........................................................................................... 28
4.4 Troubleshooting ..................................................................................... 29
4.5 Schematic ................................................................................................ 31
1
Contents
2
3
4
This marking indicates that this product should not be disposed with other household wastes throughout North America.
To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly
to promote the sustainable reuse of material resources. To return your used device, please use the return and collection
systems or contact the retailer where the product was purchased. They can take this product for environmental safe recycling.

mrcool.com 2 2
Incorrect usage may cause serious damage or injury.
The symbols below are used throughout this manual to indicate instructions that should be
followed closely or actions that should be avoided to prevent death, injury, and/or property
damage.
Safety Precautions
CAUTION
Indicates the possibility of personal injury or loss of life.
Indicates the possibility of property damage or serious
consequences.
Read Before Using
WARNING
WARNING FOR PRODUCT INSTALLATION
1. Read the manual fully before installing or using the system.
2. During the installation of the condenser and air handler, no children should be around the systems as
accidents can occur.
3. Ensure that the base of the condenser is rmly xed to installation site.
4. Check that non-condensables can enter the refrigerant system and check for refrigerant leaks before
operation.
5. Run a test cycle after installation and record the operating data.
6. Protect the unit with a suitable fuse for the maximum input current or with a similar overload protection
device.
7. Ensure that the main voltage corresponds to what is stamped on the rating plate.
8. The system must be equipped with devices capable of disconnection from the main power supply, have
a contact separation in all poles to provide full disconnection under "overvoltage category III conditions",
these devices must also be incorporated into the xed wiring in accordance with the wiring rules.
9. The air conditioner must be installed by professionals or qualied personnel.
10. Do not install the appliance at a distance of less than 19.7in(50 cm) from ammable substances (alcohol,
etc.) or from pressurized containers (spray cans, etc.).
11. If the appliance is used in areas without ventilation, precautions must be taken to prevent any leaks of
refrigerant from remaining in the environment and re hazard.
12. The packaging materials are recyclable and should be disposed of in separate waste bins. If disposing of
the system, contact qualied personnel to uninstall and take to a special water center for disposal.
13. Only use the system as instructed in this manual. These instructions are not intended to cover every
possible condition and situation. As with any electrical household appliance, common sense and caution is
recommended for installation, operation, and maintenance.
14. This system must be installed in accordance with national and local regulations.
15. Before accessing the terminals, circuits must be disconnected from the power supply.
16. The system can be used by children 8 years or older and persons with reduced physical, sensory or
mental capabilities, or those who lack experience/knowledge, if they are given supervision or instruction
concerning the use of the appliance in a safe way and understand the hazards involved. Children should
not play with the system. Cleaning and user maintenance should not be performed by children without
proper supervision.
17. Cleaning and maintenance must be carried out by specialized technical personnel. Always disconnect the
system from the main power supply before carrying out any cleaning or maintenance.
18. This system is designed for use in domestic environments and may not be used for any other purpose,
such as for drying clothes, cooling food, etc.
19. Always use the system with an air lter. Running the system without an air lter can cause an excessive
amount of dust/debris and lead to component failure.
SAFETY
1

mrcool.com3
WARNING FOR INSTALLATION CONT.
20. The owner of the system is responsible for having the appliance installed by qualied personnel, who must
check earthing/grounding is completed in accordance with national and local codes, and install a proper
disconnect and breaker.
21. Do not remain directly exposed to the ow of cool air for a prolonged period. Direct and prolonged
exposure to cool air can be dangerous to your health. Care should be taken in rooms where there are
children, elderly, or sick persons.
22. If the system gives o smoke or there is a burning smell, immediately cut o the power supply and contact
an HVAC service company to inspect the system. Prolonged use of the device in such conditions can cause
a re or electrocution.
23. Repairs must be carried out by an authorized personnel as any incorrect repairs can expose an
unexperienced person to multiple hazards.
24. Turn the system o at the breaker if you intend to not use the system for a prolonged period of time or for
cleaning/maintenance.
SAFETY RULES & PROHIBITIONS:
• Do not use extensions or gang modules.
• Do not touch the appliance when barefoot or if parts of the body are wet/damp.
• Do not obstruct the air inlet or outlet of the air handler or condenser. Obstruction of these openings can
cause a reduction in the eciency of the system or possible failures/damages.
• Do not alter the characteristics of the system.
• Do not install the appliance in environments where the air can contain ammable gases, oil, sulphuric, or
near sources of heat.
• Do not climb on or place heavy or hot objects on top of the system.
• Do not leave windows or doors open while the system is operating.
• Do not direct airow onto plants or animals.
• Do not put the system in contact with water, this can cause electric shock.
• Do not insert anything into the system as this can cause injury or damage to the system.
• This unit is equipped with a refrigerant leak detector for safety. To be eective, the unit must be
electrically powered at all times after installation, other than when servicing.
• This refrigerant sensor can only be replaced with a sensor approved by MRCOOL®. If the sensor is
replaced only as part of the component assembly, the component should be labeled.
• The system shall be installed according to MRCOOL®'s instructions.
1. Reference information in this manual to nd the dimensions of the space needed for proper installation of
the system, including the minimum distances allowed compared to adjacent structures.
2. The system should be installed, operated, and stored in a room with a oor area larger than 43ft
2
. (4m
2
.).
3. The installation of pipework should be kept to a minimum.
4. The pipework should be protected from physical damage, and should not be installed in an unventilated
space if the space is less than 43ft
2
. (4m
2
.).
5. Compliance of national gas regulations should be observed.
6. Mechanical connections should be accessible for maintenance purposes.
7. Follow the instructions in this manual for handling, installing, cleaning, maintaining, and disposal of
refrigerant.
8. Make sure ventilation openings are clear of obstructions.
9. The system should be stored in a room without open ames (ex.operating gas appliances) and ignition
sources (ex.operating electric heaters).
10. The system must be stored in a way to prevent mechanical damage from occurring.
11. It is necessary that anyone who is working on a refrigerant circuit holds a valid and up-to-date certication
from an assessment authority accredited by the industry that recognizes their competence to handle
refrigerants, in accordance with the assessment specication recognized in the industrial sector concerned.
Service operations should only be carried out in accordance with the recommendations of MRCOOL®.
CAUTION
SAFETY
1

