Goodman MBVB16CP1X00 MBVB 4 Ton, 21" Wide, Variable Speed Modular Blower for Electric Furnace

Product's Documents

Below are documents related to this product, you can read online or download:
MBVB16CP1X00 photo

Specification

This is the main product document for model MBVB16CP1X00. Additionally, the document applies to other Goodman models: MBVB16CP1X00

The file format is pdf, 8 pages, you can download this manual here .

background
SS-GMBVB www.goodmanmfg.com 10/23
* Complete warranty details available from your local dealer or at www.goodmanmfg.com. To receive the 10-Year Parts Limited Warranty,
online registraon must be completed within 60 days of installaon. Online registraon is not required in California or Québec.
The duraon of warranty coverage in Texas and Florida diers in some cases..
MBVB
Multi-position, Variable speed
ECM-based, Modular Blower
Comfortbridge
TM
Compatible
■ Product Features ■ Cabinet Features
• Variable-speed ECM blower motor
• Integrated communicang
ComfortBridge™ Technology
• Commissioning and diagnoscs via
on board Bluetooth with the CoolCloud™
phone and tablet applicaon
• Advanced conguraon of the airow
and tonnage in communicang mode
• Provides constant CFM over a wide
range of stac pressure condions
independent of duct system
• CFM indicator
• Fault recall of six most recent faults
• Provides adjustable low CFM for ecient
fan-only operaon
• Improved humidity and comfort control
• Built-in compability with mul-stage heat
pump and cooling applicaons
• UL 60335 2-40 Compliant
• AHRI cered; ETL listed
• Blower secon usable as electric heater
• Horizontal or vercal conguraon capabilies
• 21” depth for easier ac access
• Foil-faced insulaon covers the internal
casing to reduce cabinet condensaon
• Galvanized, leather grain-embossed nish
• Cabinet air leakage less than 2% at
1.0 inch H₂0 when tested in accordance
with ASHRE standard 193
• Cabinet air leakage less than 1.4% at
0.5 inch H₂0 when tested in accordance
with ASHRE standard 193
• Field Installed 3 kW – 20 kW electric
heater kits available
■ Contents
Air Handler Nomenclature .................... 2
Heater Kit Nomenclature .......................2
Product Specicaons ........................... 3
Airow Data ............................................4
Heat Kit Data ........................................... 5
Dimensions ............................................6
Wiring Diagram .......................................7
Accessories .............................................8
background
2 www.goodmanmfg.com SS-GMBVB
SS-GMBVB www.goodmanmfg.com 3
Nomenclature
M B V B 1 2 B P 1 X 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Minor Revision
Brand
A
MB - Modular Blower
Major Revision
A
Factory Installed Electric Heat KW
00 -No Electric Heat
Motor Speed
V - Variable
Circuit Breaker
X - No Circuit Breaker
