WPC-7000P
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or
maintain the product described.
Protect yourself and others by observing all safety information. Failure to comply with instructions could result in
personal injury and / or property damage! Retain instructions for future reference.
WPC-7000P
Figure 1
Model No.
Power Supply Ph-
V-Hz
Cooling Capacity
Btu/h
Power Consump-
on Wa s
Rated Current
Amps
EER Btu/
Wh
WPC-7000P
Single Phase,
208V/230V, 60Hz
28,000/29,000 3,490 15.99A/15.5A 9.3
Model No. Nema Plug
Power Cord Gauge
AWG
Power Cord
Length
Dimensions W x H x D - in.
(mm)
WPC-7000P 6-20p 12 10
22.1 x 47.3 x 29.5
(560 x 1200 x 750)
Model No.
Weight (Net / Gross)
Lbs(kg)
Condensate tank
Gallons(Liters)
No. of Cool Air
Outlets Pcs
Ambient temperature range
°F( °C)
WPC-7000P
245 / 262lbs.
(111 / 119 kg)
3.17 (12) 3 64~113 (18~45)

2 3
WPC-7000P
Owner’s Manual
Thank you for selecng this AMERICOOL by Weltem Portable Air Condioner. It provides
you with spot cooling for large areas where cooling of an enre area is not praccal or
possible. Please read this manual before installing the WPC-7000P as it provides im
-
portant informaon that should be followed during installaon and maintenance of the
Portable Air Condioner, allowing you to correctly set up your system for the maximum
safety and performance. Included is informaon on customer support and service, if it is
required. If you experience a problem with the unit, please refer to the Troubleshoong
secon in this manual to correct the problem. If the problem is not corrected, please col
-
lect informaon so that the Technical Support personnel can more eecvely assist you.
Model No.
Seng temperature
(Room cool mode) °F( °C)
Seng temperature
((Spot cool mode) °F( °C)
WPC-7000P 64~86 (18~30) 32~86 (0~30)
Model No.
Applicaon Area
(Room cool mode) ²(m²)
Refrigerant
Type / oz(g)
Design Pressure -
Hi/Low Psig
WPC-7000P 743 (70) R-410A / 30 (850) 450 / 250
Model No.
Indoor Air Flow
(High/Low)CFM(CMH)
Wheels
pcs / diameter
Hot Air Duct Diameter
In.(mm)
Maximum Duct
Length (m)
WPC-7000P
741 / 635
(1259 / 1078)
4 / 102mm 16 (400) 60 (18)
Safety Devices
Compressor overload protector, An-freezing thermister,
Full drain tank switch, Automac restart (Power inter
-
rupon), Compressor me delay program, High pressure
switch
Features
Temperature control, Self-diagnosc funcon, Two speed
fan, Oponal drain pump kit, Washable lters, °F( °C)
display, O-mer

3
WPC-7000P
Owner’s Manual
General Safety Informaon
Please read this manual carefully for instrucons on correct installaon and usage. Please read
all safeguards.
1. Transport and store the unit in an upright posion only. Leave unit in an upright posion for at
least 3 hours before rst use.
2. Always place the unit on an even, level surface.
3. Ensure the unit is connected to a grounded power supply of the correct rang / capacity.
4. The unit will cool when the room temperature is between 18°C (64°F) ~ 45°C(113°F) depend
-
ing on the thermostat seng.
5. DO NOT use this unit for funcons other than those described in this instrucon manual.
6. DO NOT lt the unit.
7. DO NOT cover or obstruct the unit’s inlet and outlet grilles.
8. DO NOT use the unit in areas where it will be exposed to rain or water.
9. NEVER unplug the unit while it is operang.
DO NOT use the unit in wet environments, such as a laundry room, to avoid
the risk of electrical shock.
DO NOT operate the unit in explosive or ammable environments.
10. DO NOT place any foreign objects on the unit.
11. DO NOT operate the unit with wet or damp hands.
12. DO NOT allow chemical substances to come into contact with the unit.
13. DO NOT operate the unit in the presence of ammable substances or vapors such as alcohols,
pescides, gasoline, etc.
14. DO NOT use the plug to start and to stop the unit. Always use the control panel to start and
to stop the unit.
15. Always turn o the unit when it is not in use and unplug the power plug from the electrical
outlet.
16. Always turn the unit o and unplug the main power plug from the electrical outlet before
cleaning, moving or performing maintenance.
17. AVOID the use of adapter plugs or extension cords. If it is necessary to use an extension cord
or an adapter plug to operate the unit, ensure that they are correctly rated for the applica
-
on. Consult a local qualied lectrician and all local electrical codes to ensure proper setup.
Any extension cord used with this device must be rated for a minimum of 20A.(220V)
18. DO NOT unplug the unit by pulling on the electrical cord. Keep electrical cord away from heat
sources and always completely unroll the cord to avoid overheang. If the power cord be
-
comes damaged, a qualied service agent, qualied electrician, or similarly qualied person
must replace it, in order to avoid a hazard or shock.

