This is the main product document for model SENTC-36TD-16. Additionally, the document applies to other Senville models: SENTC-36TD-16, SENTC-36TD-05K-16, SENTC-36TD-10K-16, SENTC-36TD-15K-16, SENTC-36TD-20K-16, SENTC-36TD-50, SENTC-36TD-05K-50, SENTC-36TD-10K-50, SENTC-36TD-15K-50, SENTC-36TD-20K-50, SIDE DISCHARGE

The file format is pdf, 46 pages, you can download this manual here .

background
Service Manual
Outdoor Unit:
SENTC-24TD
SENTC-36TD
SENTC-48TD
SENTC-60TD
Guangdong Zemspro HVAC Equipment Company Limited
background
DC Inverter Split Outdoor Unit - Part1
1
Part 1
General Information
1 Product lineup .....................................................................................................................................2
2 Specifications ...................................................................................................................................... 3
background
DC Inverter Split Outdoor Unit - Part1
2
1 Product lineup
Model
Cooling Capacity
(Btu/h)
Heating Capacity
(Btu/h)
Appearance
SENTC-24TD
24000
26000
SENTC-36TD
36000
34200
SENTC-48TD
48000
48000
SENTC-60TD
55000
54000
background
DC Inverter Split Outdoor Unit - Part1
3
2 Specifications
background
DC Inverter Split Outdoor Unit - Part2
4
Part 2
Component Layout and Refrigerant Circuit
1 Layout Functional Components .......................................................................................................... 5
2 Piping diagrams ...................................................................................................................................6
background
DC Inverter Split Outdoor Unit - Part2
5
1 Layout Functional Components
MRH32-24, MRH32-36
MRH32-48, MRH32-60
background
DC Inverter Split Outdoor Unit - Part2
6
2 Piping diagrams
NO.
Component(Outdoor unit)
Component(Outdoor unit)
Com.
Compressor
Refrigerant cooling pipe
TP
Exhaust temperature sensor
Filter
HP
High pressure switch
Liquid Stop Valve
ST1
Four-way valve
Gas Stop Valve
T4
Ambient temperature sensor
Pressure sensor
T3
Condenser coil temperature sensor
Gas-liquid separator
Con.
Condenser
Thermal fuse
EEV
Electrical Expansion Valve
Low pressure switch
background
DC Inverter Split Outdoor Unit - Part3
8
Part 3
Wiring Diagram
1 Electric wiring diagram ....................................................................................................................... 9
2 PCB .................................................................................................................................................... 10
3 Low voltage wiring diagram..............................................................................................................12
background
DC Inverter Split Outdoor Unit - Part3
9
1 Electric wiring diagram
background
DC Inverter Split Outdoor Unit - Part3
10
2 PCB
background
DC Inverter Split Outdoor Unit - Part3
11
Definition and uses of the button
K1: Press “K1” once to enter the outdoor unit parameter inspection.
K2: Press “K2” to view the parameters in sequence.
K3: Press “K3” to view the parameters in reverse order.
K4: "SET” button used to enter forced cooling mode to recover the refrigerant.
Definition of SW1~SW3
background
DC Inverter Split Outdoor Unit - Part3
12
3 Low voltage wiring diagram
The following wiring diagram are suitable for the Indoor Unit and Outdoor Unit with 24V thermostat.
background
DC Inverter Split Outdoor Unit - Part3
13
background
DC Inverter Split Outdoor Unit - Part3
14
background
DC Inverter Split Outdoor Unit - Part3
15
background
DC Inverter Split Outdoor Unit - Part3
16
Control Logic
:
Note
:
1) DH wiring is optional and requires a thermostat with a humidistat. DH functions as Passive Dehumidification
and will downstage the indoor fan to first stage. System will operate according to normal sequence of
operations if DH wiring is absent.
