Goodman HKTPD051 HKTP 5 kW Electric Heat Kit with Circuit Breaker for Packaged Units

Product's Documents

Below are documents related to this product, you can read online or download:
HKTPD051 photo

Installation Manual

This is the main product document for model HKTPD051. Additionally, the document applies to other Goodman models: HKTPD051, 8 KW, 10 KW, 15 KW, 19 KW, 20 KW

The file format is pdf, 28 pages, you can download this manual here .

background
PACKAGED AIR CONDITIONING UNITS
GPCM3 13.4 SEER2 “M” SERIES WITH R-32
INSTALLATION INSTRUCTIONS
IOG-1077
03/2025
WARNING
DO NOT BYPASS SAFETY DEVICES.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL,
ADJUST, SERVICE, MAINTENANCE OR REPAIR
(HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN
THIS MANUAL SHOULD SERVICE THE EQUIPMENT.
THIS EQUIPMENT IS NOT INTENDED FOR USE BY
PERSONS (INCLUDING CHILDREN) WITH REDUCED
PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR LACK
OF EXPERIENCE AND KNOWLEDGE, UNLESS THEY HAVE
BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING
USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR
THEIR SAFETY.
CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT
THEY DO NOT PLAY WITH THE EQUIPMENT.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR
ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SUPERVISION, SERVICE OR SERVICE
PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME
RESPONSIBILITY FOR ANY INJURY OR PROPERTY
DAMAGE WHICH MAY RESULT. IN ADDITION, IN
JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES
TO SERVICE THE EQUIPMENT SPECIFIED IN THIS
MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE
THE EQUIPMENT. IMPROPER SUPERVISION, INSTALLATION,
ADJUSTMENT, SERVICING, MAINTENANCE OR REPAIR OF
THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR
ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR
THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT
PROPER SUPERVISION OR TRAINING MAY RESULT IN
PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL
INJURY OR DEATH.
WARNING
NOTE: This equipment is approved to use only with
R-32 Refrigerant.
Our continuing commitment to quality products may mean a change in specications without notice.
© 2025 Daikin Comfort Technologies Manufacturing, L.P.
19001 Kermier Rd. Waller, TX 77484
www.goodmanmfg.com
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
background
2
TABLE OF CONTENTS
To the Installer .............................................................2
Shipping Inspection .......................................................2
Transportation Damage ..........................................2
Message to the Homeowner ...................................2
Replacement Parts .......................................................3
Ordering Parts .........................................................3
Important Safety instructions ...................................3
Recognize Safety Symbols, Words and Labels .3
General Information ....................................................4
EPA Regulations .......................................................5
National Codes .........................................................5
Major Components ................................................... 5
Pre-Installation Checkpoints ................................ 5
Unit Location..................................................................6
Clearances and Accessibility ................................6
Roof Top Installation Details ...............................6
Roof Curb Installations Only ...............................7
Rigging Details .........................................................7
Circulating Air and Filters ......................................... 8
Air Flow Conversion ...............................................8
Horizontal Air Flow.................................................8
Down Discharge Applications................................9
Ducting .......................................................................9
Connecting the Return and Supply Flexible
Duct in Manufactured or Modular Housing
Application.................................................................9
Plenum Application .................................................10
Filters .............................................................................10
Condensate Drain Piping.............................................10
Electrical Wiring ........................................................10
High Voltage Wiring ................................................12
Low Voltage Wiring ................................................12
Internal Wiring ........................................................12
Start-up Procedure and Checklist ..........................12
Air Conditioner Start Up Procedure ..................12
Final System Checks ...............................................12
Components ...................................................................13
Contactor .................................................................13
Crankcase Heater ...................................................13
Condenser Motor ....................................................13
Compressor ..............................................................13
Contactor Relay.......................................................13
Defrost Control .....................................................13
Outdoor Thermostat ..............................................13
Reversing Valve Coil ..............................................13
Indoor Blower Motor ............................................13
Blower Interlock Relay ........................................13
Defrost Control .....................................................13
Suggested Field Testing/Troubleshooting ............13
Testing Defrost Control.......................................13
Testing Defrost Thermostat ................................. 14
Airflow Measurement and Adjustment ...................14
Total External Static Pressure ...........................14
Adjusting Speed Tap for ID Blower Motor .............15
EEM Motor ................................................................15
GPCM3 CFM Delivery and Adjustments ..............15
GPCM3 Thermostat “Fan Only” Mode ..................15
Superheat and Subcooling .........................................15
TO THE INSTALLER
Carefully read all instructions for the installation prior to
installing unit. Make sure each step or procedure is un-
derstood and any special considerations are taken into
account before starting installation. Assemble all tools,
hardware and supplies needed to complete the installa-
tion. Some items may need to be purchased locally. After
deciding where to install unit, closely look the location
over – both the inside and outside of the home. Note any
potential obstacles or problems that might be encountered
as noted in this manual. Choose a more suitable location if
necessary.
IMPORTANT NOTE: IF A CRANKCASE HEATER IS
USED, THE UNIT SHOULD BE ENERGIZED 24 HOURS
PRIOR TO COMPRESSOR START UP TO ENSURE
CRANKCASE HEATER HAS SUFFICIENTLY WARMED
THE COMPRESSOR. COMPRESSOR DAMAGE MAY
OCCUR IF THIS STEP IS NOT FOLLOWED.
Before using this manual, check the serial plate for proper
model identication.
The installation and servicing of this equipment must be
performed by qualied, experienced technicians only.
SHIPPING INSPECTION
Transportation Damage
Upon receiving the unit, inspect it for damage from
shipment. Claims for damage, either shipping or
concealed, should be led immediately with the shipping
company. Check the unit model number, specications,
electrical characteristics, and accessories to determine if
they are correct. In the event an incorrect unit is shipped,
it must be returned to the supplier and must NOT be
installed. The manufacturer assumes no responsibility for
installation of incorrectly shipped units.
Message to the Homeowner
These instructions are addressed primarily to the installer;
however, useful maintenance information is included and
should be kept, after installation, for future reference.
Checking Subcooling .............................................15
Checking Superheat ................................................15
Superheat Adjustment ...........................................15
Refrigerant Charge Check ...................................15
Units with Expansion Valve (TXV)..........................15
RDS Function.............................................................16
RDS Operation...........................................................16
Electric Heat Installation & Adjustment ................18
Heater Kit ..................................................................18
Maintenance ..................................................................18
Troubleshooting Code................................................20
Troubleshooting Chart .............................................. 21
Blower Performance Data .........................................22
Unit Dimensions ............................................................24
Wiring Diagrams...........................................................25
Homeowner’s Routine Maintenance .........................26
Start-Up Checklist ....................................................... 28
background
3
REPLACEMENT PARTS
Ordering Parts
When reporting shortages or damages, or ordering repair
parts, give the complete unit model and serial numbers
as stamped on the unit’s nameplate. Replacement parts
for this appliance are available through your contractor or
local distributor. For the location of your nearest distributor,
consult:
HOMEOWNER’S SUPPORT
DAIKIN COMFORT TECHNOLOGIES
MANUFACTURING, L.P.
19001 KERMIER ROAD
WALLER, TEXAS 77484
(855) 770-5678
IMPORTANT SAFETY INSTRUCTIONS
Recognize Safety Symbols, Words, and Labels
The following symbols and labels are used throughout this
manual to indicate immediate or potential hazards. It is the
owner’s responsibility to read and comply with all safety
information and instructions accompanying these symbols.
Failure to heed safety information increases the risk of
serious personal injury or death, property damage and/or
product damage.
Cabling
Check that cabling will not be subject to wear, corrosion,
excessive pressure, vibration, sharp edges or any other
adverse environmental e󰀨ects. The check shall also take
into account the e󰀨ects of aging or continual vibration from
sources such as compressors or fans.
WARNING
Do not connect to or use any device that is not listed in the
applicable product specifications as acceptable for use with
this unit. Serious property damage, personal injury, reduced
unit performance and/or hazardous conditions may result
from the use of such non-approved devices.
WARNING
HIGH VOLTAGE!
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
WARNING
Connecting unit ductwork to unauthorized heat producing
devices such as a fireplace insert, stove, etc. May result
in property damage, fire, carbon monoxide poisoning,
explosion, personal injury or death.
WARNING
To avoid property damage, personal injury or death, do not
use this unit if any part has been under water. Immediately
call a qualified service technician to inspect the unit and to
replace any part of the control system and any gas control
having been under water.
WARNING
This unit must not be used as a “construction heater” during
the finishing phases of construction on a new structure.
This type of use may result in premature failure of the unit
due to extremely low return air temperatures and exposure
to corrosive or very dirty atmospheres.
WARNING
To prevent the risk of property damage, personal injury, or
death, do not store combustible materials or use gasoline
or other flammable liquids or vapors in the vicinity of this
appliance.
Auxiliary devices which may be a potential ignition source
shall not be installed in the duct work. Examples of
such potential ignition sources are hot surfaces with a
temperature exceeding 700 °C and electric switching devices.
WARNING
Leak detection system installed. Unit must be powered except
for service.
WARNING
This unit is equipped with electrically powered safety
measures. to be effective, the unit must be electrically
powered at all times after installation, other than when
servicing.
Do not use means to accelerate the defrosting process or to
clean, other than those recommended by the manufacturer.
the applicance shall be stored in a room without
continuously operating ignition sources (for example: open
flames, an operating gas appliance, or an operating electric
heater). Do not pierce or burn. be aware that refrigerants
may not contain an odor.
