2
Parts and Service
The tester is warranted to be free from defects in material and workmanship for two years, while under normal
use. Parts and repairs are warranted for 90 days. For the complete warranty statement, refer to the
T5-600/T5-1000 Electrical Tester Instruction Sheet.
Specifications
Accuracy is specified for one year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity
to 90 %. AC conversions are ac-coupled, average responding, and calibrated to the rms value of a sine wave
input. Accuracy specifications are given as follows:
±([ % of reading] + [number of least significant digits])
Temperature coefficient of 0.1 x (specified accuracy)/ °C for <18 °C or >28 °C (<64.4 °F or >82.4 °F)
Serial Numbers 79560000 and Above
General Specifications
Calibration One-year calibration cycle.
Maximum Voltage
Between any Terminal
and Earth Ground
T5-600: 600 V rms, Overvoltage Category III, Pollution Degree 2
T5-1000: 1000 V rms, Overvoltage Category III, 600 V RMS, OverVoltage Category IV,
Pollution Degree 2
Maximum Voltage
Between Current Fork
and Earth Ground
T5-600 and T5-1000: 1000 V rms, Overvoltage Catergory III, also 600 V rms, Overvoltage
Category IV, Pollution Degree 2, (This dual rating applies to the current fork only.)
Temperature Operating: -10 °C to +50 °C (14 °F to 122 °F); Storage: -30 °C to +60 °C (-22 °F to +140 °F)
Altitude Operating: 2000 m (6562 ft); Storage: 10,000 m (32808 ft)
Relative Humidity 0 % to 95 %, 5 °C to 30 °C (41 °F to 86°F); 0 % to 75 %, 30 °C to 40 °C (86 °F to 104 °F);
0 % to 45 %, 40 °C to 50 °C (104 °F to 122 °F)
Battery Type and Life AA (2); 360 hours continuous with alkaline; 125 hours continuous with zinc chloride
Shock, Vibration 1 m drop at -10 °C to + 50 °C (14 °F to 122 °F) per ANSI/ISA-S82.01-1994 and EN 61010-1
1995. Random vibration per MIL-PRF-28800F for a Class 2 instrument
(5 Hz to 55 Hz, 3 g maximum)
Surge Protection T5-600: 6 kV per IEC 61010, T5-1000: 8 kV per IEC 61010
Enclosure Rating IP 52 per IEC 60529, no vacuum applied