2) Dashed lines in the above thermostat wiring diagrams refer to optional wiring (wiring for Passive
Dehumidification Function and/OR Electric Heat). For thermostat wiring please refer to the Owner's Manual
of the thermostat.
3) B wire must be used with heat pump system only, the reversing valve energizes in heating.
background
DC Inverter Split Outdoor Unit - Part4
15
Part 4
Diagnosis and Troubleshooting
1 Error code table ................................................................................................................................ 17
2 Troubleshooting ................................................................................................................................ 19
2.1 Safety Precautions ..........................................................................................................................................19
2.2 ATL Troubleshooting ....................................................................................................................................... 22
2.3 E1/F0 Troubleshooting ................................................................................................................................... 23
2.4 F4/F5/F6/FC/FE/E2/E3/H8 Troubleshooting ..................................................................................................24
2.5 E4 Troubleshooting .........................................................................................................................................25
2.7 E6 Troubleshooting .........................................................................................................................................26
2.7 E8 Troubleshooting .........................................................................................................................................27
2.8 E9 Troubleshooting .........................................................................................................................................28
2.9 FA/FB Troubleshooting ................................................................................................................................... 29
2.10 FD Troubleshooting ...................................................................................................................................... 30
2.11 FF/P1/H2 Troubleshooting ........................................................................................................................... 31
2.12 F9/L0/L1 Troubleshooting ............................................................................................................................ 32
2.13 P2/H5 Troubleshooting ................................................................................................................................ 33
2.14 P3 Troubleshooting .......................................................................................................................................34
2.15 P4/H6 Troubleshooting ................................................................................................................................ 35
2.16 P5 Troubleshooting .......................................................................................................................................36
2.17 P6 Troubleshooting .......................................................................................................................................37
2.18 P7/PC Troubleshooting .................................................................................................................................38
2.19 P8 Troubleshooting .......................................................................................................................................39
2.20 P9 Troubleshooting .......................................................................................................................................40
2.21 H0 Troubleshooting ...................................................................................................................................... 41
background
DC Inverter Split Outdoor Unit - Part4
16
2.22 The outdoor unit is displaying PRH. ............................................................................................................. 41
3. Temperature Sensor Resistance Characteristics .............................................................................. 42
background
DC Inverter Split Outdoor Unit - Part4
17
1 Error code table
Error code
Error definition
FA
EEPROM fault (on main PCB)
FB
EEPROM fault (on inverter module)
H1
P5 protection appears 3 times in 180 minutes can't be recovered until re-power on
H2
FF protection appears 3 times in 150 minutes can't be recovered until re-power on
H3
PD protection appears 3 times in 180 minutes can't be recovered until re-power on
H4
P8 protection appears 3 times in 120 minutes can't be recovered until re-power on
H5
P2 protection appears 3 times in 240 minutes can't be recovered until re-power on
H6
P4 protection appears 3 times in 100 minutes can't be recovered until re-power on
H7
PC protection appears 3 times in 200 minutes can't be recovered until re-power on
H8
FE protection appears 3 times in 120 minutes can't be recovered until re-power on
HC
F7 protection appears 3 times in 180 minutes can't be recovered until re-power on
HE
F8 protection appears 3 times in 60 minutes can't be recovered until re-power on
H0
Inverter module and main PCB communication error
L0
DC bus low voltage protection
L1
DC bus high voltage protection
FF
High pressure switch fault for 20 minutes
P1
High pressure switch fault for 4 seconds
P2
Low pressure protection in cooling mode
P3