4
5
WPC-7000P
Owner’s Manual
DO NOT operate a unit with a damaged power cord.
19. The lters must be used with the product at all mes. When the lters are removed for clean-
ing, always ensure that the unit has been turned o and unplugged from the electrical outlet.
20. Regularly clean the lters to maintain e ciency. If the lters are not cleaned regularly, the units
output performance and e ciency will decline and energy consump on will increase.
21. DO NOT operate the unit with a damaged power cord or plug, a er it malfunc ons, has been
dropped or damaged.
22. Only use in the upright posi on on an even, at surface. Unit must be posi oned at least 24
inches (60 cm) from the nearest object in any direc on.
23. Stop opera on immediately if abnormal noise or odor is no ced. Contact a local service center.
24. Appliance is not to used by children or persons with reduced physical, sensory or mental
capabili es, or lack of experience and knowledge, unless they have been given supervision or
instruc on.
25. Children being supervised not to play with appliance.
26. That the appliance shall be installed in accordance with na onal wiring regula ons.
27. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly quali ed persons in order to avoid a hazard.
29. This appliance is not intended for use by persons (including children) with reduced physical,
sensory or mental capabili es, or lack of experience and knowledge, unless they have been
given supervision or instruc on concerning use of the appliance by a person responsible for
their safety.
Children should be supervised to ensure that they do not play with the appliance
30. If it is necessary to take precau ons during installa on of the appliance, appropriate details
shall be given.
31. The instruc ons for xed appliances shall state how the appliance is to be xed to its support.
The method of xing stated is not to depend on the use of adhesives since they are not
considered to be a reliable xing means.
32. Instruc ons and other text required by this standard shall be wri en in an o cial language
of the country in which the appliance is to be sold.
33. The dimensions of the space necessary for correct installa on of the appliance including
the minimum permissible distances to adjacent structures
34. A wiring diagram with a clear indica on of the connec ons and wiring to external control
devices and supply cord
35. The method of connec on of the appliance to the electrical supply and interconnec on of
separate components
36. Details of type and ra ng of fuses, or ra ng of circuit breakers
SAVE THESE INSTRUCTIONS

5
WPC-7000P
Owner’s Manual
Assembly (WPC-7000P)
Figure 2
Figure 4
Figure 5
Figure 6
Figure 7
Figure 3
Cool air outlet hose
Top fan exhaust ange
Display / Control board
Evaporater / lter
Condenser / lter
Guide bar for condensate water
tank
Electrical access panel
Power cord holder
Caster
Condensate water tank (Water level is
sensed, and the unit opera on is stopped
when tank is full. An alarm will be
displayed. Empty the tank and replace to
resume opera on)
1. Take out the cord holder from
the accessory box.
2. Place the cord holder on the
back side of air condi oner.
3. Use screws (enclosed inside
of accessory box with cord holder)
to install the cord holder on the
air condi oner as shown in Figure 4.
1. Remove cool air outlet hose(s) from carton.
2. Place the cool air outlet hose(s) on the front top of air condi oner.
3. Use screws (enclosed inside of box with cool air outlet hose(s) to install
the cool air outlet hose(s) on the air condi oner as shown in Figure 6.
By applying a detachable duct that can be easily inserted by
turning it around at once, it is easy to a ach and detach,
adding convenience to air condi oner management.
1. Remove the top fan exhaust
ange from carton.
2. Place the top fan exhaust ange
on the top of air condi oner.
3. Use screws (enclosed inside
of box with the top fan exhaust
ange) to install the top fan
exhaust ange on air condi oner
as shown in Figure 5.
POWER CORD HOLDER
DISCHARGE DUCTS/SUPPLY AIR DUCT
CONVENIENT DETACHABLE DUCT
TOP FAN EXHAUST FLANGE
Front and Right side View
Back and Le side View