WARNING
Only auxiliary devices approved by the appliance
manufacturer or declared suitable with the refrigerant
shall be installed in connecting ductwork.
WARNING
WARNING
background
4
WARNING
Prior to servicing the unit or removing the compressor
terminal plug or terminal cover, disconnect all electrical
power from the unit. multiple power sources may be present.
Do not operate the compressor(s) without the terminal plug
fully engaged or the terminal cover properly installed.
WARNING
A tripped circuit breaker or blown fuse may indicate that
an electrical problem exists. do not reset a circuit breaker
or replace fuses withouth first performing thorough
electrical troubleshooting and testing procedures.
The Following Instructions are Mandatory for
A2L Systems and Supersede Other Instructions
WARNING
Only brazing techniques or approved mechanical joints
should be used to connect refrigerant tubing connections.
Non-approved mechanical connectors and other methods
are not permitted in this system containing A2L refrigerant.
Approved mechanical joints will be detailed in the product’s
specification sheets.
Deep Vacuum Method
The Deep Vacuum Method requires a vacuum pump
rated for 500 microns or less. This method e󰀨ectively and
e󰀩ciently ensures the system is free of non-condensable
air and moisture. The Triple Evacuation Method is
detailed in the Service Manual for this product model as
an alternative. To expedite the evacuation procedure, it is
recommended that the Schrader Cores be removed from
the service valves using a core-removal tool.
1. Connect the vacuum pump, micron gauge, and vacuum-
rated hoses to both service valves. Evacuation must
use both service valves to eliminate system mechanical
seals.
2. Evacuate the system to less than 500 microns.
3. Isolate the pump from the system and hold the vacuum
for 10 minutes (minimum). Typically, pressure will rise
slowly during this period. If the pressure rises to less
than 1000 microns and remains steady, the system is
considered leak-free; proceed to system charging and
startup.
4. If pressure rises above 1000 microns but holds steady
below 2000 microns, non-condensable air or moisture
may remain, or a small leak may be present. Return to
step 2: If the same result is achieved, check for leaks
and repair. Repeat the evacuation procedure.
5. If pressure rises above 2000 microns, a leak is present.
Check for leaks and repair any leaks. Then, repeat the
evacuation procedure.
Accessory Installation
WARNING
All accessories that may become a potential ignition source
if installed. such as electronic air cleaners, must only be
powered through our accessory control board kit. If an
electronic air cleaner is already installed in the duct work
and not connected to the accessory control board. it will
have to be disabled or removed. Ensure that any additional
wiring from the indoor unit to the accessory control board
is routed and protected from damage and wear, avoiding the
flue pipe and any joints that may need brazed or disconnected
for service. Refer to the product specification sheet for the
accessory control board kit part number.
Altitude Adjustment Factor to Calculate Minimum
Room Area
The Indoor equipment mitigation requirements are
calculated at sea level. For higher altitudes adjust the
minimum room area specied on or near the Serial Plate
by the corresponding altitude adjustment factor shown
below. This table is provided as a reference.
Adjusted room area (A
min
adj
) is the product of the minimum
room area specied on or near the serial plate and the
adjustment factor AF, as shown in below formula
A
min adj
= A
min
(serial plate) * AF
Altitude Adjustment Factor (AF)Height in feetHeight in meters
1.00At sea levelAt sea level
1.021~6601~200
1.03660~1320200~400
1.051320~1970400~600
1.071970~2630600~800
1.092630~3290800~1000
1.113290~39401000~1200
1.133940~46001200~1400
1.154600~52501400~1600
1.175250~59101600~1800
1.195910~65701800~2000
1.216570~72202000~2200
1.247220~78802200~2400
1.267880~85402400~2600
1.298540~91902600~2800
1.319190~98502800~3000
1.349850~105003000~3200
GENERAL INFORMATION
The GPCM3 SEER2 M-Series air conditioners are
designed for OUTDOOR USE ONLY. GPCM3 SEER2
M-Series is available in cooling capacities of 2, 2.5, 3, 3.5,
4 and 5 nominal tons of cooling. Optional eld-installed
heat kits are available in 5, 8, 10, 15 and 20kW. The units
can be easily installed in manufactured or modular homes
with existing high-static duct work. The units can also be
easily converted to accommodate a plenum for normal or
low-static applications. The GPCM3 SEER2 M-Series are
self-contained packaged units so the only connections
WARNING
background
5
needed for installation are the supply and return ducts, the
line and low voltage wiring and drain connection. Rated
performance is achieved after 20 hours of operation. Rated
performance is delivered at the specied airow. See
product specication for packaged models.
Specication sheets can be found at:
www.goodmanmfg.com for Goodman® brand products
or www.amana-hac.com for Amana® brand products.
Within either website, please select the Products and
Services menu and then select the submenu for the type
of product to be installed, such as air conditioners, to
access a list of product pages that each contain links to
the model’s specication sheet. The units are UL listed,
and AHRI certied. The information on the rating plate is
in compliance with the FTC & DOE rating for single phase
units.
Qualification of Workers
Personnel must be certied to service, work, and/or repair
units with FLAMMABLE REFRIGERANTS. A certicate
should document the competence and qualication
achieved through training that included the substance of
the following:
• Information about the explosion potential of
FLAMMABLE REFRIGERANTS to show that
ammables may be dangerous when handled without
care.
• Information about POTENTIAL IGNITION SOURCES,
especially those that are not obvious, such as lighters,
light switches, vacuum cleaners, electric heaters.
• Information about the di󰀨erent safety concepts,
including ventilated and unventilated areas.
• Information about refrigerant detectors, including
function, operation, and service measures.
• Information about the concept of sealed components
and sealed enclosures according to IEC 60079-
15:2010.
• Information about the correct working procedures,
including commissioning, maintenance, repair,
decommissioning, and disposal procedures.
EPA Regulations
Important: The United States Environmental
Protection Agency (EPA) has issued various
regulations regarding the introduction and
disposal of refrigerants in this unit. Failure
to follow these regulations may harm the
environment and can lead to the imposition of
substantial fines. Because regulations may vary
due to passage of new laws, we suggest a certified
technician perform any work done on this unit.
Should you have any questions please contact the
local office of the EPA.
National Codes
This product is designed and manufactured to permit
installation in accordance with National Codes. It is the
installer’s responsibility to install the product in accordance
with National Codes and/or prevailing local codes and
regulations.
Major Components
The unit includes a hermetically sealed refrigerating system
(consisting of a compressor, condenser coil, evaporator coil
with owrator), an indoor blower, a condenser fan, and all
necessary internal electrical wiring. The system is factory-
evacuated, charged and performance tested. Refrigerant
amount and type are indicated on rating plate.
Pre-Installation Checkpoints
Carefully read all instructions for the installation prior
to installing unit. Ensure each step or procedure is
understood and any special considerations are taken into
account before starting installation. Assemble all tools,
hardware and supplies needed to complete the installation.
Some items may need to be purchased locally.
Check that cabling /wiring will not be subject to wear,
corrosion, excessive pressure, vibration, sharp edges or
any other adverse environmental e󰀨ects. The check shall
also take into account the e󰀨ects of aging or continual
vibration from sources such as compressors or fans.
Under no circumstances shall potential sources of ignition
be used in the searching for or detection of refrigerant
leaks. A halide torch (or any other detector using a naked
ame) shall not be used.
The following leak detection methods are deemed
acceptable for all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant
leaks but, in the case of FLAMMABLE REFRIGERANTS,
the sensitivity may not be adequate, or may need
recalibration. (Detection equipment shall be calibrated in a
refrigerant-free area.) Ensure that the detector is
not a potential source of ignition and is suitable for the
refrigerant used. Leak detection equipment shall be set
at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed, and the appropriate
percentage of gas (25 % maximum) is conrmed.
Leak detection uids are also suitable for use with most
refrigerants but the use of detergents containing chlorine
shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked ames shall be removed/
extinguished.
If a leakage of refrigerant is found which requires brazing,
all of the refrigerant shall be recovered from the system.
background
6
Before attempting any installation, the following points
should be considered:
• Structural strength of supporting members
• Clearances and provision for servicing
• Power supply and wiring
• Air duct connections
• Drain facilities and connections
• Location may be on any four sides of a home,
manufactured or modular, to minimize noise
Consider the e󰀨ect of outdoor fan noise on conditioned
space and any adjacent occupied space. It is
recommended that the unit be placed so that condenser air
discharge does not blow toward windows less than 25 feet
away.
The unit should be set on a solid, level foundation
-preferably a concrete slab at least 4 inches thick. The
slab should be above ground level and surrounded by
a graveled area for good drainage. Any slab used as a
unit’s foundation should not adjoin the building as it is
possible that sound and vibration may be transmitted to
the structure. For rooftop installation, steel or treated wood
beams should be used as unit support for load distribution.
UNIT LOCATION
NOTE: Units are designed for outdoor installation
only at a max altitude of 8,000 feet above sea
level.
WARNING
THE APPLIANCE SHALL BE INSTALLED, OPERATED AND
STORED IN A ROOM WITH A FLOOR AREA NOT LESS THAN THE
MINIMUM ROOM AREA.
Minimum Room Area Figure
IMPORTANT NOTE: Refer to the altitude adjusted
room area calculation referenced in this manual.
Clearances and Accessibility
The unit is designed to be located outside the building
with unobstructed condenser air inlet and discharge.