Over current protection
P4
Discharge temperature protection
P5
T3 high temperature protection in cooling mode
P6
Compressor inverter module protection
P7
Indoor unit anti-freezing protection(Applicable only when communication is established between
the ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
P8
IPM high temperature protection
P9
Fan motor inverter module protection
PC
Overwet operation protection(Applicable only when communication is established between the
ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
PD
High pressure protection in heating mode
F0
Outdoor unit and indoor unit communication error
F4
T4 - Ambient temperature sensor fault
F5
TP - Discharge temperature sensor fault
F6
T3 - Coil temperature sensor fault
F7
T7 temperature sensor fault (not applicable for cooling only unit)
F8
Reserved
F9
AC voltage is too high or too low protection
FC
IPM temperature sensor fault
FD
Pressure sensor fault
background
DC Inverter Split Outdoor Unit - Part4
18
FE
T3/TP temperature sensor loose protection
E1
Outdoor unit and indoor unit communication error (Applicable only when communication is
established between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
E2
Indoor unit T1 temperature sensor fault (Applicable only when communication is established
between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
E3
Indoor unit T2 temperature sensor fault (Applicable only when communication is established
between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
E4
Refrigerant concentration sensor fault (Applicable only when communication is established
between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
E6
Refrigerant leakage protection (Applicable only when communication is established between the
ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
E8
Indoor fan motor current fault (Applicable only when communication is established between the
ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
E9
Wired controller communication fault (Applicable only when communication is established
between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS485)
ATL
Ambient temperature out of bounds protection
PRH
Crankcase forced preheating for 1 hour, can not start up the system during this time
background
DC Inverter Split Outdoor Unit - Part4
19
2 Troubleshooting
2.1 Safety Precautions
The following precautions here are quite important, so be sure to follow them carefully. Read these instructions
carefully before installation. Keep this manual in a handy for future preference.
Failure to adhere to all precautionary measures listed in this section may result in personal injury, damage to the
unit or to property, or in extreme cases, death.
2.1.1 In case of Accidents or Emergency
Clean and ventilate the unit at regular intervals when operating it near a stove or near similar devices.
Do not use the unit during severe weather conditions. If possible, remove the product from the window before
such occurrences.
Indicates a potentially hazardous situation which if not avoided, could result in death or serious injury.
If a gas leak is suspected, immediately turn off the gas and ventilate the area if a gas leak is suspected before
turning the unit on.
If strange sounds or smoke is detected from the unit, turn the breaker off and disconnect the power supply
cable.
If the unit comes into contact with liquid, contact an authorized service center.
If liquid from the batteries makes contact with skin or clothing, immediately rinse or wash the area well with
clean water.
Do not insert hands or other objects into the air inlet or outlet while the unit is plugged in.
Do not operate the unit with wet hands.
Do not use a remote controller that has previously been exposed to battery damage or battery leakage.
Indicates a potentially hazardous situation which if not avoided, may result in minor or moderate injury.
It is also used to alert against unsafe practices.
background
DC Inverter Split Outdoor Unit - Part4
20
2.1.2 Information servicing(For flammable materials)
Use this unit only on a dedicated circuit.
Damage to the installation area could cause the unit
to fall, potentially resulting in personal injury, property damage, or product failure.
Only qualified personnel should disassemble, install, remove, or repair the unit.
Only a qualified electrician should perform electrical work. For more information, contact your dealer, seller, or
an authorized service center.
While unpacking be careful of sharp edges around the unit as well as the edges of the fins on the condenser
and evaporator.
2.1.3 Operation and Maintenance
Do not use defective or under-rated circuit breakers.
Ensure the unit is properly grounded and that a dedicated circuit and breaker are installed.
Do not modify or extend the power cable. Ensure the power cable is secure and not damaged during
operation.
Do not unplug the power supply plug during operation.
Do not store or use flammable materials near the unit.
Do not open the inlet grill of the unit during operation.
Do not touch the electrostatic filter if the unit is equipped with one.
Do not block the inlet or outlet of air flow to the unit.
Do not use harsh detergents, solvents, or similar items to clean the unit. Use a soft cloth for cleaning.
Do not touch the metal parts of the unit when removing the air filter as they are very sharp.
Do not step on or place anything on the unit or outdoor units.
Do not drink water drained from the unit.
Avoid direct skin contact with water drained from the unit.
background
DC Inverter Split Outdoor Unit - Part4
21
Use a firm stool or step ladder according to manufacturer procedures when cleaning or maintaining the unit.