mrcool.com 4
4
SAFETY
1
12. Every working procedure that aects safety means should only be completed by competent personnel.
13. Warning:
• Do not use any means to accelerate the defrosting process or clean the frost on your own. Follow the
recommended guidelines from MRCOOL®.
• The system should be stored in a room without continuously operating ignition sources (ex. open
ames, operating gas appliances, or an operating electric heater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odor.
14. Information on Servicing:
1) Checks to the area:
Prior to beginning work on systems containing ammable refrigerants, safety checks are necessary to
ensure that the risk of ignition is minimized. For refrigeration system repair, the following precautions
should be taken prior to conducting work on the system.
2) Work Procedure:
Work should be performed under a controlled procedure to minimize the risk of ammable gas or vapor
being present while work is performed.
3) General Work Area:
All maintenance sta and others working in the area should be instructed on the nature of the work
being performed. Work in conned spaced should be avoided. The area around the workspace should be
sectioned o. Ensure that the conditions within the area have been made safe by controlled ammable
material.
4) Checking for the Presence of Refrigerant:
The area should be checked with an appropriate refrigerant detector prior to and during work to ensure
that the technician is aware of a potential ammable atmospheres. Ensure the leak detection equipment
being used is suitable for use with ammable refrigerants, i.e. non-sparking, adequately sealed, or
intrinsically safe.
5) Presence of a Fire Extinguisher:
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate
re extinguishing equipment should be available. Have a dry powder or CO2 re extinguisher adjacent to
the charging area.
6) No Ignition Sources:
No personnel carrying out work in relation to a refrigeration system which involves exposing any pipe
work should use any sources of ignition in such a manner that it may lead to the risk of re or explosion.
All possible ignition sources, including cigarette smoking, should be kept suciently far away from the
site of installation, repair, removal/disposal, during which refrigerant can possibly be released to the
surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make
sure that there are no ammable hazards or ignition risks. "No Smoking" signs should be displayed.
7) Ventilated Area:
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system
or conducting any work that will produce heat. A degree of ventilation should continue during the
period that the work is carried out. The ventilation should safely disperse any released refrigerant and
preferably expel it externally into the atmosphere.
8) Check to the Refrigeration Equipment:
Where electrical components are being changed, they should be t for the purpose and to the correct
specication. At all times the manufacturer's maintenance and service guidelines should be followed.
If in doubt, consult MRCOOL® customer service at 270-366-0457 or at [email protected].
The following checks should be applied to the installation when using ammable refrigerants;
-- The charge size complies with the room size where the refrigerant-containing parts are installed;
-- The ventilation of machinery and outlets are operating adequately and are not obstructed;
-- If an indirect refrigerating circuit is being used, the secondary circuit should be checked for the
presence of refrigerant;
CAUTION CONT.

mrcool.com5
SAFETY
1
--Markings to the equipment should be visible and legible. Markings and signs that are illegible should be
corrected.
-- Refrigeration pipe or components are installed in a position where they are unlikely to be exposed
to any substance which may corrode refrigerant containing components, unless the components are
constructed of materials which are inherently resistant to being corroded or suitably protected against
corrosion.
9) Checks to Electrical Devices:
Repair and maintenance to electrical components should include safety checks and component
inspection procedures. If a fault exists that could compromise safety, then no electrical supply should
be connected to the circuit until the fault is corrected. If the fault cannot be corrected immediately but
it is necessary to continue operation, an adequate temporary solution should be used. This needs to be
reported to the owner of the equipment so all parties are advised.
Initial safety checks include:
-- Capacitors are discharged: this needs to be done in a safe manner to avoid the possibility of sparking;
-- That no live electrical components or wiring is exposed while charging, recovering, or purging the
system;
-- There is continuity of earth bonding.
10) Repairs to Sealed Components:
Sealed electrical components should be replaced.
11) Repairs to Intrinsically Safe Components:
Intrinsically safe components should be replaced.
12) Cabling:
Check that the cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges,
or any other adverse environmental eects. The check should also take into account the eects of aging
or continual vibration from compressors or fans.
13) Detection of Flammable Refrigerants:
Under no circumstances should potential sources of ignition be used in the searching for or detection of
refrigerants leaks. A halide torch (or any other detector using a naked ame) should not be used.
14) Leak Detection Methods:
The following leak detection methods are deemed acceptable for systems containing ammable
refrigerants.
Electronic leak detectors should be used to detect ammable refrigerants, but the sensitivity may not
be adequate or may need recalibration. (Detection equipment should be calibrated in a refrigerant-free
area). Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant
used. Leak detection equipment should be set at a percentage of the LFL of the refrigerant and should
be calibrated to the refrigerant employed until the appropriate percentage of gas (25% maximum) is
conrmed. Leak detection uids are suitable for use with most refrigerants but the use of detergents
containing chlorine should be avoided as the chlorine may react with the refrigerant and corrode the
copper pipework. If a leak is suspected, all naked ames should be removed/extinguished. If a refrigerant
of leak is found which requires brazing, all of the refrigerant should be recovered from the system, or
isolated (by means of shut o valves) in a part of the system remote from the leak. Oxygen free nitrogen
(OFN) should be purged through the system both before and during the brazing process.
15) Removal & Evacuation:
When breaking into the refrigerant circuit to make repairs or for any other purpose conventional
procedures should be used. However, it is important that best practice is used since ammability is a
concern. The following procedure should be adhered to:
-- Remove refrigerant;
-- Purge the circuit with inert gas;
-- Evacuate;
-- Purge again with inert gas;
-- Open the circuit by cutting or brazing.
The refrigerant charge has to be recovered into the correct recovery cylinders. The system should be
ushed with OFN to render the unit safe. This process may need to be repeated several times.
CAUTION CONT.

mrcool.com 6
6
SAFETY
1
Compressed air or oxygen should not be used for this task.
Flushing should be achieved by breaking the vacuum in the system with OFN and continuing to ll until
the working pressure is achieved, then venting to the atmosphere, and nally pulling down to a vacuum.
This process should be repeated until no refrigerant is within the system. When the nal OFN charge
is used, the system should be vented down to atmospheric pressure to enable work to take place. This
operation is vital if brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not near any ignition sources and ventilation is adequate.
16) Decommissioning:
Before carrying out this procedure, it is essential that the technician is completely familiar with the
equipment and all its detail. It is recommended good practice that all refrigerant is recovered safely.
Before the task is carried out, an oil and refrigerant sample should be taken in case analysis is required
prior to reusing reclaimed refrigerant. It is essential that electrical power is available before the task is
completed.
1) Become familiar with the equipment and its operation.
2) Isolate the system electrically.
3) Before attempting the procedure, ensure that:
• mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• all personal protective equipment is available and being used correctly;
• the recovery process is supervised at all times by a competent person;
• recovery equipment and cylinders conform to the appropriate standards.
4) Pump down refrigerant into the system if possible.
5) If a vacuum is not possible, make a manifold so the refrigerant can be removed from various parts of
the system.
6) Make sure that the cylinder is properly situated on the scales before recovery takes place.
7) Start the recovery machine and operate in accordance with MRCOOL®'s instructions.
8) Do not overll cylinders. (No more than 80% volume liquid charge).
9) Do not exceed the maximum working pressure of the cylinder, even temporarily.
10) When the cylinders have been lled correctly and the process completed, make sure that the
cylinders and the equipment are removed from the site promptly and all isolation valves on the
equipment are closed o.
11) Recovered refrigerant should not be charged into another refrigeration system unless it has been
cleaned and checked.
17) Labeling:
Equipment should be labeled stating it has been decommissioned and emptied of refrigerant. The label
should be dated and signed. Ensure there are labels on the equipment stating the equipment contains
ammable refrigerant.
18) Recovery:
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended
good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders
are employed. Ensure that the correct number of cylinders for holding the total system charge are
available. All cylinders to be used are designated for the recovered refrigerant and labeled for that
refrigerant (i.e.special cylinders for the recovery of refrigerant). Cylinders should be complete with a
pressure-relief valve and associated shut-o valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery
equipment should be in good working order with a set of instructions concerning the equipment that
is available and suitable for the recovery of all refrigerants including, when applicable, ammable
refrigerants. In addition, a set of calibrated weighing scales should be available and in good working
order. Hoses should be complete with leak-free disconnect couplings and in good condition. Before using
the recovery machine, check that it is in satisfactory working order, has been properly maintained, and
that any associated electrical components are sealed to prevent ignition in the event of a refrigerant
release. Consult MRCOOL® if in doubt.
CAUTION CONT.