Additionally, the unit must be situated to permit access
for service and installation. Condenser air enters from
three sides. Air discharges upward from the top of the
unit. Refrigerant gauge connections are made on the right
side of the unit as you face the compressor compartment.
Electrical connections can be made either on the right
or left sides of the unit. The best and most common
application is for the unit to be located 12” from the wall
(4” minimum) with the connection side facing the wall. This
“close to the wall” application minimizes exposed wiring.
Close to the wall application assures free, unobstructed
air to the other two sides. In more conned application
spaces, such as corners provide a minimum 12” clearance
on all air inlet sides. Allow 36” minimum for service access
to the compressor compartment and controls. The top of
the unit should be completely unobstructed. If units are to
be located under an overhang, there should be a minimum
of 48” clearance and provisions made to deect the warm
discharge air out from the overhang. See FIGURE 1:
GROUND LEVEL INSTALLATION below.
Figure 1: Ground Level Installation
Roof Top Installation (Figure 2)
1. Before locating the unit on the roof, make sure that
the strength of the roof and beams is adequate to
support the weight involved. (See specication sheet
for weight of units). This is very important and the
installer’s responsibility.
2. Make a proper consideration for weather-tight integrity
of the roof and proper drainage of condensate.
3. To ensure proper condensate drainage, unit must be
installed in a level position.
4. Consideration should also be given to shade,
appearance, and noise.
background
7
Figure 2: Rooftop Installation
Roof Curb Installations
NOTE: Sufficient structural support must be
determined prior to locating and mounting the
curb and package unit.
Curb insulation, cant strips, ashing and general roong
material are furnished by the contractor.
Curbing must be installed in compliance with the National
Roong Contractors Association Manual. Construct duct
work using current industry guidelines. The duct work must
be placed into the roof curb before mounting the package
unit. See FIGURE 3: ROOFCURB INSTALLATION.
Figure 3: Roofcurb Installation
Rigging Details
WARNING
To prevent property damage, the unit should remain in an
upright position during all rigging and moving operations.
To facilitate lifting and moving when crane is used, place
the unit in an adequate cable sling.
CAUTION
If units are lifted two at a time, the fork holes on the
condenser end of the unit must not be used. Minimum for
length is 42” to prevent damage to the unit; however, 48” is
recommended.
NOTE: Provisions for forks have been included in
the unit base frame. No other fork locations are
approved.
background
8
WARNING
To avoid possible property damage, personal injury or death,
ensure the roof has sufficient structural strength to carry
the weight of the unit(s), roofcurb, snow loads, and water
loads as required by local codes. Consult a structural
engineer to determine the weight capabilities of the roof.
CAUTION
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
WARNING
To prevent possible equipment damage, property damage,
personal injury or death, the following bullet points must
be observed when installing the unit.
Unit must be lifted by the four lifting holes located at the
base frame corners. See FIGURE 4: RIGGING.
• Lifting cables should be attached to the unit with
shackles.
• The distance between the crane hook and the top of
the unit must not be less than 60”.
• Two spreader bars must span over the unit to prevent
damage to the cabinet by the lift cables. Spreader
bars must be of su󰀩cient length so that cables do not
come into contact with the unit during transport.
• Remove wood struts mounted beneath unit base
frame before setting unit on roof curb. These struts
are intended to protect unit base frame from forklift
damage. Removal is accomplished by extracting the
sheet metal retainers and pulling the struts through
the base of the unit. Refer to rigging label on the unit.
Refer to the Roof Curb Installation Instructions for proper
curb installation. Curbing must be installed in compliance
with the National Roong Contractors Association Manual.
Figure 4: Rigging
Corner and Center of Gravity Locations
NOTE: Units should be lifted at a point above
center of gravity.
LF LR RF RR
GPCM32431
358 333 89 52 84 108 27.10 24.50
GPCM33031
371 346 69 77 115 85 27.17 23.88
GPCM33631
410 385 95 69 111 110 26.98 23.71
GPCM34231
427 402 95 75 129 103 27.12 22.58
GPCM34831
427 402 84 76 137 105 28.29 22.96
GPCM36031
479 454 132 56 143 123 27.54 20.11
Y (in)Model
Shipping
Weight (lb)
Operating
Weight (lb)
Corner Weights (lb)
X (in)
Corner Weights Table
CIRCULATING AIR AND FILTERS
Airflow Conversion
Units can easily be converted from horizontal to down
discharge air ow delivery. See FIGURE 5A: HORIZONTAL
FLOW DUCT COVER INSTALLATION and FIGURE 5B:
DOWNFLOW DUCT COVER INSTALLATION. In down
discharge or high static installations, the installer should
measure the total external static and review the blower
performance charts before performing the installation. In
some installations it will be necessary to change the blower
speed to provide proper air ow.
Horizontal Air Flow
Single phase models are shipped without horizontal duct
covers. If needed, these kits may be ordered through
Goodman’s Service Parts department.
background
9
Figure 5A: Horizontal Flow Duct Cover
Installation
Down Discharge Applications
Cut insulation around bottom openings and remove panels
from the bottom of the unit, saving the screws holding the
panels in place.
Figure 5B: Downflow Duct Cover Installation
Figure 5C: Downshot Conversion Kit
NOTE: A horizontal duct cover kit and either an
approved downflow conversion kit or an approved
downflow economizer are required for downflow
installation. refer to the spec sheet for details.
Ducting
Ducting work should be fabricated by the installing
contractor in accordance with local codes. Industry
manuals may be used as a guide when sizing and
designing the duct system-such as NESCA (National
Environmental Systems Contractors Association, 1501
Wilson., Arlington, Virginia 22209).
The unit should be placed as close as possible to the
space to be air-conditioned allowing clearance dimensions
as indicated. Ducts should run as directly as possible
to supply and return outlets. Use of non-ammable
weatherproof exible connectors on both supply and return
connections at the unit to reduce noise transmission is
recommended.
It is preferable to install the unit on the roof of the structure
if the registers or di󰀨users are in the wall or ceiling. A slab
installation is recommended when the registers are low on
the wall or in the oor.
Connecting the Return and Supply Flexible Duct in
Manufactured or Modular Housing Application
The return and supply ttings are to be attached at
the unit to a suitable square to round duct converter.
Your distributor has a factory designed square to round
converter transition. The model #’s of these kits are as
follows in the table below. (See Specication Sheets for
Dimension details).
background
10
Accessory Description Item Number
Medium Chassis Large Chassis
Downow Square to Round SQRPG101/102 SQRPG103
Horizontal Square to Round SQRPGH102 SQRPGH103
The SQRPG101, SQRPG102, and SQRPG103 t up to
the Return and Supply Downow vents having dimensions:
Return (22 ¾” x 12 ¼”) and Supply (22 ¼” x 14 ¾”). The
SQRPGH101, SQRPGH102, and SQRPGH103 t up to
the Horizontal Return and Supply downow vents having
dimensions: Medium Chassis (16 ½” x 16 ½”) and Large
Chassis (18 ½” x 18 ½”). The Medium Chassis kits
transition to a 16” Diameter and the Large Chassis kits
transition to an 18” Diameter (equivalent diameter, opening
is oval) on the return. The collars are to be slipped into the
openings, and the anges bent around the converter. The
square to round converter is attached to the anges of the
square duct openings. The exible duct is then clamped on
to the collars. Once the duct is a󰀩xed to the unit, seal the
collars and anges with a proper waterproof sealant. SEE
FIGURE 6: MANUFACTURED HOME MODIFICATION KIT.
Figure 6: Manufactured Home Modification Kit
It is strongly encouraged to use appropriately sized ducts
based upon the CFM for your application (unit’s CFM). If
duct sizing through industry manuals or air duct calculators
requires larger ducts than converter openings, run larger
duct size up to unit converter openings and reduce with a
reducer duct tting or transition right at the unit.
Plenum Application
A suitable plenum or square duct must be constructed. The
duct cross-sectional area should be determined by industry
duct sizing manuals or air duct calculators.
On ductwork exposed to outside air conditions of
temperature and humidity, use an insulation with a good
K factor, and a vapor barrier. Industry practices should be
followed. Balancing dampers are recommended for each
branch duct in the supply system. Ductwork should be
properly supported from the unit. False ceilings or drop
ceilings may be used as a return air plenum.
NOTE: Adequate return grills have to be supplied
for each room for proper return for that space.
NOTE: Proper sealing of all ductwork and air
handling compartments is extremely important to
overall unit efficiency.
Filters
Filters are not provided with unit and must be supplied
and externally installed in the return duct system by the
installer. A eld-installed lter grille is recommended for
easy and convenient access to the lters for periodic
inspection and cleaning. When installing lters, ensure
the air ow arrows on the lter are pointing toward the
circulator blower. For unit lter size information, see table
below for recommended lter size.
UNIT
2 TON 2 1/2 TON 3 TON 3 1/2 TON 4 TON 5 TON
Min.
Filter
Size
(1)25X25X1
(1)25X25X1 (1)25X25X1 (1)25X25X1 (2)20X20X1 (2)20X20X1
CONDENSATE DRAIN PIPING
The condensate drain connection of the evaporator is a
¾” NPT half coupling. A trap must be provided to have
proper condensate draining. Install condensate drain trap
as shown in FIGURE 7: CONDENSATE DRAIN TRAP
PLUMBING. Ensure drain connection is 3/4” or larger. Do
not operate unit without trap and ensure unit is level or
slightly inclined toward drain.