Do not install or operate the unit for an extended period of time in areas of high humidity or in an environment
directly exposing it to sea wind or salt spray.
Do not install the unit on a defective or damaged installation stand, or in an unsecured location.
Ensure the unit is installed at a level position
Do not install the unit where noise or air discharge
Created by the outdoor unit will negatively impact the environment or nearby residences.
Do not expose skin directly to the air discharged by the unit for prolonged periods of time.
Ensure the unit operates in areas water0r other liquids.
Ensure the drain hose is installed correctly to ensure proper water drainage.
When lifting or transporting the unit, it is recommended that two or more people are used for this task.
When the unit is not to be used for an extended time, disconnect the power supply or turn off the breaker.
background
DC Inverter Split Outdoor Unit - Part4
22
2.2 ATL Troubleshooting
ATL indicates ambient temperature out of bounds protection.
The unit stops running and will not start operating until the ambient temperature returns to the allowable
temperature range, error code is displayed on the communication board.
The allowable ambient temperature range is 5~125
℉
(-15~52
℃
).
background
DC Inverter Split Outdoor Unit - Part4
23
2.3 E1/F0 Troubleshooting
E1 indicates RS485 communication fault between outdoor unit and indoor unit(from indoor side).
F0 indicates RS485 communication fault between outdoor unit and indoor unit(from outdoor side).
The unit stops running and error code is displayed on the communication board
E1/F0
Communication terminals on outdoor
or indoor unit have short circuit or are
disconnected or misconnected.
Reconnect the communication terminals
and ensure the connection is properly.
Interference from high voltage (220V
or higher) wires
Communication wires are close to a
source of electromagnetic radiation
such as transformer or strong
fluorescent lamp.
Ensure the communication wires and high
voltage wires are separated.
Remove the source of interference, or add
additional shielding to the communication
wires.
Yes
No
No
No
The communication board is damaged
Yes
Yes
Replace the indoor control PCB
No
Replace the communication board
Yes
background
DC Inverter Split Outdoor Unit - Part4
24
2.4 F4/F5/F6/FC/FE/E2/E3/H8 Troubleshooting
E2 indicates indoor unit T1 temperature sensor fault
E3 indicates indoor unit T2 temperature sensor fault
F4 indicates ambient temperature sensor fault
F5 indicates discharge temperature sensor fault
F6 indicates coil temperature sensor fault
FC indicates IPM temperature sensor fault
FE indicates T3/TP temperature sensor loose protection
F7 indicates T7 temperature sensor fault
H8 indicates FE protection appears 3 times in 120 minutes can't be recovered until re-power on.
The unit stops running and error code is displayed on the communication board
Note:
1) Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not
consistent with the sensor’s resistance characteristics table, the sensor has failed.
2)
E2/E3 is applicable only when communication is established between the ComfortStar outdoor unit and the
ComfortStar indoor unit via RS-485.
E2/E3/F4/F5/F6/FC/F7/FE/H8
Temperature sensor is not installed
Temperature sensor connection on
PCB is loose
Temperature sensor is affected by
moisture or water
Temperature sensor has short circuit
or is failed
Replace the control PCB
Installed the temperature sensor
Ensure the sensor is connected properly
Dry the sensor
Replace the sensor
Yes
Yes
Yes
Yes
No
No
No
No
background
DC Inverter Split Outdoor Unit - Part4
25
2.5 E4 Troubleshooting
E4 indicates refrigerant concentration sensor fault, E4 is applicable only when communication is established
between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS-485
The unit stops running and error code is displayed on the communication board
E4
refrigerant concentration sensor
connection on PCB is loose
Temperature sensor has short circuit
or is failed
Replace the indoor PCB
Ensure the sensor is connected properly
Replace the sensor
Yes
Yes
No
No
No
background
DC Inverter Split Outdoor Unit - Part4
26
2.7 E6 Troubleshooting
E8 indicates
refrigerant leakage protection
, E6 is applicable only when communication is established between
the ComfortStar outdoor unit and the ComfortStar indoor unit via RS-485.