mrcool.com7
Symbols Displayed on Indoor & Outdoor Unit
DANGER
This symbol shows that this appliance uses a ammable refrigerant. If the refrigerant
is leaked and exposed to an external ignition source, there is a risk of re.
CAUTION This symbol shows that the operation manual should be read carefully.
CAUTION
This symbol shows that service personnel should be handling this equipment in
reference to the installation manual.
CAUTION
This symbol shows that information is available, such as the operating manual or
installation manual.
CAUTION
This symbol shows that when MRCOOL
®
requires additional charge, record the
resulting total refrigerant charge for each refrigerating system.
WARNING
This symbol shows that the appliance should be installed, operated, and stored in a
room with a oor area that is no less than the minimum room area.
SAFETY
1
The recovered refrigerant should be returned to the refrigerant supplier in the correct recovery cylinder,
and the relevant waste transfer note should be arranged. Do not mix refrigerants in recovery units, and
especially cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an
acceptable level to make certain that ammable refrigerant does not remain within the lubricant.
The evacuation process should be carried out prior to returning the compressor to the suppliers.
Only electric heating to the compressor body should be employed to accelerate this process. When oil is
drained from a system, it should be carried out safely.
19) Safety Instructions for Transportation & Storage:
1) No re source or smoking.
2) According to the local and national rules and laws.
CAUTION CONT.
Installation Safety Principles:
1. Site Safety
Open Flames Prohibited Ventilation Necessary
2. Operation Safety
Mind Static Electricity
Must wear protective clothing
and anti-static gloves
Do not use a mobile phone

mrcool.com 8
8
3. Installation Safety:
• Refrigerant Leak Detector
• Appropriate Installation Location
The picture to the right shows a refrigerant leak
detector.
Please note that:
1. The installation site should be well-ventilated.
2. The site for installing and maintaining an air conditioner using R-454B should be free from open re, welding,
smoking, ovens, or any other heat source higher than 745°F (396°C), which can easily produce a re.
3. When installing the system, it is necessary to take appropriate anti-static measures such as wearing anti-
static clothing and/or gloves.
4. It is necessary to choose the site most convenient for installation or maintenance wherein the air inlet and
outlet of the indoor and outdoor units should not be surrounded by obstacles or close to any heat source or
combustible and/or explosive environment.
5. If the air handler has a refrigerant leak during installation, it is necessary to immediately turn o the valve of
the outdoor unit and all personnel should leave the space until the refrigerant completely disperses for 15
minutes or more. If the product is damaged, it must be repaired o-site.
6. It is necessary to choose a place where the inlet and outlet of the air handler is level.
7. It is necessary to avoid areas where there are other electrical products, power switches, plugs, sockets,
kitchen cabinets, beds, sofas, or other valuables under or on the sides of the air handler.
2.1 Nomenclature
MCAE = MRCOOL Air
Equipment
MCAE
UNIT OVERVIEW
2

mrcool.com9
UNIT OVERVIEW
2
2.4 Unit Size
2.2 Suggested Tools
Tool Picture Tool Picture Tool Picture
Standard Wrench Pipe Cutter Vacuum Pump
Adjustable/
Crescent Wrench
Screw Drivers
(Phillips & Flat)
Safety Glasses
Torque Wrench
Manifold &
Gauges
Anti-Static
Gloves
Hex Keys or Allen
Wrenches
Level Refrigerant Scale
Drill & Drill Bits Flaring Tool Micron Gauge
Hole Saw
Clamp on Amp
Meter
Torch
2.3 Inspection
The condenser is packaged for shipment to avoid damage during normal transit and handling. It is the
receiving party's responsibility to inspect the condenser upon arrival. Any obvious damage to the box should be
reported on the bill of lading ,then a claim should be led with the transportation company, as well as notifying
MRCOOL®. All condensers should be stored in the box in a dry location until installation. Carefully remove the
packaging and inspect for hidden damage. Any hidden damage should be recorded and MRCOOL® should be
notied. The gauge port can be used to ensure the refrigerant charge has been retained during transit.
When mounting the condenser on the roof or on a pad, be sure that its dimensions are ≥ 29in (73.66 cm) x 29in
(73.66 cm).
Unit H x W x D in (cm)
MCAESHV8T2421BA 24.94 x 29.125 x 29.125 (63.35 x 73.98 x 73.98)
MCAESHV9T3621BA 24.94 x 29.125 x 29.125 (63.35 x 73.98 x 73.98)
MCAESHV8T4821BA 33.81 x 29.125 x 29.125 (85.88 x 73.98 x 73.98)
MCAESHV7T6021BA 33.81 x 29.125 x 29.125 (85.88 x 73.98 x 73.98)

mrcool.com 10
10
UNIT OVERVIEW
2
Installation Clearance Requirements:
• Ensure the top of the system's discharge area is
unrestricted 60in (152cm) above.
• Do not locate the condenser near bedrooms, as the
noise can cause a disturbance.
• Position the condenser in a way that allows
adequate space for unobstructed airow, wiring,
refrigerant line set routing, and maintenance.
• Allow a minimum clearance of 12in (30.48cm) on the
access panels side to a wall and a minimum of 24in.
(60.96cm) on the other side of the access panel.
• Maintain a minimum distance of 24in (30.48cm)
Between condensers.
Exposure to corrosive environments may shorten the lifespan of the system, corrode metal parts, or negatively
aect the system's performance. Corrosive elements include, but are not limited to: sodium chloride, sodium
hydroxide, sodium sulfate, and other compounds commonly found in ocean water, sulfur, chlorine, uorine,
fertilizers, and various chemical contaminants from industry/manufacturing plants. If the system is installed
in areas where it may be exposed to corrosive environments, attention should be given to the system's
placement and maintenance.
• Do not have lawn sprinklers/waste water spraying directly onto the system for prolonged periods.
• In coastal areas, install the system on the side of the structure away from the waterfront.
CAUTION
2.5 Location Restrictions
Avoid installation
near bedrooms
≥ 12in. (30.48cm.)
to obstructions
≥ 60in. (152cm.) unrestricted
≥ 24in. (30.48cm.)
unrestricted
• Position the condenser in an area where water, snow,
or ice from roofs or overhangs are not able to fall
directly on the condenser.
≥ 12in. (30.48cm.)
to obstructions
≥ 24in. (30.48cm.)
from wall to
access panel