2" Minimum
3" Minimum
A Positive Liquid Seal
Is Required
Flexible
Tubing-Hose
Or Pipe
Drain
Connection
Unit
Figure 7: Condensate Drain Trap Plumbing
ELECTRICAL WIRING
WARNING
HIGH VOLTAGE!
prior to servicing the unit or removing the
compressor terminal plug or terminal cover,
disconnect all electrical power from the unit.
Multiple power sources may be present.
WARNING
Do not operate the compressor(s) without the terminal
plug fully engaged or the terminal cover properly installed.
Get away if unusual sounds are heard from within the
compressor. Disconnect electrical power from the unit.
background
11
WARNING
A tripped circuit breaker or blown fuse may indicate that an
electrical problem exists. Do not reset a circuit breaker or
replace fuses without first performing thorough electrical
troubleshooting and testing procedures.
WARNING
Hermetic compressor electrical terminal venting can be
dangerous. In certain circumstances, the terminal may be
expelled, venting the refrigerant vapor and compressor
oil contained within the compressor housing and system. Be
alert for sounds of arcing (Sizzling, sputtering, or popping)
inside the compressor. Immediatly get away if you hear these
sounds and disconnect electrical power from the unit.
Never operate the compressor without the terminal cover
secured and properly in place or without the electrical plug
fully seated and engaged to the terminal posts.
If a terminal is damaged, electrically overloaded, or short
circuits to ground, there is a remote possibility that the
terminal can be suddenly expelled from the terminal
housing thereby venting the refrigerant and compressor oil
mixture to atmosphere.
This discharge can be ignited from electrical arcing, or
other open sources of ignition, and can cause potentially
severe or fatal injury. This event is known as “Terminal
Venting”.
To reduce the possibility of external ignition, all open
ames or other heat sources must be extinguished, and
all electrical power must be turned o󰀨 prior to opening the
terminal cover or removing the electrical plug and servicing
the system.
Proper sealed system evacuation is required during
servicing to maintain adequate internal system cleanliness
while eliminating contaminates.
Be alert for sounds of arcing (sizzling, sputtering, or
popping) inside the compressor. IMMEDIATELY GET
AWAY from the unit if you hear these sounds and
disconnect electrical power.
NOTE: Never operate the compressor in a vacuum
or in reverse operation.
CAUTION
To avoid property damage or personal injury due to fire,
use only copper conductors.
All wiring should be made in accordance with the National
Electrical Code. The local power company should be
consulted to determine the availability of su󰀩cient
power to operate the unit. The voltage, frequency, and
phase at the power supply should be checked to make
sure it corresponds to the unit’s RATED VOLTAGE
REQUIREMENT.
Install a branch circuit fused disconnect near the unit, in
accordance with the N.E.C. or local codes. Wire sizes and
overcurrent protection should be determined from the unit
nameplate ampacity and in accordance with N.E.C. and
local building codes. Under no circumstances should wiring
be sized smaller than is recommended by either of these
two sources.
Fuses smaller than that recommended on the unit
nameplate could result in unnecessary fuse failure or
service calls. The use of protective devices of larger size
than indicated could result in extensive damage to the
equipment. The manufacturer bears no responsibility for
damage caused to equipment as result of the use of larger
than is recommended size protective devices.
All units have undergone a run test prior to packaging for
shipment. This equipment has been started at minimum
rated voltage and check for satisfactory operation. Do not
attempt to operate this unit if the voltage is not within the
minimum and maximum voltages shown on the nameplate.
The units are designed for operation at the voltage,
frequency, and phase as shown on the rating plate. All
internal wiring in the unit is complete. It is necessary to
bring in the power supply to the contactor as shown on the
unit wiring diagram which is supplied with each unit. The
low voltage wiring must be connected between the unit
control panel and the room thermostat.
All exterior wiring must be within approved weatherproof
conduit. The unit must be permanently grounded in
accordance with local codes, or in absence of local codes
with N.E.C. ANSI/NFPA NO. 70 or latest edition by using
ground lug in the control box.
DO NOT EXCEED THE MAXIMUM OVERCURRENT
DEVICE SIZE SHOWN ON UNIT DATA PLATE.
Fuses or HACR type circuit breakers may be used where
codes permit.
IMPORTANT NOTE: Units may be equipped with a
single pole contactor. Caution must be exercised
when servicing as only one phase of the power
supply is broken with the contactor.
Rated Voltage
Minimum Supply
Voltage
Maximum
Supply Voltage
208/240V 197 253
background
12
WARNING
HIGH VOLTAGE!
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
CAUTION
To avoid the risk of electrical shock, wiring to the unit
must be grounded.
High Voltage Wiring
Single phase – Connect two leads to terminals L1 & L2 in
the electrical control section, using wire sizes specied in
wiring table.
Branch Circuit
Ampacity
15 20 25 30 35 40 45 50
SUPPLY WIRE
LENGTH - FEET
200 6 4 4 4 3 3 2 2
150 8 6 6 4 4 4 3 3
100 10 8 8 6 6 6 4 4
50 14 12 10 10 8 8 6 6
Figure 8: Wiring Table
NOTE: The unit transformer is factory connected
for 240V operation. If the unit is to operate on
208V, reconnect the transformer primary lead as
shown on the unit wiring diagram.
Low Voltage Wiring
Air Conditioners – Connect 24V wires from the thermostat
to the corresponding wires in the control box using No. 18
AWG as follows:
GPCM3
Terminal Thermostat
Red R (24V)
Green G (fan)
Yellow Y (Cool)
White W1 (Heat, Aux Heat Stage 1)*
Brown W2 (Heat, Aux Heat Stage 2)*
Blue C (Common)
*Optional eld installed heat connections
Thermostats must be set to energize “G” during cooling.
This is default on most thermostats.
Internal Wiring
A diagram detailing the internal wiring of this unit is located
on the electrical box cover. If any of the original wire
supplied with the appliance must be replaced, the wire
gauge and insulation must be the same as the original
wiring.
1. For branch circuit wiring (main power supply to unit
disconnect), the minimum wire size for the length
of the run can be determined from N.E.C., local
building codes, and using the circuit ampacity found
on the unit rating plate. From the unit disconnect
to unit, the smallest wire size allowable may be
used for the ampacity, as the Disconnect MUST
be in accordance with federal, state, and local
jurisdiction requirements.
2. Wire size based on 60°C rated wire insulation and
30°C Ambient Temperature (86°F).
3. For more than 3 conductors in a raceway or cable,
see the N.E.C. for derating the ampacity of each
conductor.
START-UP PROCEDURE AND CHECKLIST
Begin with power turned o󰀨 at ALL disconnects.
WARNING
HIGH VOLTAGE!
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
Air Conditioner Start-Up Procedure
1. Turn thermostat system switch to “Cool,” and fan
switch to “Auto” and turn temperature setting as high
as it will go.
2. Inspect all registers and set them to the normal open
position.
3. Turn on the electrical supply at the disconnect.
4. Turn the fan switch to the “ON” position. The blower
should operate after a 10 second delay.
5. Turn the fan switch to “AUTO” position. The blower
should begin ramping down after an approximate
60-second delay.
6. Slowly lower the cooling temperature until the unit
starts. The compressor, blower, and fan should now
be operating. Allow the unit to run 10 minutes, make
sure cool air is being supplied by the unit.
7. Turn the temperature setting to the highest position,
stopping the unit. The indoor blower will continue to
run for approximately 60 seconds.
8. Turn the thermostat system switch to “OFF” and
disconnect all power when servicing the unit.
Final System Check
1. Check to see if all supply and return air grilles are
adjusted and the air distribution system is balanced
for the best compromise between heating and cooling.
2. Check for air leaks in the ductwork.
3. Check air ow and refrigerant charge. See Sections
on Air Flow Measurement and Adjustment and
Checking Charge.
4. Ensure the unit is free of “rattles”, and the tubing in
the unit is free from excessive vibration. Also make
sure tubes or lines are not rubbing against each
other or sheet metal surfaces or edges. If discovered,
background
13
ensure issue is corrected.
5. Set the thermostat at the appropriate setting for
cooling and heating or automatic changeover for
normal use.
6. Ensure the Owner is instructed on the unit operation,
lter, servicing, correct thermostat operation, etc.
NOTE: The “Air Conditioner Start-up Procedure”
is a recommended step as it serves as a system
indicator that the unit will operate normally.
COMPONENTS
Contactor – This control is activated (closed) by the room
thermostat for both heating and cooling. The contactor
has a 24V coil and supplies power to the compressor and
outdoor fan motor.
Crankcase Heater – This item is “ON” whenever power
is supplied to the unit and crankcase heater thermostat is
closed. Crankcase heater thermostat closes at 67° and
opens at 85°. It warms the compressor crankcase thereby
preventing liquid migration and subsequent compressor
damage. The insert type heater is self-regulating. It is
connected electrically to the contactor L1 & L2 terminals.
Condenser Motor – This item is activated by the contactor
during heating and cooling, except during defrost and
emergency heat operation.
Compressor – This item is activated by the contactor for
heating and cooling, except during emergency heat. It is
protected by an internal overload.
Contactor Relay – This control is activated by the
thermostat (24V coil) and supplies power to the system.