The unit stops running and error code is displayed on the communication board.
R32 refrigerantR32 refrigerant is a flammable gas. When the E4 fault occurs, first ensure that the ventilation
around the indoor unit is good and that the refrigerant concentration is within a safe range.
Replace the indoor control PCB
The liquid or gas side pipes of indoor unit
are not connected properly
No
There is leakage on the heat exchanger of
indoor unit
E6
Check the piping connection and ensure the
pipes are connected properly.
No
Inspect the indoor heat exchanger with soapy
water. Find the leak and perform a repair
weld to ensure the heat exchanger is
properly sealed. If welding repair is not
feasible, replace the indoor heat exchanger.
Yes
Yes
background
DC Inverter Split Outdoor Unit - Part4
27
2.7 E8 Troubleshooting
E8 indicates indoor fan motor current fault, E8 is applicable only when communication is established
between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS-485.
The unit stops running and error code is displayed on the communication board
Replace the indoor control PCB
Wires of fan are not connected properly
No
The power supply is abnormal
E8
The fan motor is blocked or failed
Ensure wires are connected properly
No
No
Remove obstruction or replace the fan
motor
Check the power supply equipment
Yes
Yes
Yes
background
DC Inverter Split Outdoor Unit - Part4
28
2.8 E9 Troubleshooting
E9 indicates wired controller communication fault, E9 is applicable only when communication is established
between the ComfortStar outdoor unit and the ComfortStar indoor unit via RS485.
The unit stops running and error code is displayed on the communication board
E9
Communication terminals on wired
controller or indoor unit have short
circuit or are disconnected or
Reconnect the communication terminals
and ensure the connection is properly.
Interference from high voltage (220V
or higher) wires
Communication wires are close to a
source of electromagnetic radiation
such as transformer or strong
fluorescent lamp.
Ensure the communication wires and high
voltage wires are separated.
Remove the source of interference, or add
additional shielding to the communication
wires.
Yes
No
No
No
Yes
Yes
Replace the indoor control PCB
background
DC Inverter Split Outdoor Unit - Part4
29
2.9 FA/FB Troubleshooting
FA indicates EEPROM fault on the main PCB
FB indicates EEPROM fault on the inverter module
The unit stops running and error code is displayed on the communication board
FA/FB
Control PCB DIP switch setting is
wrong
EEPROM is not properly connected
to the refrigerant PCB
Replace the control PCB
Adjust the DIP switch
Ensure the EEPROM is connected properly
Yes
Yes
No
No
background
DC Inverter Split Outdoor Unit - Part4
30
2.10 FD Troubleshooting
FD indicates pressure sensor fault
The unit stops running and error code is displayed on the communication board
FD
Pressure sensor connection is loose
Ensure the pressure sensor is connected
properly
Replace the control PCB
Pressure sensor is short-circuited or failed
Replace the pressure switch.
No
Yes
Yes
No
background
DC Inverter Split Outdoor Unit - Part4
31
2.11 FF/P1/H2 Troubleshooting
FF indicates high pressure switch fault for 20 minutes.
P1 indicates high pressure switch fault for 4 seconds.
H2 indicates FF protection appears 3 times in 150 minutes can't be recovered until re-power on.
The unit stops running and error code is displayed on the communication board
FF/P1/H2
High pressure switch connection is loose
Outdoor side heat exchange is poor
Ensure the pressure switch is connected
properly
The piping should be cleaned and the
refrigerant system should be vacuumed.
Check the condenser, outdoor fan and air
outlets for dirt/blockages.
Replace the control PCB
Pressure switch is short-circuited or failed
Moisture in the system;
The high pressure side is blocked : filter or
EXV is blocked by ice, crushed or bent pipe,
impurities in the pipes
Replace the pressure switch.
