1587 FC/1587/1577
Users Manual
38
Ohms Measurement
Range Resolution
Accuracy all 1587 models
[1]
+(% of Rdg+Counts)
Accuracy 1577
[1]
+(% of Rdg+Counts)
600.0 0.1
±(0.9 % + 2) ±(1.2 % + 2)
6.000 k 0.001 k
60.00 k 0.01 k
600.0 k 0.1 K
6.000 M 0.001 M
50.0 M
[2]
0.01 M ±(1.5 % + 3) ±(2.0 % + 3)
[1] Accuracies apply from 0 % to 100 % of range.
[2] Up to 80 % relative humidity.
Overload Protection ............................................ 1000 V rms or dc
Open Circuit Test Voltage ................................... <8.0 V dc
Short Circuit Current ........................................... <1.1 mA
Diode Test (all 1587 models)
Diode Test Indication .......................................... Display voltage drop: 0.6 V at 1.0 mA nominal test current:
Accuracy ............................................................. ±(2 % + 3)
Continuity Test
Continuity Indication ........................................... Continuous audible tone for test resistance below 25 and off above 100 . Maximum Reading; 1000
Open Circuit Voltage ........................................... <8.0 V
Short Circuit Current ........................................... 1.0 mA typical
Overload Protection ............................................ 1000 V rms
Response Time ................................................... >1 m sec
Frequency Measurement (all 1587 models)
Range Resolution
Accuracy ±(% of Rdg+Counts)
99.99 Hz 0.01 Hz
±(0.1 % + 1)
999.9 Hz 0.1 Hz
±(0.1 % + 1)
9.999 kHz 0.001 kHz
±(0.1 % + 1)
99.99kHz 0.01 kHz
±(0.1 % + 1)
1.888.610.7664 sales@GlobalTestSupply.com
Fluke-Direct
.com
Loading ...
Loading ...
Loading ...