mrcool.com11
UNIT OVERVIEW
2
• Take precautions for condensers installed in areas
where snow accumulation and prolonged below
freezing temperatures occur.
• Elevate the unit per local climate and code
requirements.
• Additional height will allow the condenser to drain
snow and ice that is melted during the defrost cycle
to ow out prior to it refreezing.
• Installation of a snow drift barrier is recommended
to be installed around the condenser to prevent a
build-up of snow accumulation.
≥ 12in. (30.48cm.)
3~12in.
(7.62~30.48cm.) of
elevation
Pad
Risers
Snow
barrier
Condenser Position:
• When mounting the condenser on a roof, ensure the roof will support the weight of the condenser, located
on the nameplate.
• Proper placement of the condenser is recommended to prevent sound or vibration to the building's
structure.
2.6 Refrigerant Charge & Room Area Limitations
• In UL/CSA 60335-2-40, R-454B
refrigerant is classied as class A2L,
which is mildly ammable. Therefore,
R-454B refrigerant will limit the area of
the rooms being served by the system.
• Similarly, the total amount of
refrigerant in the system should be
less than or equal to the allowable
maximum refrigerant charge. The
allowable maximum refrigerant charge
depends on the area of the rooms
being served by the system.
NOTE:
The abbreviations in this section are explained as follows:
Mc - the actual refrigerant charge in the system
A - the actual room area where the appliance is installed
Amin - the required minimum room area
Mmax - the allowable maximum refrigerant charge in a room
Qmin - the minimum circulation airow
Anvmin - the minimum opening area for connected rooms
TAmin - the required minimum total area of the conditioned
space (for units serving two or more rooms with an air duct
system)
TA - the total area of the conditioned space connected by air
ducts (for units serving two or more rooms with an air duct
system)
CAUTION
The space considered should be any space which contains refrigerant-containing parts or into which
refrigerant could be released. The room area (A) of the smallest, enclosed, occupied space should be used in
the determination of the refrigerant quantity limits.
Room Area Calculation Requirements
• For determination of room area (A), when used to calculate the refrigerant charge limit, the following shall
apply:
• The room area (A) shall be dened as the room area enclosed by the projection to the base of the walls,
partitions, and doors of the space in which the appliance is installed. Spaced connected by only drop
ceilings, ductwork, or similar connections should not be considered a single space.
• Units mounted higher than 70.86in (1.79m), and spaces divided by partition walls that are no higher than
62.98in (1.59m), shall be considered a single space.

mrcool.com 12
12
UNIT OVERVIEW
2
• Rooms on the same oor and connected by an open passageway between the spaces can be considered a
single room when determining compliance to Amin, if the passageway complies with all of the following:
1. It is a permanent opening.
2. It extends to the oor.
3. It is intended for people to walk through.
• The area of the connected rooms, on the same oor,connected by a permanent opening in the walls and/or
doors between occupied spaces, including gaps between the wall and the oor, can be considered a single
room when determining compliance to Amin provided all of the following conditions are met, as well as
those in the gure.
• Low Level Opening
• The opening shall not be less than Anvmin in the following table.
• The area of any openings above 11.81in (30cm) from the oor shall not be considered when determining
compliance with Anvmin.
• At least 50% of the opening area of Anvmin shall be below 7.88in (20cm) from the oor.
• The bottom of the opening is not more than 3.94in (10cm) from the oor.
• The opening is a permanent opening that cannot be closed.
• For openings extending to the oor, the height shall not be less than 0.78in (1.98cm) above the surface of
the oor covering.
• High Level Opening
• The opening shall not be less than 50% of Anvmin in the following table.
• The opening is a permanent opening that cannot be closed.
• The opening shall be at least 59in (1.49m) above the oor.
• The height of the opening is not less than 0.78in (1.98m).
• Room Size Requirement
• The room into which refrigerant can leak, plus the connected adjacent room(s) shall have a total area no
less than Amin. Amin is shown in the following table
• The room area in which the unit is installed shall be no less than 20% Amin. Amin is shown in the
following table on pg. 13.
NOTE: The requirement for the second opening can be met by drop ceilings, ventilation ducts, or similar
arrangements that provide an airow path between the connected rooms.
• The minimum opening for natural ventilation (Anvmin) in connected rooms is related to the room area (A),
the actual ventilation (Anvmin) in connected rooms is related to the room area (A), the actual refrigerant
charge of refrigerant in the system (Mc), and the allowable maximum refrigerant charge in the system
(Mmax), Anvmin can be determined according to the following table on pg 13.

mrcool.com13
UNIT OVERVIEW
2
A Mc Mmax Anvmin
ft
2
lb oz lb oz ft
2
40 9 9 2 10 0.9
50 9 9 3 5 0.8
60 9 9 4 0 0.7
70 9 9 4 10 0.6
80 9 9 5 5 0.6
90 9 9 6 0 0.5
100 9 9 6 10 0.4
110 9 9 7 5 0.3
120 9 9 8 0 0.2
130 9 9 8 10 0.2
140 9 9 9 5 0.1
150 9 9 10 0 0.0
160 9 9 10 10 0.0
Note: Take the Mc=17lbs. 3oz. as an example.
• For appliances serving two or more rooms with an air duct system, the room area calculation shall be
determined based on the total area of the conditioned space (TA) connected by ductwork, taking into
consideration the circulating airow distributed to all the rooms by the unit's integral indoor fan will mix and
dilute the leaking refrigerant before entering any room.
Opening Conditions for Connected Rooms
Allowed Maximum Refrigerant Charge & Required Minimum Room Area
• If the fan inside the unit is being continuously operated or operation is initiated by a refrigerant detection
system with a sucient circulation airow rate, the allowable maximum refrigerant charge (Mmax) and the
required minimum room area (Amin/TAmin) is shown in the following tables.
A/TA Mmax A/TA Mmax
ft
2
lb oz ft
2
lb oz
40 2 10 160 10 10
50 3 5 170 11 5
60 4 0 180 12 0
70 4 10 190 12 10
80 5 5 200 13 5
90 6 0 210 14 0
100 6 10 220 14 10
110 7 5 230 15 5
120 8 0 240 16 0
130 8 10 250 16 10
140 9 5 260 17 5
150 10 0
Allowable Maximum Refrigerant Charge
Mc
Amin/
TAmin
Mc
Amin/
TAmin
lb oz ft
2
lb oz ft
2
4 6 66.1 11 0 165.3
4 13 72.7 11 7 171.9
5 4 79.3 11 14 178.5
5 11 86 12 5 185.1
6 2 92.6 12 12 191.7
6 9 99.2 13 3 198.4
7 0 105.8 13 10 205
7 7 112.4 14 1 211.6
7 15 119 14 8 218.2
8 6 125.6 14 15 224.8
8 13 132.2 15 6 231.4
9 4 138.8 15 14 238
9 11 154.5 16 5 244.6
10 2 152.1 16 12 251.2
10 9 157.7 17 3 257.9
Required Minimum Room Area