No
Yes
Yes
Yes
Yes
No
No
No
background
DC Inverter Split Outdoor Unit - Part4
32
2.12 F9/L0/L1 Troubleshooting
F9 indicates AC voltage is too high or too low protection
L0 indicates DC bus low voltage protection
L1 indicates DC bus high voltage protection
Allowable voltage range of power source
178~265V
Upper limit of DC generatrix voltage
430V
Lower limit of DC generatrix voltage
150V
The unit stops running and error code is displayed on the communication board
The voltage of power source is too high or
too low.
Check and ensure the power supply wire is
connected properly
F9/L0/L1
Replace the control PCB
Loose connection of power supply wire to
the control PCB
Adjust the power supply and make sure the
power supply is stable
Yes
No
No
Yes
background
DC Inverter Split Outdoor Unit - Part4
33
2.13 P2/H5 Troubleshooting
P2 indicates low pressure protection in cooling mode.
H5 indicates P2 protection appears 3 times in 240 minutes can't be recovered until re-power on.
The unit stops running and error code is displayed on the communication board
No
P2/H5
Low pressure switch connection is loose
Inspect the refrigerant system for leaks and
add refrigerant
Ensure the pressure switch is connected
properly
Insufficient refrigerant caused by
refrigerant leakage
The piping should be cleaned and the
refrigerant system should be vacuumed.
Pressure switch is short-circuited or failed
Moisture in the system;
The low pressure side is blocked : filter or
EXV is blocked by ice, crushed or bent pipe,
impurities in the pipes
Replace the control PCB
Replace the pressure switch.
No
No
No
Yes
Yes
Yes
Yes
background
DC Inverter Split Outdoor Unit - Part4
34
2.14 P3 Troubleshooting
P3 indicates over current protection
The unit stops running and error code is displayed on the communication board
Yes
The power supply is abnormal.
Adjust the power supply and make sure the
power supply is stable, the allowable
voltage range of power source refer to F9
Refer to FF/P1 troubleshooting
Yes
P3
The refrigerant pressure is too high which
caused by high pressure switch fault, poor
heat exchange or blockage on the outdoor
unit
Replace the control PCB
No
No
background
DC Inverter Split Outdoor Unit - Part4
35
2.15 P4/H6 Troubleshooting
P4 indicates discharge temperature protection
H6 indicates P4 protection appears 3 times in 100 minutes can't be recovered until re-power on.
The unit stops running and error code is displayed on the communication board.
Discharge refrigerant temperature sensor
has short circuit or is failed.
Discharge refrigerant temperature sensor
connection is loose.
Poor ventilation at installation position or
the location of the unit is near the place
where temperature is too high.
The fan or fan motor is blocked or damaged
Condenser is dirty or blocked.
Replace the control PCB
Ensure the discharge temperature sensor is
connected properly
Ensure the fan or fan motor works normally
Replace the temperature sensor
Clean the condenser
Install the unit in the place with good
ventilation and away from high
temperature source.
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Insufficient refrigerant caused by
refrigerant leakage
Inspect the refrigerant system for leaks and
add refrigerant
Yes
P4/H6
background
DC Inverter Split Outdoor Unit - Part4
36
2.16 P5 Troubleshooting
P5 indicates T3 high temperature protection in cooling mode
The unit stops running and error code is displayed on the communication board.
Yes
Outdoor unit fan failure
Check if the outdoor unit fan is jammed
and ensure that the fan is operating
normally.
Ensure that the outdoor unit has good
ventilation and remove dust and other
debris from the condenser
Yes
P5
Poor heat exchange caused by Poor
ventilation of the outdoor unit or blockage
of condenser
Replace the control PCB
No
No
background
DC Inverter Split Outdoor Unit - Part4
37
2.17 P6 Troubleshooting
P6 indicates compressor inverter module protection.
The unit stops running and error code is displayed on the communication board.
