Safety Specifications
Battery...............................2 x AA (IEC LR6)
Temperature
Operating........................-10 °C to +50 °C (+14 °F to +122 °F)
Storage...........................-30 °C to +60 °C (-22 °F to +140 °F)
Operating Relative Humidity
0 % to 95 %....................5 °C to 30 °C (41 °F to 86 °F)
0 % to 75 %....................30 °C to 40 °C (86 °F to 104 °F)
0 % to 45 %....................40 °C to 50 °C (104 °F to 122 °F)
Altitude
Operating........................2000 m
Storage...........................10 000 m
Safety
General...........................IEC 61010-1: Pollution Degree 2
Measurement .................IEC 61010-2-032, IEC 61010-2-033
T6-600..........................CAT III 600 V
T6-1000/T6-1000 Pro...CAT IV 600 V / CAT III 1000 V
Electromagnetic Compatibility (EMC)
International....................IEC 61326-1: Portable Electromagnetic
Environment
CISPR 11: Group 1, Class A
Group 1: Equipment has intentionally generated and/or uses
conductively-coupled radio frequency energy that is necessary
for the internal function of the equipment itself.
Class A: Equipment is suitable for use in all establishments
other than domestic and those directly connected to a low-
voltage power supply network that supplies buildings used for
domestic purposes. There may be potential difficulties in
ensuring electromagnetic compatibility in other environments
due to conducted and radiated disturbances.
Caution: This equipment is not intended for use in residential
environments and may not provide adequate protection to radio
reception in such environments.
Korea (KCC)...................Class A Equipment (Industrial
Broadcasting & Communication
Equipment)
Class A: Equipment meets requirements for industrial
electromagnetic wave equipment and the seller or user should
take notice of it. This equipment is intended for use in business
environments and not to be used in homes.
USA (FCC).....................47 CFR 15 subpart B. This product is
considered an exempt device per clause
15.103.