Defrost Control – The Defrost control provides
time/temperature initiation and termination of the defrost
cycle. When a Defrost cycle is initiated, the defrost control
shifts the reversing valve to “cooling” mode, stops the
outdoor fan and brings on supplemental heat. Normally, a
Defrost cycle will take only 2-3 minutes unless system is
low on charge or outdoor conditions are severe. (Windy
and cold). The defrost control also provides for a 3 minute
o󰀨 cycle compressor delay.
Outdoor Thermostat – These optional controls are used
to prevent full electric heater operation at varying outdoor
ambient (0°F to 45°F). They are normally open above their
set points and closed below to permit staging of indoor
supplement heater operation. If the outdoor ambient
temperature is below 0°F (-18°C) with 50% or higher RH,
an outdoor thermostat (OT) must be installed and set at
(0°F) on the dial. Failure to comply with this requirement
may result in damage to the product which may not be
covered by the manufacturer’s warranty.
Reversing Valve Coil – This coil is activated by the
thermostat, in the colling mode and during defrost.
It positions the reversing valve pilot valve for cooling
operation.
Indoor Blower Motor – Units with EEM Motors Only.
The EEM model indoor blower motor is activated by
the room thermostat by COOLING/HEATING or fan ON
position. EEM motors are constant torque motors with low
power consumption.
(See Air Flow Measurement and Adjustment for speed
adjustment instructions).
Blower Interlock Relay – This relay is used to energize
the blower during the electric heat operation. Some room
thermostats do not energize the motor during electric
heat. This relay ensures blower operation when the room
thermostat energizes heat. This relay is energized by the
electric heat kit sequencer.
Defrost Control
During operation the power to the circuit board is controlled
by a temperature sensor, which is clamped to a feeder tube
entering the outdoor coil. Defrost timing periods of 30,60
and 90 minutes may be selected by setting the circuit
board jumper to 30, 60 and 90 respectively. Accumulation
of time for the timing period selected starts when the
sensor closes (approximately 30 ± 5°F), and when the wall
thermostat calls for heat. At the end of the timing period,
the unit’s defrost cycle will be initiated provided the sensor
remains closed. When the sensor opens (approximately
60°± 5°F), the defrost cycle is terminated and the timing
period is reset. If the defrost cycle is not terminated due to
the sensor temperature, a twelve-minute override interrupts
the unit’s defrost period.
SUGGESTED FIELD TESTING/
TROUBLESHOOTING
TESTING DEFROST CONTROL
NOTE: PCBDM133 Defrost controls have a three
(3) minute compressor off cycle delay.
NOTE: The PCBDM133 defrost controls are
shipped from the factory with the compressor
delay option selected. This will de-energize the
compressor contactor for 30 seconds on defrost
initiation and defrost termination. If the jumper
is set to normal, the compressor will continue
to run during defrost initiation and defrost
termination. The control will also ignore the low-
pressure switch connected to R-PS1 and PS2 for 5
minutes upon defrost initiation and 5 minutes after
defrost termination.
To check the defrost control for proper
sequencing, proceed as follows: With power ON;
unit not running.
1. Jumper defrost thermostat by placing a jumper wire
across the terminals “DFT” and “R”/” R-DFT” at
defrost control board.
2. Remove jumper from timer pins and jump across test
pins on defrost control board.
NOTE: Do not use screwdriver or field
supplied jumper to test the control.
3. Set thermostat to call for heating. System should go
into defrost within 21 seconds.
4. Immediately remove jumper from test pins.
5. Using VOM check for voltage across terminals “C &
O”. Meter should read 24 volts.
background
14
6. Using VOM check for voltage across fan terminals
DF1 and DF2 on the board. Should read line voltage
(208-230 VAC) indicating the relay is open in the
defrost mode.
7. Using VOM check for voltage across “W”/”W2” & “C”
terminals on the board. Should read 24 volts.
8. If not as above, replace control board.
9. Set thermostat to o󰀨 position and disconnect power.
Remove jumper from defrost thermostat and replace
timer jumper to the desired defrost time.
NOTE: Remove jumper across defrost thermostat
before returning system to service. See Figure 9:
Defrost control Wiring Schematic.
Figure 9: Defrost Control Wiring Schematic
Testing Defrost Thermostat
1. Install a thermocouple type temperature test lead on
the tube adjacent to the defrost control. Insulate the
lead point of contact.
2. Check the temperature at which the control closes its
contacts by lowering the temperature of the control. It
should close at approximately 30°F.
3. Check the temperature at which the control opens its
contacts by raising the temperature of the control. It
should open at approximately 60°F. If not as above,
replace control.
AIR FLOW MEASUREMENT AND
ADJUSTMENT
After reviewing section on DUCTING, proceed with airow
measurements and adjustments. Unit’s blower curves
(in Specication Sheets) are based on external static
pressure (ESP, in. of W.C.). The duct openings on the unit
are considered internal static pressure, so long as ESP
is maintained, the unit will deliver the proper air up to the
maximum static pressure listed for the CFM required by the
application (i.e., home, building, etc.).
In general, 400 CFM per ton of cooling capacity is a rule
of thumb. Some applications depending on the sensible
and latent capacity requirements may need only 350
CFM or up to 425 CFM per ton. Check condition space
load requirements (from load calculations) and equipment
expanded ratings data to match CFM and capacity.
After unit is set and ducted, verify ESP with a 1” inclined
manometer with pitot tubes or a Magnahelic gauge and
conrm CFM to blower curves in the specication sheets.
All units have multiple speed blower motors. If factory
selected speed is not utilized, the speed tap can be
changed.
NOTE: Never run CFM below 300 CFM per ton,
evaporator freezing, or poor unit performance is
possible.
Total external static pressure
1. Using a digital manometer measure the static
pressure of the return duct at the inlet of the unit
(Negative Pressure). SEE FIGURE 10: TOTAL
EXTERNAL STATIC.
Figure 10: Total External Static
2. Measure the static pressure of the supply duct
(Positive Pressure).
3. Add the two readings together.
EXAMPLE:
static reading from return duct = -.1”w.c.
static reading from supply duct = .3”w.c.
total external static pressure on this system =.4”w.c.
NOTE: Both readings may be taken simultaneously
and read directly on the manometer if so desired.
4. Consult proper table for quantity of air.
background
15
If the external static pressure exceeds the maximum
allowable static, check for closed dampers, dirty lter,
undersized or poorly laid out ductwork.
ADJUSTING SPEED TAP FOR INDOOR
BLOWER MOTOR
EEM Motor
The blower motor speed for the EEM motor is controlled by
three 24V low voltage leads: green, yellow, and white. The
green lead sets the speed for fan-only mode. The yellow
lead sets the speed for cooling.
EEM Motor Speed Adjustment
The white lead sets the speed for electric heat mode
(emergency heat and second stage heat, if applicable).
The leads are factory connected as follows: Green to T1,
Yellow to T2, and White to T3. T1 is the low speed setting
and is dedicated to fan-only mode. T2 is medium speed
cooling and T3 is medium speed heating. T4 is high speed
cooling and T5 is high speed heating. To adjust the blower
speed, move the yellow and/or white wires to T4 and T5.
NOTE: If more than one lead is energized at the
same time, the motor will use the higher speed
setting.
See appendix for Blower Performance Data tables.
GPCM3 CFM Delivery and Adjustments
See Appendix for CFM Output, Adjustments, and DIP
switch settings.
GPCM3 Thermostat “Fan Only” Mode
During Fan Only Operations, the CFM output is 50% of the
high stage cooling setting.
SUPERHEAT AND SUBCOOLING
Checking Subcooling
NOTE: Units with a TXV should be charged to
Subcooling only.
EXAMPLE:
a. Liquid Line Pressure = 417 PSI
b. Corresponding Temp. = 120°F
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling, subtract 109°F
from 120°F. The di󰀨erence is 11° subcooling. See the
specication sheet or technical information manual for the
design subcooling range for your unit.
SUBCOOLING FORMULA = SATURATED LIQUID LINE
TEMPERATURE - LIQUID LINE TEMPERATURE
Checking Superheat
EXAMPLE:
a. Suction Pressure = 143 PSI
b. Corresponding Temp. = 50°F
c. Thermometer on Suction Line = 59°F
To obtain the degrees temperature of superheat, subtract
50.0 from 59.0°F. The di󰀨erence is 9° Superheat. The 9°
Superheat would fall in the ± range of allowable superheat.
SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION
TEMP.
Superheat Adjustment
NOTE: Superheat adjustments should not be made
until indoor ambient conditions have stabilized
and correct air flow (CFM) has been verified.
This could take up to 24 hours depending on
indoor temperature and humidty. Before checking
superheat, run the unit in cooling for 15-20
minutes or until refrigerant pressure stabilizes.
NOTE: TXV adjustments should not exceed one
turn clockwise (CW) or counterclockwise (CCW)
from the factory setting.
Unscrew the cover from the expansion valve, locate the
adjustment screw, and turn it clockwise (in) to increase su-
perheat or counterclockwise (out) to decrease superheat.
It is recommended to make small adjustments at a time,
1/8-1/4 turn increments. Replace adjustment cap. Wait a
minimum of 10 minutes between adjustments to allow time
for the TXV and pressures to stabilize.
Refrigerant Charge Check
NOTE: For optimal performance, follow charging
instructions below.
GPCM32431 - 14.5 Piston High 95
GPCM33031 - 11.0 Piston High 95
GPCM33631 - 11.0 Piston High 95
GPCM34231 - 12.0 Piston High 95
GPCM34831 - 8.0 Piston High 95
GPCM36031 12.5 13.0 TXV High 95
Design Superheat & Subcooling
Model
Subcooling
(±1°F)
Superheat
(±2°F)
Expansion
device
Cooling
Stage
Ambient
Figure 11: Design Superheat and Subcooling
NOTE: Subcooling should be measured at outdoor
liquid line.