Situation1: P6 appears immediately when the outdoor unit is powered-on
Situation2: P6 appears immediately after the compressor starts up
Situation3: P6 appears after the compressor has been running for a period of time.
Replace the control PCB
U,V,W wire between PCB and compressor is
not connected properly.
P6
Yes
The control PCB is damaged
P6
Yes
Ensure U, V, W wire is connected properly
The compressor is damaged
Replace the control PCB
Replace the compressor
Yes
No
No
The control PCB has overheated
P6
The PCB is over-current
Replace the control PCB
Refer to P3 troubleshooting
Refer to P8 troubleshooting
Yes
Yes
No
No
background
DC Inverter Split Outdoor Unit - Part4
38
2.18 P7/PC Troubleshooting
P7 indicates Indoor unit anti-freezing protection.
PC indicates overwet operation protection.
The unit stops running and error code is displayed on the communication board.
P7/PC is applicable only when communication is established between the ComfortStar outdoor unit and the
ComfortStar indoor unit via RS485.
Yes
Indoor unit fan failure
Check if the indoor unit fan is jammed and
ensure that the fan is operating normally.
Ensure that the indoor unit has good
ventilation and remove dust and other
debris from the evaporator and air filter.
Yes
P7/PC
Poor heat exchange caused by poor
ventilation of the indoor unit or blockage of
evaporator or air filter.
Replace the indoor control PCB
No
No
background
DC Inverter Split Outdoor Unit - Part4
39
2.19 P8 Troubleshooting
P8 indicates IPM high temperature protection.
The unit stops running and error code is displayed on the communication board.
Power supply voltage is too high or too low.
Install the outdoor unit in the place with
good ventilation and away from high
temperature source.
P8
Outdoor fan is blocked or abnormal fan speed
Poor ventilation at installation position or
the location of the outdoor unit is near the
place where temperature is too high.
Condenser is dirty or blocked
Replace the control PCB
Adjust the power supply and make sure the
power supply is stable
Clean the condenser
Check if the outdoor fan is jammed and
ensure that the fan is operating normally.
No
No
No
No
Yes
Yes
Yes
Yes
background
DC Inverter Split Outdoor Unit - Part4
40
2.20 P9 Troubleshooting
P9 indicates fan motor inverter module protection
The unit stops running and error code is displayed on the communication board.
Outdoor fan is blocked
P9
Outdoor fan motor is disconnected
Ensure the outdoor fan motor is connected
properly
Check if the outdoor fan is jammed and
ensure that the fan is operating normally.
No
No
Yes
Outdoor fan motor is disconnected
No
Replace the outdoor fan motor
Replace the control PCB
background
DC Inverter Split Outdoor Unit - Part4
41
2.21 H0 Troubleshooting
H0 indicates Inverter module and main PCB communication error
The unit stops running and error code is displayed on the communication board.
There is only one control PCB in the electric control box which integrates the functions of main control board and
inverter module, maintenance personnel has to replace the PCB when H0 fault occurs.
2.22 The outdoor unit is displaying PRH.
PRH indicates crankcase forced preheating for 1 hour, the unit can not start up during this time, the code is
displayed on the communication board.
The purpose of preheating is to protect the compressor from damage caused by insufficient oil, and it is not a
product fault. This will only occur when the unit is powered on for the first time. The installer and user simply
need to wait for 1 hour until the preheating is completed, after which the unit can start up normally.
background
DC Inverter Split Outdoor Unit - Part4
42
3. Temperature Sensor Resistance Characteristics
Room temperature sensor(T1), condenser coil temperature sensor(T2), condenser coil temperature sensor(T3)
and outdoor ambient temperature sensor(T4) resistance characteristics.
background
DC Inverter Split Outdoor Unit - Part4
43
background
DC Inverter Split Outdoor Unit - Part4
44
Compressor exhaust temperature sensor (T5) resistance characteristics.

Specifications