6 7
WPC-7000P
Owner’s Manual
Installaon
MOVING THE UNIT
PLUGGING IN THE UNIT
Unlock the casters and push the unit using the side handles to a at, level surface and set the
caster brakes to the locked posion.
Check the prongs and surface of the power cord plug for dust/dirt. If dust and/or dirt are pres
-
ent, wipe o with a clean, dry cloth.
Check the power cord, plug and prongs for damage or excess play.
If any damage or excess play is found, contact a qualied repair technician or a qualied electri
-
cian to perform replacement or repair of the power cord, plug or prongs.
NOTE: Make sure the AC outlet is free of dirt, dust, oil, water, or any other foreign material. The
unit is equipped with an approved NEMA plug conguraon. ( WPC-7000P : 6-20P ) The
appropriate outlet must be used for each plug type.
WARNINGS REGARDING PROPER LOCATION FOR INSTALLATION
Do not use the unit in explosive environments or in areas where ammable
gas leakage may occur.
Do not use the unit in areas where it will be exposed to rain or water.
Do not use the unit in a corrosive atmosphere.
Do not use the unit above 18°C(64°F) ~ 45°C(113°F).
Do not install the unit on uneven or sloping surface. The unit may roll or
topple over even if the casters are set to the locked posion.
This product must be used indoors
If the power cord or plug is damaged, repair should only be performed by
qualied electrical personnel.
Do not connect / disconnect the power cord or aempt to operate buons
with wet hands. This could result in electrical shock.

7
WPC-7000P
Owner’s Manual
Operaon
CONTROL PANEL
Figure 8
· Press the power buon for 2 seconds to acvate the product.
· Press the power buon for 2 seconds while driving to stop the product.
· Self-diagnosis will be performed to test for abnormalies, aer marking
“VER” for 3seconds when power is “ON”. And the blowing is operated
as “High”, and the compressor is operated aer 1 minute.
← Example of “VER” sign when it’s ON

8 9
WPC-7000P
Owner’s Manual
Cooling mode.
1) Cooling mode
· The basic operaon is based on “out” control. (discharge temperature TH1)
· On/o the operaon of the compressor. (COOL ↔ BLOWER)
· The set temperature cannot be changed and it operates which is set to
0 degrees Celsius.
2) When blower is operating
· LOW → HIGH → AUTO It consists of three modes and operates in circulation.
· LOW, HIGH, AUTOIn “LCD”, the middle wing of each mode rotate and operate.
· AUTO MODE
- If the power source becomes “on” aer “o”, it operates as “auto” and then as “high”
or “low” depending on the sensor value aer 3 seconds.
- The dierence between “current temp” and “target temp” operates as “high” when
it is 8 degrees Celsius or higher, and “low” when it is 6 degrees Celsius or lower.
← Example of normal operation of cooling mode.
←
LOW Examples
of moves.
←
AUTO Examples
of moves.
OUT
CON.
COOL
OUT
CON.
COOL
OUT
CON.
COOL
AUTO

9
WPC-7000P
Owner’s Manual
LOCK MODE
1) It is a mode that prevents the operation of the rest of the buttons except for power.
· It can be operated and released by pressing for 2 seconds.
Blowing mode
1) The compressor does not operate, but only the blowing fan operates.
· LOW → HIGH → AUTO It consists of three modes and operates in circulation.
Reservaon mode
1) It’s the o reservaon mode.
· Press the ‘me’ buon for 2 seconds, select the ‘blower’ buon, and select ‘on/o’,
minutes as the ‘up/down’ buon.
· You can choose to make a reservaon for turning it on -> ON, o->OFF.
· UIt can be adjusted every 30 minutes with up/down’ and up to 720 minutes
(12 hours).
· If the ‘me+up’ buon or the me is “0”, the reservaon will be canceled.
← Example of blowing.
← Example of displaying the remaining time
(minutes) during “timer” operation during cooling.
←
Example
of a set-up.
←
Example of
releasing it.
OUT
CON.
OUT
CON.
COOL
TIMER