Communicating Controls Protocol
B - ComfortBridge
Electrical
K - ClimateTalk
1 208/230 V, 1 Phase, 60 Hz
Airflow Delivered Cabinet
12 - 1200 cfm P - Painted
16 - 1600 cfm
20 - 2000 cfm
Cabinet Width
B - 17.5"
C - 21.0"
D - 24.5"
H K T A D 2 5 D 1
1 2 3 4 5 6 7 8 9
Unit Type
Electrical
HKTA - Electric heater
Kit for 2-piece air handlers
A - Single phase 208 V
B - Single phase 240 V
1 - Single phase 208/240 V
Service Disconnect
3 - Three phase 208/240 V
D - Service disconnect
N - No service disconnect
Cabinet Size
X - All Cabinets C - C Cabinet
D - D Cabinet
Heang Capacity @ 240 V
3 3.00 kW 6 6.00 kW 10 10.00 kW
5 5.00 kW 8 7.00 kW 15 15.00 kW
20 20.00 KW
background
2 www.goodmanmfg.com SS-GMBVB
SS-GMBVB www.goodmanmfg.com 3
Product Specifications
Model MBVB12BP1X00 MBVB16CP1X00 MBVB20DP1X00
Blower
Diameter 10" 10" 11"
Width 8" 8" 10"
Electrical Data
Voltage (V) 208/230 208/230 208/230
MCA (A) 4.9 6.5 6.5
MOP (A) 15
Blower Motor Power (HP) ½ ¾ ¾
Dimensions
Width 17½" 21" 24½"
Depth 21" 21" 21"
Height 26" 30" 30"
Ship Weight (Lbs.) 67 80 86
• Minimum Circuit Ampacity and Maximum Overcurrent Protecon Device (MOD) for blower without supplemental heat installed.
Refer to unit nameplate for these specicaons with approved accessory heaters installed.
• Condensate management kits are available for units installed in high temperature and high humidity areas. Kit number MBK0002
has been developed to resolve condensate issues in the eld and is available from the Service Parts Department. Refer to IO-849
for installaon instrucons.
background
4 www.goodmanmfg.com SS-GMBVB
SS-GMBVB www.goodmanmfg.com 5
Airflow Data
Model Speed Tap Speed 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
MBVB12
BP1X00A*
A Low 420 415 400 400 395 390 390 390 380
B Low 550 545 540 540 535 530 530 525 520
C Low 680 675 670 665 660 655 655 650 640
D Low 810 805 800 800 800 795 790 785 785
A High 615 605 600 600 595 590 590 585 580
B High 805 805 800 800 800 795 790 785 780
C High 1010 1005 1000 1000 995 995 990 985 975
D High 1210 1205 1200 1200 1200 1195 1195 1190 1180
MBVB16
CP1X00A*
A Low 690 680 670 665 660 655 625 595 575
B Low 850 830 800 795 790 785 775 750 725
C Low 980 970 940 935 930 910 890 865 860
D Low 1110 1085 1070 1055 1045 1025 1000 990 975
A High 1045 1015 1000 990 975 950 935 920 900
B High 1245 1215 1200 1180 1175 1165 1150 1130 1115
C High 1415 1410 1400 1365 1360 1350 1340 1330 1320
D High 1605 1600 1600 1540 1530 1520 1510 1500 1490
MBVB20
DP1X00A*
A Low 835 815 800 800 795 795 790 775 750
B Low 1075 1070 1070 1065 1050 1045 1045 1040 1035
C Low 1210 1205 1200 1200 1195 1190 1190 1185 1175
D Low 1345 1340 1340 1320 1320 1315 1315 1305 1305
A High 1210 1205 1200 1195 1150 1150 1145 1135 1115
B High 1610 1605 1600 1540 1535 1535 1530 1520 1510
C High 1830 1805 1800 1785 1760 1760 1755 1750 1715