NOTE: Superheat should be measured at
compressor suction line.
Units with Expansion valve (TXV)
Single Stage Cooling Application: Refer to the Design
Superheat & Subcooling table.
Two-Stage Cooling Application: Run unit on Low Stage
cooling and refer to Design Superheat & Subcooling table.
1. Purge gauge lines. Connect service gauge manifold
to access ttings. Run system at least 10 minutes
to allow pressure to stabilize.
background
16
2. Temporarily install thermometer on liquid (small)
line near liquid line access tting with adequate
contact and insulate for best possible reading.
3. Check subcooling and superheat. System should
have a subcooling and superheat within the range
listed on the Design Superheat and Subcooling
table.
a. If subcooling and superheat are low, adjust TXV
superheat, then check subcooling.
NOTE: To adjust superheat, turn the
valve stem clockwise to increase and
counterclockwise to decrease. Refer to
TXV Superheat Adjustment referenced in
this manual.
b. If subcooling is low and superheat is high,
add charge to raise subcooling then check
superheat.
c. If subcooling and superheat are high, adjust TXV
valve superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust
TXV valve superheat and remove charge to
lower the subcooling.
NOTE: Do NOT adjust the charge based
on suction pressure unless there is a
gross undercharge. If an undercharge
is suspected, recover the charge, re-
evacuate the system, and recharge per
data plate. No adjustments should be
made if suspecting a charge issue.
4. Disconnect manifold set, installation is complete.
RDS Function
The mitigation system is a stationary device that detects
the presence of R-32 refrigerant above 25% LFL using
refrigerant sensors and then initiates mitigation actions.
The mitigation system’s primary function is to reduce the
concentration of leaked R-32 refrigerant to prevent serious
safety hazards. The mitigation actions are accomplished
by halting HVAC operation and continuing indoor blower
operation to provide airow. Once refrigerant concentration
reaches below a safe threshold, the unit will remain in
mitigation mode for ve minutes to evacuate any remaining
R-32 refrigerant within the unit. Upon completion, the unit
will resume its normal operation.
RDS Operation
The mitigation system is controlled by a refrigerant
sensor(s), which is secured to a designated location(s) for
active monitoring. If a leak is detected, HVAC operation is
disabled and the indoor blower fan is activated, providing
airow at or above the minimum required airow to
evacuate excess concentration. If a Zone Control system
is installed in the ductwork attached to this system, the
Zone controller must be powered through a Daikin Zoning/
Accessory PCB to ensure that the Zoning Dampers open
during mitigation mode to provide ventilation throughout
all ducting. If the unit is installed with a communicating
thermostat, the thermostat will display relevant alerts/
information concerning mitigation mode. Once sensors
read concentration levels below a safe threshold, a ve
minute timer will initiate. Once the time is over, the unit will
resume its normal operation. If the sensors detect another
concentration excess, the unit will go back into mitigation
mode and will repeat the same process.
background
17
HKTPD051 HKTPD081 HKTPD101 HKTPD151 HKTPD191 HKTPD201
GPCM32431 T3 T3 T3
GPCM33031 T3 T3 T3 T5
GPCM33631 T3 T3 T3 T5
GPCM34231 T3 T3 T3 T5
GPCM34831 T3 T3 T3 T3 T5
GPCM36031 T3 T3 T3 T3 T5
Speed Tap Selection for 0.0 - 0.5 E.S.P.
Model
Heater Kit Part #
IN. W.C kPa MCA MOP MCA MOP MCA MOP
HKTPD051 0.8 0.19 24.74 25 - - 4.75 16200
HKTPD081 0.8 0.19 36.46 40 - - 7.00 23800
HKTPD101 0.8 0.19 49.48 50 - - 9.50 32400
HKTPD151 0.8 0.19 49.48 50 24.74 25 14.25 48600
HKTPD191 0.8 0.12 49.48 50 36.46 25 19.00 64800
HKTPD201 0.8 0.19 49.48 50 36.46 25 19.00 64800
Part Number
Max E.S.P.
Circuit 1
Circuit 2 Output @ 240V
HKTPD051 HKTPD081 HKTPD101 HKTPD151 HKTPD191 HKTPD201
GPCM32431 XXX
GPCM33031 XXXX
GPCM33631 XXXX
GPCM34231 XXXX
GPCM34831 XXXX X
GPCM36031
XXXX X
GPCM3
Model
Heater Kit Part #
HKTPD051 HKTPD081 HKTPD101 HKTPD151 HKTPD191 HKTPD201
GPCM32431 T5 T5 T5
GPCM33031 T5 T5 T5 T5
GPCM33631 T5 T5 T5 T5
GPCM34231 T5 T5 T5 T5
GPCM34831 T5 T5 T5 T5 T5
GPCM36031 T5 T5 T5 T5 T5
Speed Tap Selection for 0.5 - 0.8 E.S.P.
Model
Heater Kit Part #
background
18
ELECTRICAL HEAT INSTALLATION &
ADJUSTMENT
Heater Kit
NOTE: A separate power supply is required for
HKTP Heater Kits.
Refer to the specication manual for heater kit match up
and Heater Kit Electrical Data.
This series of electric cooling package equipment is
designed to accept a eld installed electric heat kit. The
unit is equipped to easily install the HKTP Series Electric
Heat Kit. Full Installation Instructions are included in
this kit. Please use this document for guidance in eld
equipping the package unit with electric heat. Choose the
heat kit that ts the application for the specic installation.
Permanently mark the unit’s nameplate with the model
being installed.
High and low voltage connections are detailed in the heat
kit instructions. Indoor Blower motor speed tap selection
may need to be modied to accommodate normal
continuous operation to prevent a nuisance trip.
MAINTENANCE
The Self-Contained Package Air Conditioner should
operate for many years without excessive service calls if
the unit is installed properly. However, it is recommended
that the homeowner inspect the unit before a seasonal
start up. The coils should be free of debris so adequate
airow is achieved. The return and supply registers should
be free of any obstructions. The lters should be cleaned
or replaced. These few steps will help keep the product
up time to a maximum. The troubleshooting Chart (see
Appendix) should help in identifying problems if the unit
does not operate properly.
WARNING
HIGH VOLTAGE!
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
Recovery
When removing refrigerant from a system, either for
servicing or decommissioning, all refrigerants must
be removed safely. When transferring refrigerant into
cylinders, ensure that only appropriate refrigerant recovery
cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge is available.
All cylinders to be used are designated for the recovered
refrigerant and labeled for that refrigerant (i.e. special
cylinders for the recovery of refrigerant). Cylinders shall be
complete with pressure-relief valve and associated shut-o󰀨
valves in good working order. Empty recovery cylinders are
evacuated and, if possible, cooled before recovery occurs.
All recovery equipment must be suitable for the recovery
of A2L refrigerant and in good working order. Ensure that
you follow the manufacturer’s instructions carefully. If in
doubt, the manufacturer should be consulted. In addition, a
set of calibrated weighing scales shall be available and in
good working order. Hoses shall be complete with leak-free
disconnect couplings and in good condition.
The recovered refrigerant shall be processed according
to local legislation in the correct recovery cylinder,
and the relevant waste transfer note arranged. Do not
mix refrigerants in recovery units and especially not in
cylinders.
If compressors or compressor oils are to be removed,
ensure that they have been evacuated to an acceptable
level to make certain that ammable refrigerant does not
remain within the lubricant. The compressor body shall not
be heated by an open ame or other ignition sources to
accelerate this process. When oil is drained from a system,
it shall be carried out safely.
Charging Procedures
In addition to conventional charging procedures, the
following requirements shall be followed.
• Ensure that contamination of di󰀨erent refrigerants
does not occur when using charging equipment.
Hoses or lines shall be as short as possible to
minimize the amount of refrigerant contained in them.
• Cylinders shall be kept in an appropriate position
according to the instructions.
• Ensure that the REFRIGERATING SYSTEM is
grounded prior to charging the system with refrigerant.
• Label the system when charging is complete (if not
already).
• Extreme care shall be taken not to overll the
REFRIGERATING SYSTEM.
Prior to recharging the system, it shall be pressure tested
with the appropriate purging gas. The system shall
be leak-tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out
prior to leaving the site.
NOTE: “Earthing” is defined as achieving an earth
ground by connecting the equipment’s supplied
background
19
grounding lug to the earth. This should be
verified by a certified technician.
Clean Outdoor Coil (Qualified Servicer Only)
The coil with the outside air owing over it should be
inspected annually and cleaned as frequently as necessary
to keep the nned areas free of lint, hair and debris.
Clean Indoor Coil (Qualified Servicer Only)
Before cleaning the indoor coil, A2L sensor must be
removed from the unit to avoid damage and contamination.
Air lters should also be removed before performing
maintenance. The coil with the ltered air owing over
it should be inspected and cleaned as frequently as
necessary to keep the nned areas free of debris. Coil
cleaning should be performed, utilizing an approved
cleaning method and cleaning agent, from inside-out
(opposite operating airow direction) to prevent damage
to the tube, n coil, and any other components. Prior to
resuming unit operation, ensure to reinstall the A2L sensor.