10 11
WPC-7000P
Owner’s Manual
Maintenance
FILTER CLEANING (See Figures 10 and 11)
There are two lters in the unit. The evaporator lter is located at the front of the unit. The
condenser lter is located at the side of the unit.
1. loosen up 2 bolts on the front lter guard.
2. Slide lter up and use a vacuum cleaner to remove the dust from the lter.
3. If the lter is heavily covered with dust and dirt, warm water and mild soap or neutral deter
-
gent may be used to wash the lter. Do not use any other chemicals to clean lter, as they will
likely damage the lter.
4. Dry the lter in a shaded area before replacing it. Do not operate the unit without the lter
installed and the lter guard in the closed posion.
5. Replace the clean lter and close the lter guard.
6. To clean the condenser lter, li up on the side lter from the middle bar slightly and then
angle the lter outwards from the boom and remove.
7.Use the same cleaning procedure as above (3 – 5).
8. To replace the condenser lter, place the top of the lter in the guide and slide the lter up
unl the boom of the lter clears the frame. Then push the boom of lter into the guide
and let lter gently fall inside the guide.
NOTE: For eecve cooling clean the lter at least every 2 weeks.
– For your convenience, record the complete model number and product name (located on the
Product Idencaon Plate), the purchase date, purchase locaon, serial number, and war
-
ranty period in the table below.
– Also, aach your purchase receipt as proof of purchase to this instrucon manual for future
reference.
– To ensure your product is covered by warranty, the complete faulty product along with your
original purchase receipt must be provided at the place of purchase.
Do not operate without the lter ed.
Do not operate the unit with a damaged cord or plug, aer the unit malfunc
-
ons, or if the unit has been dropped or damaged.
– Loosen up 2 bolts on
the front filter guard.
– Slide filter up and use
a vacuum cleaner to remove
the dust from the filter.
– Remove dust from the filter
using a vacuum cleaner
hose aachment.
– If required wash the filter in
lukewarm water with a mild
detergent. Leave to dry in
a shaded area before
reinstalling.
Figure 10 – Removing Filters
Figure 11 – Removal of Dust

11
WPC-7000P
Owner’s Manual
Maintenance (Connued)
– To ensure your product is covered by warranty, the complete faulty product along with your
original purchase receipt must be provided at the place of purchase.
Product Portable Air Condioner
Model No.
Date of Purchase
Place of Purchase
Serial No.
Period of Warranty
Customer: Please read and keep this
manual for future reference and keep
sales receipt as proof of purchase.
SPRING REPLACEMENT (See Figure 12)
SELF-DIAGNOSTIC CODES (See Table 1)
The alarm light is acvated if abnormal operaon occurs, and a code is displayed on the control
panel. The compressor and condenser fan motor will stop operang. The evaporator fan will con
-
nue to run for 3 minutes. If the fault is reced within 3 minutes, the unit will resume opera-
on. If the fault persists for more than 3 minutes, the evaporator fan also stops. The fault must
be reced before the unit can resume normal operaon.
There are two springs on the rear of condensate water tank guide.
1. Release the screw on the spring hook.
2. Take o the spring hook, and then pull out the opposite spring
hook from hole in the condensate water tank guide.
3. Replace with a new spring in reverse order.
4. Repeat this cycle for the other spring.
Figure 12 – The process of
spring replaccement

12 13
WPC-7000P
Owner’s Manual
SELF-DIAGNOSTIC ALARM CODES
Alarm Display Problem Cause Correcve Acon
Compressor
overloaded
• Ambient temperature
is too high
• Unstable voltage
supply
• Defecve compressor
• Do not use the air
condioner if ambient
temperature is higher
than 45°C (113°F)
• Contact a qualied
service agent
• Replace compressor
Condensate water
level alarm
Condensate tank is full
• Empty the water tank
• Aer installaon of the
water tank, press the
SPOT/COOL or ROOM/
COOL buon to resume
operaon
Drain pump alarm
Drain pump defecve or
improper hose connec
-
on (including kink or
blockage)
• Check the aconnecon
and hose
• Replace drain pump
Refrigerant high
pressure switch
• Blocked air lter
• Blocked / kinked
exhaust duct
• Ambient temperature
is too high
• Clean air lter
• Ensure exhaust duct is
not blocked / kinked
• Do not use the air
condioner if ambient
temperature is higher
than 45°C (113°F)
Table 1- Alarm Codes