D High 2020 2010 2000 1995 1995 1970 1970 1965 1955
Cooling and Heat Pump Airflow
S1 S2 Speed Tap
MBVB12BP1X00
Airflow (SCFM)
MBVB16CP1X00
Airflow (SCFM)
MBVB20DP1X00
Airflow (SCFM)
o o A 600 1000 1200
on o B 800 1200 1600
o on C 1000 1400 1800
on on D 1200 1600 2000
Cooling / HP / Aux Trim Cooling Profile
S3 S4 Trim Value S5 S6
o o 0 o o A
on o 10% on o B
o on -10% o on C
on on 0 on on D
Heat Kit Airflow
S9 S10 S11 Heater KW
MBVB12BP1X00
Airflow (SCFM)
MBVB16CP1X00
Airflow (SCFM)
MBVB20DP1X00
Airflow (SCFM)
o o on 20 NA NA 2000
o on o 15 1400 1500 1500
o on on 10 1000 1000 1200
on o o 8 740 1000 1000
on o on 6 635 800 800
background
4 www.goodmanmfg.com SS-GMBVB
SS-GMBVB www.goodmanmfg.com 5
Models
Circuit 1 (208V/240V) Circuit 2 (208V/240V)
Single-Point Kit
(208V/240V)
Heater Amps MCA¹ MOP² Heater Amps MCA¹ MOP² MCA¹ MOP²
MBVB12BP1X00AB
HKTAN031
HKTA*051
HKTAN061
HKTA*081
HKTA*101
HKTAD151
0/0
10.8/12.5
18.1/20.8
21.7/25.0
25.3/29.2
36.1/41.7
36.1/41.7
4.9/4.9
18.4/20.5
27.4/30.9
32.0/36.1
36.5/41.3
50.0/57.0
50.0/57.0
15/15
20/25
30/35
35/40
40/45
50/60
50/60
---
---
---
---
---
---
18/20.8
---
---
---
---
---
---
22.5/26.0
---
---
---
---
---
---
25/30
---
---
---
---
---
---
72.6/83.0
---
---
---
---
---
---
80/90
MBVB16CP1X00AB
HKTAN031
HKTA*051
HKTAN061
HKTA*081
HKTA*101
HKTAD151
0/0
10.8/12.5
18.1/20.8
21.7/25.0
25.3/29.2
36.1/41.7
36.1/41.7
6.5/6.5
20.0/22.1
29.1/32.5
33.6/37.8
38.1/43.0
51.6/58.6
51.6/58.6
15/15
20/25
30/35
35/40
40/45
60/60
60/60
---
---
---
---
---
---
18/20.8
---
---
---
---
---
---
22.5/26.0
---
---
---
---
---
---
25/30
---
---
---
---
---
---
74.2/84.6
---
---
---
---
---
---
80/90
MBVB20DP1X00AB
HKTAN031
HKTA*051
HKTAN061
HKTA*081
HKTA*101
HKTAD151
HKTAD201
0/0
10.8/12.5
18.1/20.8
21.7/25.0
25.3/29.2
36.1/41.7
36.1/41.7
36.1/41.7
6.5/6.5
20.0/22.1
29.1/32.5
33.6/37.8
38.1/43.0
51.6/58.6
51.6/58.6
51.6/58.6
15/15
20/25
30/35
35/40
40/45
60/60
60/60
60/60
---
---
---
---
---
---
18/20.8
36.1/41.7
---
---
---
---
---
---
22.5/26.0
45.2/52.1
---
---
---
---
---
---
25/30
50/60
---
---
---
---
---
---
74.2/84.6
96.8/111
---
---
---
---
---
---
80/90
100/125
All ampacies noted above include air handler motor amps
Circuit 1: Single-phase for Air Handlers / Circuit 2: Three-phase for HKR3 Heater Kits
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protecon = 2.25 X Motor Amps + Heater Amps
* D - Service disconnect, N - No service disconnect
--- indicates Not Required
Heat Kit Data
Heating kW Correction Factor
Supply Voltage 240 230 220 210 208
Correction Factor 1.00 0.92 0.84 0.77 0.75
Mulply the 240-volt heang capacity by correcon factors.
background
6 www.goodmanmfg.com SS-GMBVB
SS-GMBVB www.goodmanmfg.com 7
Dimensions
MBVC_TOP_VIEWS
9 8 7 6 5 4 3 2 1
9 8 7 6 5 4 3 2 1
F
C
D
E
B
A
F
C
D
E
B
A
SC
CC
11.3"
11.1"
20.0"
10.9"
16.5"
10.3"
13.2"
11.3"
23.5"