mrcool.com 14
14
UNIT OVERVIEW
2
Mc Qmin Mc Qmin
lb oz CFM lb oz CFM
4 6 119 11 0 298
4 13 131 11 7 310
5 4 143 11 14 322
5 11 155 12 5 334
6 2 167 12 12 346
6 9 179 13 3 358
7 0 191 13 10 370
7 7 203 14 1 382
7 15 215 14 8 394
8 6 227 14 15 405
8 13 239 15 6 418
9 4 251 15 14 430
9 11 263 16 5 442
10 2 275 16 12 454
10 9 287 17 3 466
Minimum Circulation Airow
CAUTION
• The Allowable Maximum Refrigerant Charge or the Required Room Area is only used if the following
conditions are met:
• Minimum velocity of 3.28ft/s, which is calculated using the air handlers air ow divided by the nominal face
area of the outlet. The grille area should not be deducted.
• The Minimum Circulation Airow rate must correspond with the table, which is related to the actual
refrigerant charge of the system (Mc).
• The R-454B refrigerant leakage sensor is congured.
• The maximum refrigerant limit described above applies to unventilated areas. If adding additional
measures, such as areas with mechanical ventilation or natural ventilation, the maximum refrigerant
charge can be increased or the minimum room area can be reduced. The R-45B refrigerant leakage sensor
is congured for the indoor unit, meets the incorporated circulation airow requirements, the maximum
refrigerant charge or minimum room area can be determined according to the tables for the Allowable
Maximum Refrigerant Charge and the Required Minimum Room Area.
• If the actual room area, air outlet height, and refrigerant charge amount are not reected in the above
table, more severe cases need to be recongured according to the data from the tables.

mrcool.com15
3.1 Refrigerant Line
Refrigerant Line Limitations:
• Use only the line set sizes indicated in the table below to determine the required line set length.
• Do not use suction lines other than what is recommended if the line set length is greater than 50ft (15.24m).
Model
Suction
Line
Liquid
Line
Total Equivalent Length ft (m)
Dimensions in
Inches
25 (7.62) 50 (15.24) 75 (22.86) 100 (30.48) 164 (49.99)
Maximum Elevation Dierence ft (m)
MCAESHV8T2421BA 3/8 3/4 25 (7.62) 50 (15.24) 45 (13.72) 40 (12.19) /
MCAESHV9T3621BA 3/8 3/4 25 (7.62) 50 (15.24) 50 (15.24) 40 (12.19) /
MCAESHV8T4821BA 3/8 7/8 25 (7.62) 50 (15.24) 50 (15.24) 40 (12.19) 35 (10.67)
MCAESHV7T6021BA 3/8 7/8 25 (7.62) 50 (15.24) 50 (15.24) 40 (12.19) 35 (10.67)
Line Sizes & Maximum Length
Maximum Line Length =____ft (m) Maximum Elevation Dierence =____ft (m)
Refrigerant Charge
1 = Precharged part (see nameplate)
2 = Added during install
1 + 2 = Total amount
INSTALLATION
3

mrcool.com 16
Piping Length & Additional Refrigerant
Model MCAESHV8T2421BA MCAESHV9T3621BA MCAESHV8T4821BA MCAESHV7T6021BA
Length of pipe with standard
charge ft(m)
25 (7.62) 25 (7.62) 25 (7.62) 25 (7.62)
Refrigerant capacity of
standard charge lbs(kg)
4.75 (2.15) 6.28 (2.85) 8.82 (4) 8.82 (4)
Longest pipe length ft(m) 100 (30.48) 100 (30.48) 165 (50.29) 165 (50.29)
Additional refrigerant charge
lbs/ft(kg/m)
0.0335 (0.0489) 0.0335 (0.0489) 0.0335 (0.0489) 0.0335 (0.0489)
Max. di. between the indoor
and outdoor unit ft(m)
50 (15.24) 50 (15.24) 50 (15.24) 50 (15.24)
Example: a 36K model has a pipe length of 100ft. (30.48m.), the additional refrigerant charge is (100-25) x 0.0335
= 2.51 lbs. ((30.48-7.62) x 0.0489 = 1.12 kg.). The total refrigerant capacity is 6.28 + 2.51 = 8.97 lbs. (2.85 + 1.12 =
3.97 kg.)
Total Refrigerant Capacity lb (kg)
Model Category
LFL (lbs/
ft
3
)
h
0
(ft)
Pipe Length ft (m)
25 (7.62) 49 (14.94) 66 (20.12) 98 (29.87) 164 (49.99)
MCAESHV8T2421BA
R-454B 0.0185 7.2
4.74 (2.15) 5.57 (2.53) 6.12 (2.78) 7.22 (3.27) /
MCAESHV9T3621BA 6.28 (2.85) 7.11 (3.23) 7.66 (3.47) 8.76 (3.97) /
MCAESHV8T4821BA 8.82 (4) 9.65 (4.38) 10.2 (4.63) 11.3 (5.13) 13.5 (6.12)
MCAESHV7T6021BA 8.82 (4) 9.65 (4.38) 10.2 (4.63) 11.3 (5.13) 13.5 (6.12)
Minimum Room Area ft
2
(m
2
)
Model Category
LFL (lbs/
ft
3
)
h
0
(ft)
Pipe Length ft (m)
25 (7.62) 49 (14.94) 66 (20.12) 98 (29.87) 164 (49.99)
MCAESHV8T2421BA
R-454B 0.0185 7.2
71 (6.6) 26 (2.42) 28 (2.6) 33 (3.07) /
MCAESHV9T3621BA 95 (8.83) 32 (2.97) 35 (3.25) 40 (3.72) /
MCAESHV8T4821BA 40 (3.72) 44 (4.09) 47 (4.37) 52 (4.83) 62 (5.76)
MCAESHV7T6021BA 40 (3.72) 44 (4.09) 47 (4.37) 52 (4.83) 62 (5.76)
Refrigerant Line Insulation:
• The suction line must always be insulated.
• Do not allow the suction and liquid line to come
into direct contact with metal.
Liquid Line
Suction Line
Insulation
INSTALLATION
3
16