13
WPC-7000P
Owner’s Manual
SELF-DIAGNOSTIC ALARM CODES
Alarm Display Problem Cause Correcve Acon
Abnormal tempera
-
ture sensor value
TH1(Outlet)
temperature sensor
has a loose or broken
connecon
Contact a qualied service
agent
Abnormal tempera
-
ture sensor value
TH2(Inlet)
temperature sensor
has a loose or
broken connecon
Contact a qualied service
agent
Abnormal tempera
-
ture sensor value
TH3 (Prevenon of
Freeze) Sensor open
circuit or poor
connecon.
Contact a qualied service
agent
Frost prevenon
sensor and Abnormal
temperature sensor
value
• Indoor heat ex
-
changer tempera-
ture too low
• TH3 temperature
sensor has a loose
or broken connec
-
on
• Do not use the air
condioner if ambient
temperature is lower
than 18°C (64°F)
• Contact a qualied
service agent
Table 1- Alarm Codes

14 15
WPC-7000P
Owner’s Manual
Wiring Diagram
Figure 13 - Circuit Wiring Diagram (WPC-7000P)
136
116
바이어명
Model
PART NO.
WPC-7000P23.02.06 신규
라벨 사이즈 136x116
1D R ICEN2302060101
적용모델
작 성 검 토 확 인
수정사항
1
2
3
4
5
6
7
8
1
2
3
4
5
1. 재질 : 은무데드롱 25미크론
2. 인쇄방법: 씨링인쇄
3. 인쇄색상: 흑색 1도
4. 표면처리: 라미네이팅(OPP코팅)
5. 인쇄기준 : 도면 및 설계 제공 필름
6 외곽의 치수선(붉은선)은 인쇄후 절단선임.
WPC-7000P 일체형
Display & Control
ON
OFF
DIP SWITCH (Three Phase (3P))
ON
OFF
DIP SWITCH (Single Phase (1P))
FAN'
MOTOR
C
C
R
S
COMP'
DRAIN
PUMP
(Option)
COM
L
H
COM
L
H
L-1
N-1
SV1
SP2
COM
EMC
L
H
(FUSE)1A
ALARM
COM NO NC
SP1
HP1
(HP)
MOTO R
LCD-OUT
TH1
LP1
(LP)
TH2
TH3
ON
OFF
T (AC) S
R
(FUSE) 8A
TH1
TH1
OUT_TEMP
SENSOR
TH3
TH3
ICE_TEMP
SENSOR
TH2
TH2
IN_TEMP
SENSOR
LOW
PRESSURE
SWITCH
(Option)
HIGH
PRESSURE
SWITCH
LP
LP
HP
HP
CO2
CO1 (CO)
EFO
CFO (RO)
FT
EXT
FD
F LO AT
SWITCH
Power Remote
Control (Option)
FD
FD
FT
FT
EXT
EXT
N - 1
L - 1
DIP SWITCH
E
N
L
Power
1P AC 220V 60Hz
TGP-050
Terminal Block
COM
NO
NC

15
WPC-7000P
Owner’s Manual
Troubleshoong chart
Symptom Possible Cause(s) Correcve Acon
Water leakage
High water level in con
-
densate tank
1. Remove blockage from drain
hose
2. Remove any object stuc un
-
deerneath of the black panel
nuder the water tank
The unit doesn’t work
1. Check the power supply
to verify that power is
available to the unit
1. Reset the circuit breaker and
restart the unit
2. Verify that the power
cord is connected
2. Connect power cord
No cold air ows from the
cold air outlet
1. Ambient air cannot be
properly cooled if the
lter is dirty and not
regularly cleaned
1. Clean the lter
2. Compressor will not
work if the unit is
turned o and on
quickly.
2. Wait 2 minutes aer unit is
turned o before turning the
unit back on.
3. The ambient air tem
-
perature may be too
high
3. The temperature of the com
-
pressor can be higher when
the ambient temperature is
too high. The compressor will
not work unless the ambient
air temperature is within the
acceptable operang range of
the unit
Water ow can be heard
aer compressor shuts o
No cause Common to hear coolant owing
aer unit shuts o
Alarm displays “FT”with
less than half of condensate
water in the tank
Spring is possibly broken
Spring is possibly broken Replace a new spring
(See Maintenance page 8)