SPECIAL CHARACTERISTICS: (REFER MSP 822-01 FOR DETAILS)
= CRITICAL CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.33 AND USE OF STATISTICAL PROCESS CONTROL.
= SIGNIFICANT CHARACTERISTIC REQUIRES AN INITIAL CPK OF 1.00 AND USE OF STATISTICAL PROCESS CONTROL.
INABILITY TO MEET THE REQUIRED INITIAL CPK VALUE WILL REQUIRE 100% INSPECTION.
COMPONENTS AND MATERIALS SPECIFIED HEREIN WILL ALSO CONFORM TO THE APPLICABLE SECTION OF GOODMAN MSP
860-01 WORKMANSHIP STANDARD.
CONFIDENTIAL PROPERTY OF GOODMAN MANUFACTURING COMPANY, L.P. OR ITS AFFILIATES NOT TO BE DISCLOSED TO
OTHERS, COPIED, OR USED FOR ANY PURPOSE EXCEPT AS AUTHORIZED IN WRITING. MUST BE RETURNED UPON DEMAND,
ON COMPLETION OF ORDER, OR OTHER PURPOSE FOR WHICH IT WAS LENT
GOODMAN MANUFACTURING COMPANY,L.P.
DRAWING TO BE INTERPRETED IN
ACCORDANCE WITH ASME Y14.100
TITLE
MBVC_DIMENSIONS
DIMENSIONS ARE IN INCHES
UNLESS OTHERWISE NOTED.
TOLERANCES UNLESS
OTHERWISE NOTED
ANGLES 1.5
.X .1
.XX .03
.XXX .015
HOLES : .005
TUBE CUT LG: .063
DWN: HCL-BS ENG: SCALE: NTS
DATE: CHK: SHEET: 1 OF 1
DWG.
NO.
MBVC_TOP_VIEWS
21"
17½"
24½"
Model
Dimensions
Width Depth Height
MBVB12BP1X00 17½" 21" 26"
MBVB16CP1X00 21" 21" 30"
MBVB20DP1X00 24½" 21" 30"
Top View
Side and Front Views
W"
H"
D"
10.9"
16.5"
4.0 (10.6 cm)
2.5" (6.35 cm) 2.5" (6.35 cm)
4.0 (10.6 cm)
10.3
5.8" (14.73 cm)
7.3" (18.54 cm)
17½"
4.0" (10.6 cm)
5.8" (14.73 cm)
7.3" (18.54 cm)
2.5" (6.35 cm)16.1" (40.89 cm)
11.3"
11.1"
20.0"
4.0" (10.6 cm)
21"
4.0" (10.6 cm)
5.8" (14.73 cm)
7.3" (18.54 cm)
2.5" (6.35 cm)19.6" (49.78 cm)
4.0" (10.6 cm)
13.2"
11.3"
23.5"
24½"
background
6 www.goodmanmfg.com SS-GMBVB
SS-GMBVB www.goodmanmfg.com 7
Wiring Diagram – Air Handler
⚠ Warning
High Voltage: Disconnect all power before servicing or installing this unit. Mulple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
TB3
TB4
TB7
DH/
Y2
GR
C
Y
W
R1
2C
CIRCULATOR BLOWER
1
1
CIRCULATOR
CIRCULATOR
RD
WH
TO
MICRO
AUX IN
AIR
230 VAC
PL1
SEE
NOTE 7
DEHUM
24 VAC
RD
4
BLWR
5
AIR
40 VA
8
40 VA TRANSFORMER, SEE NOTES 1 AND 14
L1
9
INDOOR
7
24 VAC
4
BK
1
5
BL
PL2
FUSE 3 A
208/230 VAC
GRND
ECM MOTOR
HARNESS
GRND
6
L2
6
L1
COM
BR
G
INTEGRATED CONTROL MODULE
W
BK
3
24V THERMOSTAT CONNECTIONS
COM
L2
DISCONNECT
BL
BK
TR2
C
3
GRND (4)
2
2
INDOOR
9
RD
TH2
+VDC (1)
Y
208 VAC
BK
RX (2)
RD
GRND
GRND
4
GN
R
8
5
EH1
RD
TX (3)
BL
3
GRND
ELECTRIC STAGE 2
RD
TRANSFORMER
ELECTRIC HEAT STAGE 1
GN
7
2
BLWR
EQUIPMENT GRND
TERMINAL
PLUG CONNECTION
LOW VOLTAGE FIELD
HI VOLTAGE FIELD
JUNCTION
HI VOLTAGE (230V)
PROT. DEVICE
INTEGRATED CONTROL
LOW VOLTAGE (24V)
FIELD SPLICE
INTERNAL TO
FIELD GRND
OVERCURRENT
0140A01418-A
1
2
3
CONDENSATE SWITCH
AUX OUT
EH2
RESISTOR
43
2
1
SEE NOTE 9
4 - GND
NC
SEE NOTE 6
GY PU
WH
GR BL RD BL RD GY BK
THERMOSTAT
OUTDOOR UNIT
(SEE NOTE 13)
NOTES:
1. PLACE RED WIRES ON TRANSFORMER TERMINAL 2 FOR 208 VAC OPERATION.