mrcool.com17
INSTALLATION
3
Note:
If using existing refrigerant lines, make sure that all
joints are brazed, not soldered.
MRCOOL® recommends that only compatible indoor and outdoor systems should be installed. All split systems
are certied by AHRI, the indoor unit is equipped with a piston or TXV, and the model of piston and TXV is
selected by MRCOOL®; please do not change those by yourself. The benets of installing a compatible indoor
and outdoor split system are maximum eciency, best performance, and best overall system reliability.
Isolated from beam/rafter:
Use isolators to x the
pipes on the beams every
8ft (2.44m). Every 8ft
(2.44m), tape, wire, or
other suitable methods
are used to x the liquid
line directly to the suction
line.
Isolated on the wall:
Use isolators to x the
suction line every 8ft
(2.44m). Every 8 ft (2.44m),
tape, wire, or other
suitable methods are
used to x the liquid line
directly to the suction
line.
Reusing Existing Refrigerant Lines
For applications where the existing refrigerant lines will be
used, the following precautions should be taken:
• Ensure the refrigerant lines are the correct size
according to the Line Size & Maximum Length table.
• It is not recommended to use a suction line that is
larger than the standard size as this can result in poor
oil return for an inverter compressor.
3.2 Refrigerant Pipeline Routing
Note:
Take preventative measures to prevent excess noise throughout the building casued by refrigerant pipline
vibrations. For example:
• When the refrigerant pipeline must be xed on oor joists or other framework, use isolated hangers.
• When the refrigerant pipeline runs in the column space or closed ceiling, the isolation hanger should also
be used.
• When refrigerant lines pass through walls or windowsills, they should be insulated and isolated.
• Isolate the pipeline from all piping systems.
• Try to reduce the number of 90° laps.
Comply with national, state, and local regulations when isolating the wire group from joists, rafters, walls, or
other structural elements.

mrcool.com 18
18
INSTALLATION
3
3.3 Refrigerant Line Connection
• The condenser has been prelled with refrigerant (check the condenser's nameplate for specic refrigerant
amounts).
• Do not use the allen wrench to open the stop valves before ensuring the pipes are connected and verify
that there are no non-condensables in the line sets.
• Do not install the line set until the air handler and condenser have been installed. Make sure to insulate the
gas and liquid line sets to prevent condensation.
• Take precautions to not damage, dent, or deform the pipe while cutting. This will reduce the heating
eciency of the system.
WARNING
Cutting Pipes:
When preparing the refrigerant lines, take precautions
to cut and are the piping properly. This will ensure
ecient operation and minimize the need for future
maintenance.
• Measure the distance between the air handler and
condenser.
• Cut the pipes longer than the measured distance.
90°
Pipe
Pipe cutter
Lean Uneven Burr
Remove Burrs:
Burrs can aect the seal on the refrigerant lines. Make
sure to completely remove them.
• Completely remove all burrs from the cross section
of the piping.
• Place the end of the copper lines in a downward
position as you remove the burrs to avoid dropping
burrs into the tubing.
Wall Isolation

mrcool.com19
Flaring:
Perform aring using a aring tool as shown.
Outside Diameter in. A in.
3/8 0.03~0.04
3/4 0.02~0.03
7/8 0.02~0.03
Flaring Dimensions
Firmly hold the copper piping in a die using the
dimensions shown in the table above.
Checking Work:
• Compare aring work with the gure shown.
• If the are is defective, cut o the ared section and repeat.
Note:
Connect piping to the air handler rst, then connect to
the condenser.
Connection:
Connect the suction line rst, then the liquid line.
1. Align the center of the two pipes you will be connecting.
2. Tighten the are nut as tight as possible by hand.
3. Use a wrench and grip the nut on the unit's tubing.
Note:
Use two wrenches to connect the piping with the air
handler/condenser to keep the copper from cracking.
4. While rmly gripping the nut, use a torque wrench to
tighten the are nut according to the torque values.
5. Insert the connecting pipe from the air handler into
the reamer transfer nozzle aring of the condenser,
and braze the connecting port.
6. Insulate all piping including the gas valve on the
condenser.
Connecting Pipe Size (in.) Torque Values (lbf*in)
3/8 327~372
3/4 620~664
7/8 690~735
Torque Values
CAUTION
Make sure to wrap insulation around the piping. Direct contact with bare piping may result in burns or
frostbite.
Make sure the pipe is properly connected. Over-torquing may damage the bell mouth and under torquing may
lead to leaks.
Check to make sure there are no refrigerant leaks after completing pipe installation. If there is a refrigerant
leak, ventilate the area immediately and evacuate the system.
INSTALLATION
3

mrcool.com 20
3.4 Leakage Check
1. Use dry nitrogen to pressurize the refrigerant line
and evaporator coil to 150 PSIG.
2. Use soapy water or foam at each soldering
position to check for leaks.
• After the completion of eld piping for split
systems, the eld pipework should be pressure
tested with an inert gas and then vacuum tested
prior to refrigerant charging, according to the
following requirements:
• Entire line set and evaporator coil should
hold 600 psig for 1 hour.
• Field-made refrigerant joints indoors should
be tightness-tested. The test method should
have a sensitivity of 5g per year of refrigerant
or better under a pressure of at least 0.25
times the maximum allowable pressure. No
leak should be detected.
WARNING
3.5 Evacuation
1. Evacuate until the micrometer reading is not
higher than 350 micrometers, and then close the
valve of the vacuum pump.
NOTE: Do not open the service valve until the
leakage inspection and emptying of refrigerant lines
and indoor coils are completed.
2. Observe the micrometer gauge. If the meter does
not rise above 500 micrometers within (1) minute,
the evacuation is completed. After the evacuation,
turn o the vacuum pump and micrometer, and
close the valve on the manifold instrument cluster.
INSTALLATION
3
20

mrcool.com21
3.6 Open the Service Valve
• When opening the liquid side service valve, be extra careful. Turn counterclockwise until the valve stem just
touches the hem. No torque is required. Failure to observe this warning will result in a sudden release of
system pressure, and may result in personal injury and/or property damage.
• Before opening the service valve, the leakage inspection and emptying must be completed. The valve of
copper welded pipe installation should be used for leakage inspection and vacuum pumping. The use of a
separate suction port in this process will lead to refrigerant loss.
• Before opening the liquid side service valve, the gas side service valve must be opened rst.
WARNING
1. Remove the valve cover.
2. Insert the hex wrench into the
valve stem completely and back out
counterclockwise until the valve stem just
touches the bead.
3. Replace the valve stem cap to prevent
leakage. Tighten it with your ngers and
turn it for another 1/6 turn.
4. Repeat steps 1-3 for the liquid side
service valve.
3.7 Low Voltage Electrical Connections
• Be cautious when opening the liquid service valve. Turn the valve counterclockwise until the valve touched
the rolled edge. No torque is required.
• Failure to follow this will result in abrupt release of the systems charge and may lead to personal injury
and/or property damage.
WARNING
Congure the maximum length of low voltage wiring
from the condenser to the air handler, then from the
air handler to the thermostat.
Field-installed conduit is required for the low voltage
wire entry point. Animals such as frogs, snakes,
spiders, etc. may climb into the control box and can
damage the PCB.
INSTALLATION
3