Servicing Measures for The Refrigerant
Dectection System
Before servicing, identify the mode of operation of the
system by reading the LED ashing pattern on the PCB
within the control box and matching the LED ashing
pattern with mode of operation in the A2L PCB fault code
table on the wiring diagram which is attached on the back
side of the control box panel (RDS PCB Fault Code Table).
After identifying the mode of operation, take recommended
actions as specied in the Recommended Actions for PCB
LED Flashing Codes Table.
REFRIGERANT SENSORS for REFRIGERANT
DETECTION SYSTEMS shall only be replaced with
sensors specied by the manufacturer. If REFRIGERANT
SENSOR requires replacement, please replace with
Sensata R32 Sensor PN#RGD-00ML12 (Daikin
PN#SER2A08012).
MODE LED FLASHING PATTERN
NORMAL OPERATION
SLOW LED FLASHING PATTERN
(2 SECONDS ON 2 SECONDS OFF)
R-32 LEAK ALARM
FAST LED FLASHING PATTERN
DELAY MODE
LED WILL BE ON CONTINUOUSLY
SYSTEM
VERIFICATION MODE
FAST LED FLASHING PATTERN
CONTROL BOARD INTERNAL
FAULT
LED WILL FLASH 2 TIMES AND THEN
BE OFF FOR 5 SECONDS
R32 SENSOR
COMMUNICATION FAULT
LED WILL FLASH 3 TIMES AND THEN
BE OFF FOR 5 SECONDS
R32 SENSOR FAULT
LED WILL FLASH 4 TIMES AND THEN
BE OFF FOR 5 SECONDS
LED STATUS
RDS PCB Fault Code Table
background
20
TROUBLESHOOTING CODE
Recommended Actions for PCB LED Flashing Codes Table
warning; flammable materials
service indicator; read technical
manual
operator's manual; operating
instructions
warning; low burning velocity
material
UN GHS flame symbol
Marking Symbol Table
background
21
TROUBLESHOOTING CHART
21
TROUBLESHOOTING CHART
SYMPTOM
YDEMERESUACELBISSOP
High head - low suction a. Restriction in liquid line or owrator a. Remove or replace with proper size owrator.
High head - high or normal suction a. Dirty condenser coil
b. Overcharged
c. Condenser fan not running
a. Clean coil
b. Correct System charge
c. Repair or Replace
Low head - high suction a. Incorrect owrator
b. Defective compressor valves
c. Flowrator not seating properly
a. Replace with correct owrator
b. Replace compressor
c. Check for debris under owrator or deformed
owrator. Remove debris or replace owrator.
noitcennoclacirtceleesoolrofforewoP.anurtonlliw tinU
b. Thermostat out of calibration set too high
c. Defective contactor
d. Blown fuses or tripped breaker
e. Transformer defective
f. High or low pressure control open
(Optional)
g. Compressor overload contacts open
a. Check for unit voltage at contactor in unit
b. Reset
c. Check for 24 volts at contactor coil replace if
contacts are open
d. Replace fuse or reset breaker Check wiring -
replace transformer
f. Reset high pres
sure control or check unit charge
High pressure control opens at 610 psig
Low pressure control opens at 22 psig
g. Replace compressor
NOTE: Wait at least 2 hours for overload to
reset
Condenser fan runs,
compressor doesn't
a. Loose connection
b. Compressor stuck, grounded or open
winding open internal overload
c. Low voltage connection
d. Capacitor weak, open, or shorted
a. Check for unit voltage at compressor check
& tighten all connections
b. Wait at least 2 hours for overload to reset If still
open, replace the compressor.
c. At compressor terminals, voltage must be within
10 % of nameplate volts when unit is operating
d. Check capacitor. If not within specication, replace.
Low suction - cool compressor
Iced evaporator coil
a. Low indoor airow
a. Increase speed of blower or reduce restriction
- replace air lters
Compressor short cycles a. Defective overload protector
b. Unit cycling on low pressure control
c. High pressure switch cuts out
a. Replace - check for correct voltage
b. Check refrigerant charge and / or airow
c. Check airow (Indoor & outdoor)
wolfriawoL.ataewssretsigeR
a. Increase speed of blower or reduce
restriction replace air lters
High suction pressure a. Excessive load
b. Defective compressor
c. Reversing valve not seating properly.
a. Recheck load calculation
b. Replace
c. Replace
Insucient cooling a. Improperly sized unit
b. Improper airow
c. Incorrect refrigerant charge.
d. Incorrect voltage
a. Recalculate load
b. Check - should be approximately 400 CFM per ton
c. Charge per procedure attached to unit
service panel
d. At compressor terminals, voltage must be within
10% of nameplate volts when unit is
operating
Evaporator coil freezing or frosting a. Low airow
b. Low refrigerant charge
c. Operating unit in cooling mode below
65°F outdoor temperature
a. Check - should be approximately 400 CFM per
ton, dirty air lters, all duct outlets open
b. Properly charge unit
c. Install or check low ambient control, should be
open below 65°F outdoor temperature
background
22
GPCM3[24-60]31** BLOWER PERFORMANCE DATA
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
CFM
580
505
445
390
320
-
-
-
Watts
36
46
54
60
65
-
-
-
CFM
1101
1048
993
935
874
785
740
651
Watts
140
146
152
159
167
214
207
212
CFM
1230
1190
1140
1095
1040
990
920
850
Watts
202
212
220
233
235
243
249
262
CFM
-
550
475
415
340
270
-
-
Watts
-
50
59
66
74
77
-
-
CFM
1357
1297
1241
1188
1136
1081
1022
962
Watts
241
252
264
271
278
286
292
299
CFM
1345
1305
1260
1220
1180
1125
1080
975
Watts
258
273
272
283
292
298
306
310
CFM
1070
1030
980
935
870
775
720
665
Watts
145
161
165
173
181
190
198
202
CFM
1432
1382
1332
1286
1242
1198
1136
1084
Watts
225
235
248
258
270
281
291
304
CFM
1505
1465
1420
1385
1335
1300
1250
1205
Watts
359
371
384
383
393
398
406
416
CFM
1035
995
945
895
845
790
695
630
Watts
132
144
152
157
168
176
183
189
CFM
1506
1460
1418
1386
1339
1300
1260
1207
Watts
292
304
316
325
336
343
354
362
CFM
1698
1654
1604
1558
1513
1467
1421
1370
Watts
370
381
386
396
405
413
421
429
CFM
1355
1300
1250
1210
1155
1110
1045
965
Watts
212
228
230
246
248
261
273
282
CFM
1745
1705
1664
1623
1586
1533
1494
1459
Watts
414
425
437
448
460
468
475
481
CFM
1895
1855
1805
1770
1730
1685
1640
1600
Watts
558
558
578
584
590
594
602
612
CFM
1360
1300
1260
1215
1175
1125
1085
1030
Watts
213
221
233
244
255
264
273
293
CFM
2001
1964
1923
1882
1840
1760
1697
1654
Watts
544
3030
575
583
592
605
615
622
CFM
2000
1960
1925
1875
1835
1800
1760
1725
Watts
642
651
660
651
672
683
691
699
Horizontal
Model Motor Tap
Compressor
stage
Volts
E.S.P. (In. of H
2
O)
GPCM32431**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM33031**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM33631**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM34231**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM34831**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM36031**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
NOTES:
• Data shown is dry coil. Wet coil pressure drop is approximately: 0.1” H2O, for two-row indoor coil; 0.2” H2O, for three-
row coil; and 0.3” H2O, for four-row indoor coil.
• Data shown does not include lter pressure drop, approx. 0.08” H2O.
• Reduce airow by 2% for 208-volt operation.
background
23
GPCM3[24-60]31** BLOWER PERFORMANCE DATA
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
CFM
545
475
418
367
301
-
-
-
Watts
37
47
55
62
67
-
-
-
CFM
1003
1012
950
881
818
707
702
628
Watts
168
172
181
191
196
232
212
217
CFM
1156
1119
1072
1029
978
931
865
799
Watts
207
217
226
239
241
249
255
269
CFM
-
517
447
390
320
254
-
-
Watts
-
51
60
68
76
79
-
-
CFM
1349
1285
1230
1178
1126
1067
996
919
Watts
246
257
266
273
280
288
296
303
CFM
1264
1227
1184
1147
1109
1058
1015
917
Watts
264
280
279
290
299
305
314
318
CFM
1006
968
921
879
818
729
677
625
Watts
149
165
169
177
186
195
203
207
CFM
1340
1288
1241
1248
1181
1119
1055
970
Watts
254
224
226
261
279
289
303
330
CFM
1415
1377
1335
1302
1255
1222
1175
1133
Watts
368
380
394
393
403
408
416
426
CFM
973
935
888
841
794
743
653
592
Watts
135
148
156
161
172
180
188
194
CFM
1502
1455
1404
1354
1296
1245
1227
1146
Watts
323
333
357
352
413
481
470
447
CFM
1596
1554
1508
1465
1423
1179
1336
1288
Watts
379
390
395
406
415
424
432
439
CFM
1274
1222
1175
1137
1086
1043
982
907
Watts
217
234
236
252
254
268
280
289
CFM
1750
1707
1660
1614
1569
1524
1475
1419
Watts
406
421
433
445
457
466
473
475
CFM
1781
1744
1697
1664
1626
1584
1542
1504
Watts
572
572
592
599
605
609
617
627
CFM
1278
1222
1184
1142
1105
1058
1020
968
Watts
218
227
239
250
261
271
280
300
CFM
1964
1923
1882
1840
1790
1715
1650
1607
Watts
543
561
567
582
593
605
617
625
CFM
1880
1842
1810
1763
1725
1692
1654
1622
Watts
658
667
677
667
689
700
708
716
Downshot
Model Motor Tap
Compressor
stage
Volts
E.S.P. (In. of H
2
O)
GPCM32431**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM33031**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM33631**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM34231**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM34831**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
GPCM36031**
T1 Single stage 230
T2/T3 Single stage 230
T4/T5 Single stage 230
NOTES:
• Data shown is dry coil. Wet coil pressure drop is approximately: 0.1” H2O, for two-row indoor coil; 0.2” H2O, for three-
row coil; and 0.3” H2O, for four-row indoor coil.
