Mitsubishi 1886028 42000 BTU Single Zone Mini Split System with Concealed Ducted Ceiling Indoor Unit, 15 SEER, 10.7 EER, 230-208 Volts AHRI Certified, cETLus Certification, H2i Hyper Heating Technology, Inverter Compressor Technology

User Manual - Page 7

For 1886028.

PDF File Manual, 36 pages, Read Online | Download pdf file

1886028 photo
Loading ...
Loading ...
Loading ...
45˚± 2˚
A B
ø
A
A
B
C
D
D
A
E
B
C
Fig. 4-3
A Front piping cover
B Piping cover
C Stop valve
D Service panel
E Bend radius : 100 mm, 3-15/16 inch-150 mm, 5-27/32 inch
6
4. Installing the refrigerant piping
4.1.
Precautions for devices that use R410A refrigerant
Refer to 1.5. for precautions not included below on using air conditioners
with R410A refrigerant.
Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration
oil applied to the ared sections.
Use C1220 copper phosphorus, for copper and copper alloy seamless
pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thick-
nesses specified in the table to the below. Make sure the insides of the
pipes are clean and do not contain any harmful contaminants such as sul-
furic compounds, oxidants, debris, or dust.
Warning:
When installing or relocating, or servicing the air conditioner, use only the
specied refrigerant (R410A) to charge the refrigerant lines. Do not mix it with
any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pres-
sure in the refrigerant line, and may result in an explosion and other hazards.
The use of any refrigerant other than that specied for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
Liquid pipe
ø9.52 mm, 3/8inch
thickness 0.8 mm, 1/32 inch
Gas pipe
ø15.88 mm, 5/8 inch
thickness 1.0 mm, 3/64 inch
Do not use pipes thinner than those specied above.
4.2. Connecting pipes (Fig. 4-1, Fig. 4-2)
When commercially available copper pipes are used, insulate both the liquid and
gas pipes separately with commercially available insulation materials (heat-resis-
tant to 100°C, 212°F or more, thickness of 12 mm, 1/2 inch or more). (Fig. 4-1)
The indoor parts of the drain pipe should be wrapped with polyethylene foam insula-
tion materials (specic gravity of 0.03, thickness of 9 mm, 23/64 inch or more).
[Fig. 4-2]
Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten-
ing are nut. A
Use two wrenches to tighten piping connections. B
Use leak detector or soapy water to check for gas leaks after connections are
completed.
Apply refrigerating machine oil over the entire are seat surface. C
Use the are nuts for the following pipe size. D
Gas side Pipe size (mm, inch) ø15.88, 5/8”
Liquid side Pipe size (mm, inch) ø9.52, 3/8”
*: The are nut is supplied as an outdoor unit accessory.
Be sure to use it otherwise gas leakage or even pipe extraction may occur.
When bending the pipes, be careful not to break them. Bend radii of 100 mm,
3-15/16 inch to 150 mm, 5-27/32 inch are sufcient.
Make sure the pipes do not contact the compressor. Abnormal noise or vibration
may result.
1 Pipes must be connected starting from the indoor unit.
Flare nuts must be tightened with a torque wrench.
2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil
(Applied on site).
Warning:
When installing the unit, securely connect the refrigerant pipes before start-
ing the compressor.
4.3. Refrigerant piping (Fig. 4-3)
Remove the service panel D (3 screws) and the front piping cover A (2 screws) and rear
piping cover B (2 screws: HA24) (4 screws: HA30, HA36, HA42).
1 Perform refrigerant piping connections for the indoor/outdoor unit when the out-
door unit’s stop valve is completely closed.
2 Vacuum-purge air from the indoor unit and the connection piping.
3 After connecting the refrigerant pipes, check the connected pipes and the indoor
unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)
4 Vacuumize the refrigerant lines through the service port of the liquid stop valve and
then open the stop valves completely (for both the liquid and gas stop valves). This
will completely connect the refrigerant lines of the indoor and outdoor units.
• If the stop valves are left closed and the unit is operated, the compressor and
control valves will be damaged.
• Use a leak detector or soapy water to check for gas leaks at the pipe connec-
tion sections of the outdoor unit.
• Do not use the refrigerant from the unit to purge air from the refrigerant lines.
• After the valve work is completed, tighten the valve caps to the correct torque:
20 to 25 N·m, 14 to 18 ft·lbs (200 to 250 kgf·cm).
Failure to replace and tighten the caps may result in refrigerant leakage. In
addition, do not damage the insides of the valve caps as they act as a seal to
prevent refrigerant leakage.
5 Use sealant to seal the ends of the thermal insulation around the pipe connec-
tion sections to prevent water from entering the thermal insulation.
A (Fig. 4-1)
Copper pipe O.D.
Flare dimensions
øA dimensions
(mm) (inch) (mm) (inch)
ø6.35 1/4” 8.7 - 9.1 11/32 - 23/64
ø9.52 3/8” 12.8 - 13.2 1/2 - 33/64
ø12.7 1/2” 16.2 - 16.6 41/64 - 21/32
ø15.88 5/8” 19.3 - 19.7 49/64 - 25/32
B (Fig. 4-1)
Copper pipe O.D. Flare nut O.D. Tightening torque
(mm) (inch) (mm) (inch) (N·m) (ft·lbs)
ø6.35 1/4” 17 43/64 14 - 18 10 - 13
ø9.52 3/8” 22 7/8 34 - 42 25 - 30
ø12.7 1/2” 26 1 - 3/64 49 - 61 35 - 44
ø15.88 5/8” 29 1 - 9/64 68 - 82 49 - 59
A Liquid pipe
B Gas pipe
C Insulation
D Taping
A Flare cutting dimensions
B Flare nut tightening torque
Fig. 4-1
mm (inch)
Fig. 4-2
C
D
R0.4 (1/64) to
R0.8 (1/32)
90˚± 0.5˚
en
007
Loading ...
Loading ...
Loading ...