mrcool.com 22
22
Low Voltage Connection Diagram
Control Wiring
Wire Size Max. Wire Length
18 AWG 164ft.
Class 2 low voltage control wiring should not be run in conduit alongside the main power wiring and must be
run separately, unless class 1 wire of the proper voltage rating is used.
• Low voltage control wiring should be color-coded 18 AWG.
• Refer to the wiring diagrams attached to the air handler and condenser to be connected.
• Make sure separation between the control wiring and power wiring has been maintained.
Thermostat Wiring Diagram
INSTALLATION
3

mrcool.com23
3.8 High Voltage Electrical Connections
• During the installation, testing, maintenance, and troubleshooting of this product, it may be necessary to
use live electrical parts. Failure to observe all electrical safety precautions when exposed to live electrical
parts may result in death or serious injury.
• The high voltage power supply must match the nameplate of the unit (208/230V, 1PH, 60Hz).
• Power supply wiring must comply with national, state, and local regulations.
WARNING
Min. Circuit Ampacity
of System (A)
Min. Wire Cross-
Sectional Area mm
2
Specication of Switch
(A)
Fuse Specication (A)
≤8 0.75 15 15
>8 and ≤10 1 15 15
>10 and ≤15 1.5 20 25
>15 and ≤24 2.5 25 40
>24 and ≤28 4 35 45
>28 and ≤32 6 40 55
Dedicated Distribution Device & Wire For System
Note:
The table above is only for reference, the installation will need
to meet the requirements of local laws and regulations.
Power Supply
Model Voltage MCA MOP
MCAESHV8T2421BA
208/230V-1Ph-60Hz
16 A 25 A
MCAESHV9T3621BA 22 A 35 A
MCAESHV8T4821BA 35 A 60 A
MCAESHV7T6021BA 35 A 60 A
INSTALLATION
3

mrcool.com 24
24
INSTALLATION
3
Wiring Material Ampacity AWG
4 22
7 20
10 18
13 16
18 14
25 12
30 10
40 8
55 6
70 4
Field wiring must comply with the National Electric Code (C.E.C in Canada) and any applicable local ordinance.
Disconnect all power to the system before installing or servicing. More than one disconnect switch may be
required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death.
WARNING
Minimum Cross-Sectional Area of Power and Signal Cables
The ampacities shown above apply to appliance wiring materials with insulation rated no less than 194°F (90°C).
The supply circuit power wiring must be 167°F (75°C) minimum, copper conductors only.
It is important there is proper power available for connection of the system model that is to be installed.
Refer to the unit's nameplate, wiring diagram, and electrical data.
• Install a branch circuit disconnect of adequate size located within sight of, and readily accessible to, the unit.
• The supply circuit's power wiring must be 167°F (75°) minimum copper conductors. Refer to the electrical
data in this section for ampacity, wire size, and circuit protector requirements. Supply circuit protective
devices may either be fuses or "HACR" type circuit breakers.
Install a separate disconnect switch on the condenser. Field-provided exible electrical conduit must be used for
main power wiring.
In order to retain the warranty on the compressor, it is required that a surge protector be installed to prevent
the system from damage caused by abnormal power spikes.
High Voltage Disconnect Switch

mrcool.com25
3.9 System Startup
1. Make sure that all previous installation steps have been completed.
2. Set the thermostat to o.
3. Turn on the disconnect switch and turn on the power to the air handler and condenser.
4. Set the thermostat to on.
Attempting to use the system in conditions beyond the specied range can cause the systems protection
device to trigger and prevent operation. Use only in the following conditions.
WARNING
Mode/Temperature Heating Cooling Dry
Room Temperature 32 °F~30°F (0°C~30°C) 63°F~90°F (17°C~32°C)
Outdoor Temperature -5°F~80°F (-20°C~27°C) 5°F~125°F (-15°C~125°C)
With the power supply connected, restart the system after shutdown, or switch it to a dierent mode during
operation. This will allow the system's protection device to reset and resume operation after 3 minutes.
High Voltage Grounding
Ground the outdoor unit according to the requirements of national, state, and local regulations.
Preheating: When the heating function is enabled, the indoor unit will take 2~5 minutes to preheat. Once the
preheating operation is complete, the system will start heating.
Defrosting: During heating operating the condenser will frost and the system will enable an automatic
defrosting function to defrost itself. During this cycle, the air handler and condenser fans will cease operation.
The system will resume its normal operation automatically once this cycle is complete.
Heating Operation:
INSTALLATION
3

mrcool.com 26
4.1 System Display
Condenser Main PCB LED Display & Fault Table
The LED on the main control board can display the operating status of the condenser.
DSP1-1 DSP1-2 DSP1-3
DSP1-1/DSP1-2: Normally blank, but it displays codes accordingly if there is a
damaged sensor or command response.
See the fault code table below.
DSP1-3: Displays the outdoor unit's operation mode.
DSP1-3 Code Description
0 Standby
1 Ready
2 Cooling
3 Cooling
4 Oil Return Operation
5 Defrosting Operation
6 Forced Defrost
7 Forced Cooling Operation
8 Forced Heating Operation
A Fault
H Dehumidication Mode
Operation
DSP1-3: Displays Condenser's Operation Mode Dip Switch Settings
SW1 Dip Switch Description
No.
Setting
Item
Status Content
SW1-1
Single
Cooling/
Heat Pump
On AC Outdoor Unit
Digit HP Outdoor Unit
SW1-2
Operating
Capacity
On Lower Capacity
Digit Normal Capacity
SW1-3
SW1-4
Control
Mode
On
485
Communication
Digit 24V On/O Control
POST-INSTALLATION
4