16 17
WPC-7000P
Owner’s Manual

17
WPC-7000P
Owner’s Manual

18 19
WPC-7000P
Owner’s Manual

19
WPC-7000P
Owner’s Manual
OBTAINING SERVICE
If the AmeriCool by Weltem Portable Air Condioner requires Service:
1. Use the TROUBLESHOOTING secon in this manual to eliminate obvious causes.
2. Verify there are no circuit breakers tripped.
3. Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve
the problem, call
AmeriCool by Weltem Portable Air Condioner Technical Support at
562.231.7175. Please have the following informaon available BEFORE calling the Technical
Support Department:
a. Your name and address.
b. The serial number of the unit.
c. Where and when the unit was purchased.
d. All of the model informaon about your
AmeriCool by Weltem Portable Air Condi-
oner.
e. Any informaon on the failure, including LED’s that may or may not be illuminated.
f. A descripon of the protected equipment, including model numbers if possible.
SHIPPING LIST
• (1) PORTABLE AIR CONDIRIONER
• (1) Owner’s Manual
• (1) POWER CORD HOLDER
• (2) DISCHARGE / SUPPLY AIR DUCTS
• (1) EXHAUST FLANGE

20 20
WPC-7000P
Owner’s Manual
LIMITED WARRANTY
AmeriCool warrants all AmeriCool products to be free from defects in materials or workmanship,
under normal use and service, for a period of 12 months from the date of purchase to the end user
(original invoice must be provided). AmeriCool warrants that the compressor will be free from
defects in materials and workmanship for 12 months from the date of purchase to the end user.
AmeriCool’s obligaon under this warranty is limited to the repair or replacement at its opon,
of any part or parts, which, upon Ameriool’s examinaon are shown to be defecve, or at Ameri
-
Cool’s opon, the return of the purchase price to the purchaser.
Correcon of such defects by repair or replacement, or at AmeriCool’s opon, the return of the
purchase price shall constute fulllment of warranty obligaons to the purchaser. This warranty
does not cover defects or malfuncons which result from causes beyond AmeriCool’s control,
including, without limitaon,(i) unusal physical or electrical stress:(ii) accident, neglect, abuse,
misuse or other abnormal use; (iii) failure to perform roune maintenance in accordance with
AmeriCool’s recommended procedures; (iv)normal wear and tear; (v) repairs or aempted repairs
by an unauthorized person; (vi) modicaons or alteraons to the Products; (vii) use with parts or
devices not supplied or approved by AmeriCool (viii) improper installaon or service; (ix) shipping
damage to any units or spare parts during shipping. This includes and is not limited to compres
-
sors, evaporators and condenser coils. This warranty shall extend only to the original end-user and
shall be void if any labels or other idenfying marks permanently axed to Products when shipped
by AmeriCool are removed, altered, defaced or obliterated.
TO THE EXTENT PERMITTED BY LAW, THIS WARRANTY, AS LIMITED HEREIN, SHALL BE IN LIEU OF
AND EXCLUSIVE OF ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, ON THE PART OF
AMERICOOL INC., OR WELTEM CO.,LTD. WHETHER ARISING FROM LAW, COURSE OF DEALING, US
-
AGE OF TRADE, OR OTHERWISE, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF
MERCHANT-ABILITY OR FITNESS OF A PARTICULAR PURP OSE OR ANY LIABILITY FOR COMMERCIAL
LOSSES BASED UPON NEGLIGENCE OR MANUFACTURER’S STRICT LIABILITY. EXCEPT AS EXPRESSLY
PROVIDED HEREIN,NEITHER AMERICOOL, INC., NOR WELTEM CO., LTD. WILL, IN ANY EVENT, BE
LIABLE FOR LOST PROFITS, COSTS OF PROCESSING,INJURY, GOODWILL, OR ANY OTHER CONSE
-
QUENTIAL DAMAGES OF ANY KIND ARISING FROM BREACH OF THIS WARRANTY.
Printed in March, 2023
Manufactured in Weltem Co., Ltd.,
154, Jayumuyeok 3-gil, Masanhoewon-gu, Changwon-City, Gyeongsangnam-do,
Republic of KOREA 51340 www.weltem.com
Distributed by Americool,Inc. In the USA (Tel.888-726-6158)
WWW.AMERICOOLLLC.COM
S/N : 1D M AMERICOOL2302240201