• Data shown does not include lter pressure drop, approx. 0.08” H2O.
• Reduce airow by 2% for 208-volt operation.
background
24
UNIT DIMENSIONS
BLOWER
ACCESS PANEL
BLOWER
ACCESS PANEL
MINIMUM CLEARANCES
NOTE: Roof overhang
Should be no more than 48”
MEDIUM CHASSIS
[GPC] M32431
[GPC] M33031
LARGE CHASSIS
[GPC] M33631
[GPC] M34231
[GPC] M34831
[GPC] M36031
WD A B
GPCM32431
47 51 32 16 Medium
GPCM33031
47 51 32 16 Medium
GPCM33631
47 51 40 18 Large
GPCM34231
47 51 40 18 Large
GPCM34831
47 51 40 18 Large
GPCM36031
47 51 40 18 Large
Model
Chassis
Size
Height
Unit Dimensions
WHWH
GPCM52431
16 16 16 16
GPCM53031
16 16 16 16
GPCM53631
16 18 16 18
GPCM54231
16 18 16 18
GPCM54831
16 18 16 18
GPCM54831
16 18 16 18
Model
Duct Openings
Supply Return
background
25
WIRING DIAGRAM
GPCM3[24-60]31
HIGH VOLTAGE!
D ALL .
M . F
.
ISCONNECT POWER BEFORE SERVICING
ULTIPLE POWER SOURCES MAY BE PRESENT AILURE TO DO
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
background
26
PACKAGE UNITS - AC UNITS
HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS
WE STRONGLY RECOMMEND A BI-ANNUAL MAINTENANCE CHECKUP BE PERFORMED BY A QUALIFIED SERVICE AGENCY BEFORE
THE HEATING AND COOLING SEASONS BEGIN.
WARNING
HIGH VOLTAGE!
Disconnect all power before servicing or
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury or death.
REPLACE OR CLEAN FILTER
IMPORTANT NOTE: Never operate unit without a
filter installed as dust and lint will build up on
internal parts resulting in loss of efficiency,
equipment damage and possible fire.
A return air lter is not supplied with this unit; however,
there must be a means of ltering the return air. An indoor
air lter must be used with your comfort system. A properly
maintained lter will keep the indoor coil of your comfort
system clean. A dirty coil could cause poor operation and/
or severe equipment damage. The installer of your unit can
tell you where your lter(s) are and how to clean or replace
them.
Check your return lter(s) at least once every two months.
When they are dirty, replace or clean as required.
Disposable type lters should be replaced. Reusable
type lters may be cleaned. NOTE: Reusable type
filters should be washed with warm water,
dried completely and sprayed with an adhesive
according to the manufacturers recommendations.
You may want to ask your dealer about high e󰀩ciency
lters. High e󰀩ciency lters are available in both electronic
and non-electronic types. These lters can do a better job
of catching small airborne particles.
Improper lter maintenance is the most common cause of
inadequate heating or cooling performance. Filters should
be cleaned (permanent) or replaced (disposable) every two
months or as required. When replacing a lter, it must be
replaced with a lter of the same type and size and always
make certain the air ow arrows on the lter point in the
proper direction.
CONDENSER AND EVAPORATOR MOTORS
The bearings on the air circulating blower motor and
condenser motor are permanently lubricated and require
no further lubrication.
COMPRESSOR
The compressor motor is hermetically sealed and does not
require additional oiling.
ALUMINUM INDOOR COIL CLEANING (QUALIFIED
SERVICER ONLY)
This unit is equipped with an aluminum tube evaporator
coil. The safest way to clean the evaporator coil is to simply
ush the coil with water. This cleaning practice remains as
the recommended cleaning method for both copper tube
and aluminum tube residential cooling coils.
An alternate cleaning method is to use one of the products
listed in the technical publication TP-109 (shipped in the
literature bag with the unit) to clean the coils. The cleaners
listed are the only agents deemed safe and approved
for use to clean round tube aluminum coils. TP-109 is
available on the web site in Partner Link > Service Toolkit.
NOTE: Ensure coils are rinsed well after use of
any chemical cleaners.
ANNUAL INSPECTION (QUALIFIED SERVICER ONLY)
Your package unit should be inspected by a qualied
installer, or service agency at least twice every year.
This check should be performed before the heating and
cooling seasons begin. This will ensure that the system is
performing properly and safely. Repair as necessary.
• Check physical support of the unit. Ensure it is sound
without any sagging, cracks, or gaps, around the
base.
• Check for obvious signs of deterioration of the unit.
• Check both condenser and evaporator coil to make
sure each are clean.
• Return Air Connection. Check for physical soundness
and ensure that the connection is rmly sealed to the
package unit casing.
• Wiring. Check wires for damage. Check electrical
connections for tightness and/or corrosion.
• Filters. Check that lters are clean and in the proper
placement in the unit or duct system.
• Louvers. Inspect air inlet louvers inside the heat
exchanger compartments. Ensure the area is clean
and free of dirt and debris.
Before Calling Your Servicer
• Check the thermostat to conrm that it is properly set.
• Check the disconnect switch near the unit to conrm
that it is closed.
• Check the electrical panel for tripped circuit breakers
or open fuses . Reset the circuit breakers or replace
fuses as necessary.
• Check for blockage of the indoor air inlets and outlets.
Conrm that they are open and have not been
blocked by objects (rugs, curtains or furniture).
• Check for obstructions on the unit . Conrm that it has
not been covered on the sides or the top. Remove
any obstruction that can be safely removed. If the unit
is covered with dirt or debris, call a qualied servicer
to clean it.
• Check the lter. If it is dirty, clean or replace it.
background
27
START-UP CHECKLIST
START-UP CHECKLIST
Residential Package - (Indoor Section)
ELECTRICAL
2L - 1L)egatloV 2L dna 1L erusaeM( egatloV eniL
C - R)egatloV tuptuO remrofsnarT erusaeM( egatloV yradnoceS
Blower Amps
Heat Strip 1 - Amps
Heat Strip 2 - Amps
BLOWER EXTERNAL STATIC PRESSURE
.C.W .NI erusserP citatS riA nruteR
.C.W .NI erusserP citatS riA ylppuS
.C.W .NI)ereh latot dda ,evoba gnidaer eht morf -/+ gnirongI( erusserP citatS
lanretxE latoT
TEMPERATURES
F° BWF° BD )blub teW / blub yrD( erutarepmeT riA nruteR
DB °F WB °F
F° BD erutarepmeT riA ylppuS gnitaeH
F° BDesiR erutarepmeT
F° BD)serutarepmeT nruteR dna ylppuS neewteb ecnereffiD( T atleD
GAS PRESSURES
.C.W .NIerusserP telnI saG
.C.W .NI)eriF woL( erusserP dlofinaM saG
.C.W .NI)eriF hgiH( erusserP dlofinaM saG
Gas Type (NG) = Natural Gas / (LP) = Liquid Propane
Residential P
ackage - (Outdoor Section)
ELECTRICAL
2L - 1L)egatloV 2L dna 1L erusaeM( egatloV ylppuS
Compressor Amps
Condenser Fan Amps
PRESSURES / TEMPERATURES
F°PMETGISP)erutarepmeT eniL noitcuS / erusserP( tiucriC noitcuS
F°PMETGISP)erutarepmeT diuqiL / erusserP( tiucriC diuqiL
F° BWF° BD)blub teW / blub yrD( erutarepmeT riA roodtuO
SUPERHEAT / SUBCOOLING SH SC
Additional Checks
Check wire routings for any rubbi
ng
Check product for proper draining
Check for kinked pressure switch tubing.
Check ue elbow for alignment and clamp tightness.
Check screw tightness on blower wheel.
Check factory wiring and wire connections.
Check screw tightness on Outdoor Motor and Blade
Check product for proper clearances as noted by installation instructions
°F to °C formula: (°F - 32) divided by 1.8 = °C °C to °F formula: (°C multiplied by 1.8) + 32 =
°F
Model Number
Serial Number
Cooling Supply Air Temperature (Dry bulb / Wet bulb)
background
28
CUSTOMER FEEDBACK
We are very interested in all product comments.
Please ll out the feedback form on one of the following links:
Goodman
®
Brand Products: (http://www.goodmanmfg.com/about/contact-us).
Amana
®
Brand Products: (http://www.amana-hac.com/about-us/contact-us).
You can also scan the QR code on the right for the product brand
you purchased to be directed to the feedback page.
GOODMAN
®
BRAND
AMANA
®
BRAND
Our continuing commitment to quality products may mean a change in specications without notice.
© 2025 Daikin Comfort Technologies Manufacturing, L.P.
19001 Kermier Rd. Waller, TX 77484
www.goodmanmfg.com
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.

Specifications