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C AND LOCAL CODES.
5. TO RECALL THE LAST 6 FAULTS, DEPRESS THE RIGHT PUSH BUTTON FROM STATUS MENU ONCE AND THEN USE THE LEFT OR RIGHT
BUTTON TO REVIEW ALL THE FAULTS HISTORY.
6. 2 GREEN LEDS INDICATES CLIMATE TALK AND DATA AC NETWORK TRAFFIC STATUS. USE LEARN MENU FOR CLIMATE TALK NETWORK
RESET.
7. DISCARD CONNECTOR PL1 W HEN INSTALLING OPTIONAL HEAT KIT.
8. THE CONDENSATE ALARM SWITCH (AUX) TERMINALS CAN ONLY BE UTILIZED WITH COMMUNICATING MODE SETUPS AND MUST BE
ENABLED WITH COMMUNICATING THERMOSTAT. THIS FEATURE IS NOT OPERATIONAL WITH NON COMMUNICATING SYSTEMS.
9. USE N.E.C CLASS 2 WIRE.
10. SEE MANUAL FOR PUSH BUTTON OPERATION.
11. SEE MANUAL FOR 7-SEGMENT DISPLAY DIAGNOSTIC CODES AND MENU CODES.
12. SEE MANUAL FOR LEDS FUNCTIONALITY
13. R AND C TERMINALS (USED FOR 24VAC OUTDOOR CONTROL VOLTAGE) ARE OPTIONAL FOR 2 STAGE COMMUNICATING AIR
CONDITIONERS. R AND C TERMINALS ARE NOT TO BE USED FOR 2 STAGE COMMUNICATING HEAT PUMP APPLICATIONS.
FOR COMMUNICATING HEAT PUMP OR IF ONLY TWO THERMOSTAT WIRES ARE AVAILABLE, A SEPARATE TRANSFORMER MUST BE
INSTALLED IN THE OUTDOOR UNIT FOR CONTROL BOARD POWER.
1 AND 2 WIRES ARE REQUIRED FOR ALL APPLICATIONS. SEE INSTALLATION MANUAL FOR FULL SYSTEM WIRING EXAMPLES.
14. LOW VOLTAGE TRANSFORMER RATED 24VAC OUTPUT 40VA @ AMP 1.67A
BL ---- BLUE
PK ---- PINK
GY ---- GRAY
WH ----WHITE
BR ---- BROWN
COLOR CODES:
OR ---- ORANGE
RD ---- RED
PU ---- PURPLE
YL ---- YELLOW
GN ---- GREEN
BK ---- BLACK
208 / 230 VAC
III
READ THE INSTRUCTIONS
CLASS III
III
SEE NOTES 1 AND 14
background
8 www.goodmanmfg.com SS-GMBVB
SS-GMBVB www.goodmanmfg.com PB
Our connuing commitment to quality products may mean a change in specicaons without noce.
©2023 • Houston, Texas • Printed in the USA.
Accessories
Single Point Kit
HKTAD151 HKTAD201
SPW-01 X X
Can only be installed along with the above heat kits. This kit will t any MBVK blower as long
as a compable heat kit is installed in the unit.
MBVB Blower Performance Data Dipswitch Summary
Dipswitch Number Funcon Default Seng
S1 - S2*
Cooling / HP Airow
A/B/C/D
Airow D
S3 - S4*
Cooling / HP / Aux Trim
(-10%, 0, +10%)
No Trim
S5 - S6*
Cooling Prole
A,B,C,D
Prole 1
S7*
Dehum
(on/o)
O
S8 Unused On
S9 - S11 Heater Kit Kw O/O/O
* Valid only if the system is wired in legacy mode. If system is wired in the 4-wire communicang
mode, these funcons are selected via the user menu in the CTK01AA T-STAT.
Heat Kit Selection
Model MBVB12BP1X00 MBVB16CP1X00 MBVB20DP1X00
HKTAN031 X X X
HKTAN051 X X X
HKTAD051 X X X
HKTAN061 X X X
HKTAN081 X X X
HKTAD081 X X X
HKTAN101 X X X
HKTAD101 X X X
HKTAD151 X X X
HKTAD201 --- --- X
Refer to the minimum airow requirements for each of the heat kits.
--- Indicates Not Permied

Specifications

Goodman MBVB16CP1X00 Questions and Answers

Questions and Answers

Related Products