mrcool.com27
Error Code Description
E0
Communication failure between air
handler and condenser
E1
Air handler environment
temperature sensor failure
E2
Air handler fan coil temperature
sensor failure
E3
Condenser fan coil temperature
sensor failure
E4 Low refrigerant charge
E5 Model conguration error
E6 Air handler PG/DC fan failure
E7
Condenser ambient temperature
sensor failure
E8
Condenser exhaust temperature
sensor failure
E9
Condenser IPM module failure/
compressor drive failure
EA Condenser current sensor failure
Eb
Main control board and display
screen communication failure
EC
Condenser module communication
failure
EE Condenser EEPROM fault
EF Condenser DC fan failure
EH Condenser air intake sensor failure
EP Compressor shell top failure
EU Condenser voltage sensor failure
Ej
Condenser middle coil temperature
sensor failure
En
Condenser air pipe temperature
sensor failure
Ey
Condenser liquid pipe temperature
sensor failure
FA
Compressor phase current
detection fault
Fb
Refrigeration and heating overload
protection
FC
Reduced frequency power overload
protection
FE
Reduced/frequency module
current (compressor phase current)
protection
FF
Reduced/frequency module
temperature protection
FH Reduced/frequency drive protection
FP Dewdrop protection
Error Code Description
FU Frost protection
P0 IPM module protection
P1 Over and under voltage protection
P2 Overcurrent protection
P3 Other protections
P4
Condenser exhaust temperature is
too high
P5 Refrigerant anti-freezing protection
P6
Refrigerant anti-overheating
protection
P7
Heating and anti-overheating
protection
P8
Condenser temperature too high or
too low protection
P9
Compressor drive protection
(abnormal load)
PA
Top outlet wind plate
communication fault/mode conict
F0 Infrared sensing sensor failure
F1 Electricity module failure
F2 Exhaust temperature sensor failure
F3
Outer pipe temperature sensor bag
failure protection
F4
Refrigerant circuit abnormal
protection
F5 PFC protection
F6
Compressor missing/reverse phase
protection
F7 Module temperature protection
F8
Four-way valve reversing abnormal
protection
F9
Module temperature sensing circuit
failure
Fj
Reduced frequency exhaust
protection
Fn
Reduced frequency external
machine AC current protection
Fy
Reduced frequency lack of uorine
protection
H1 High-pressure switch malfunction
H2 Low-pressure switch malfunction
H3 High-pressure sensor failure
H4 Low-pressure sensor failure
Hd
Air handler refrigerant leak
protection
POST-INSTALLATION
4
4.2 Error Codes

mrcool.com 28
28
POST-INSTALLATION
4
4.3 Components
Name Symbol Function
Inverter Compressor INV
Adjusts refrigerant ow rate by changing the speed (RPS) based on objective
pressure.
DC Motor FAN
Outputs heat exchanger capacity by adjusting the motor rotation speed based on
operation pressure.
Electronic Expansion
Valve
EEV
1. Fully open in cooling mode and defrost.
2. Controls compressor discharge superheat in heating mode.
Reversing Valve ST1 (RV)
Switches the operation mode between heating and cooling (including defrost
control).
Temperature Sensor
TH Controls defrost during heating operation.
TA Detects the outdoor ambient temperature and controls the fan speed.
TL Detects the liquid line temperature and calculates sub-cooling (SC).
TD
Detects the compressor discharge temperature and calculates discharge superheat
(DSH).
TF Detects the heat sink temperature of the inverter module.
High Pressure Switch HP Detects high pressure.
Low Pressure Switch LP Detects low pressure.
Accumulator ACC Prevents the compressor from ingesting liquid refrigerant.

mrcool.com29
POST-INSTALLATION
4
4.4 Troubleshooting
CAUTION
If one of the following conditions occur, turn power to the system o immediately and contact a technician or
support for further assistance.
• The operation light continues to ash rapidly after the system has been restarted.
• The unit continually trips fuses or circuit breakers.
• A foreign object or water enters the system.
• The indoor unit leaks.
• Other abnormal situations.
The following symptoms are not malfunctions and in most situations will not require repairs.
Problem Possible Cause
Abnormal condenser
noise.
The unit will make dierent sounds based on its operation mode.
Both condenser and air
handler make noise.
The system may hum during operation. This is normal in operation that is caused by refrigerant
gas owing through the system.
When the system is stopped or in heat mode a hiss may be heard. This sound is normal and is
caused by the refrigerant stopping or changing direction through the reversing valve.
The system does not
turn on when pressing
the On/O button.
The system has a 3 minute protection that prevents the unit from overloading. The system
cannot be restarted within 3 minutes of being turned o.
Cooling and heating modes: If the operation light and PRE-DEF (Pre-heating/Defrost) indicators
are shows, the outdoor ambient temperature is too low and the unit's anti-cold wind function is
activated in order to defrost the system.
The unit changes from
COOL mode to FAN
mode.
The system changes settings to prevent frost from forming. Once the temperature increases,
the unit will start operating again.
Both air handler and
the condenser emit a
white mist.
When the unit restarts in HEAT mode after defrosting, white mist may be emitted due to
moisture generated from the defrosting process.
Dust is emitted from
either the air handler or
condenser.
The unit may accumulate dust during extended periods of non-use which can circulate once
the system is powered on. This can be mitigated by covering the unit during long periods of
inactivity.
The unit emits a bad
odor.
The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.)
which will be circulated during operation.
The air handlers air lter has become moldy and should be cleaned.
The fan of the outdoor
unit does not operate.
During operation, the fan speed is controlled to optimize operation.

mrcool.com 30
30
POST-INSTALLATION
4
When some of the issues below occur, please check the following points before contacting a technician.
Problem Possible Cause Solution
The system is not
working.
Power failure Wait for power to be restored.
The power switch is o Turn on the power.
The fuse is burned out Replace the fuse.
The unit's 3-minute protection has been
activated
Wait three minutes after restarting the system.
Poor cooling
performance
The temperature setting may be higher than
the ambient room temperature
Lower the temperature setting.
The coils on the air handler or condenser is
dirty
Clean the coils.
The air lter is dirty Remove the air lter and clean/replace.
The air inlet or outlet of either unit is blocked
Turn the system o, remove the obstruction,
and turn the system back on.
Doors and windows are open
Make sure that all doors and windows are
closed while operating the unit.
Excessive heat is generated by sunlight
Close windows and curtains during periods of
high heat or bright sunshine.
Low refrigerant due to a leak
Check for leaks, re-seal if necessary, and top
o refrigerant (Contact a service technician).
The system starts and
stops frequently
There is too much or too little refrigerant in
the system
Check for leaks and recharge the system with
refrigerant. (Contact a service technician).
There is air, incompressible gas or a foreign
material in the system
Evacuate and recharge the system with
refrigerant.
System circuit is blocked
Determine which circuit is blocked and replace
the malfunctioning piece of equipment.
The compressor is broken Replace the compressor
The voltage is too high or too low
Install a manostat voltage regulator to regulate
the voltage.
Poor heating
performance
The outdoor temperature is lower than 44.5°F
(6.9°C)
Check for leaks and recharge the system with
refrigerant.
Cold air is entering through doors and
windows
Make sure that all doors and windows are
closed during use.
Low refrigerant due to a leak
Check for leaks, re-seal if necessary, and top
o refrigerant.

mrcool.com31
POST-INSTALLATION
4
4.5 Schematic

MRCOOL
®
Signature Series
TruInverter™
Split System Heat Pump
The design and specications of this product and/or manual are subject to change without prior notice.
Consult with the sales agency or manufacturer for details.