Reliance 1066DHPTS 66 Gallon Smart Hybrid Electric Heat Pump Water Heater

Installation Guide & Use and Care Guide - Page 36

For 1066DHPTS.

PDF File Manual, 40 pages, Read Online | Download pdf file

1066DHPTS photo
Loading ...
Loading ...
Loading ...
36 • Residenal Electric Water Heater Use and Care Guide
MAINTENANCE
MAINTENANCE
5
Mark the wires with tape so
you will know how to put
them back on.
6
Disconnect the wires from
the bad ECO and remove the
ECO from the metal
mounng clip.
7
Install the new ECO in the
metal mounng clip.
8
Make sure the new ECO ts
snuggly against the tank. You
should NOT be able to slip a
business card between the ECO and
the tank. If you can, bend the ECO
mounng clip unl the ECO ts ghtly
against the tank.
9
Aach the wires following
the wiring diagram on the
water heaters label. Make
sure all wire connecons are ght.
10
Replace the plasc element/
ECO cover, insulaon, and
access panel.
11
Replace the cover on the
electrical juncon box.
12
Turn ON power to the water
heater at the circuit breaker/
fuse box.
T&P Relief Valve
Maintenance
Read and follow the operang and
annual maintenance instrucons
provided by the manufacturer of
the T&P Relief Valve (yellow label
aached to the T&P Relief Valve).
If no label is aached to the T&P
Relief Valve, follow the instrucons
in this secon. Minerals in the
water can form deposits that cause
the valve to sck or create blocked
passages, making the T&P Relief Valve
inoperave. Follow these guidelines:
At least annually, operate the T&P
Relief Valve manually to ensure the
waterways are clear and the valve
mechanism moves freely. Before
operang the valve manually, check
that it will discharge in a place for
secure disposal. If the water does
not ow freely from the end of the
discharge pipe, turn OFF the power
to the water heater. Call a qualied
person to determine the cause.
WARNING! Hot water will be
released. Before operang the T&P
Relief Valve manually, check that it
will discharge in a safe place. If water
does not ow freely from the end of
the discharge pipe, turn the power to
the water heater OFF. Call a qualied
person to determine the cause.
Figure 49 - T&P Relief Valve.
At least every ve years, have a
qualied person inspect the T&P
Relief Valve and discharge pipe.
Damage caused by corrosive water
condions, mineral deposits,
or other problems can only be
determined when a qualied person
removes and inspects the valve and
its components.
Note that a dripping T&P Relief Valve
is usually caused by the home’s
water pressure being too high or
the lack of a Thermal Expansion
Tank. If your T&P Relief Valve drips,
see “Drips from T&P Relief Valve
Discharge Pipe” on page 29.
Air Filter Maintenance
The heater will monitor the heat
pump operaon status and indicate
whether the lter should be cleaned.
If the Control Assembly displays the
code 080, this indicates the lter
should be cleaned or replaced with
the following process (see exploded
view of the unit on page 39 for air
lter locaon).
NOTICE: Before aempng to clean
or replace the air lter, turn OFF the
power to the water heater at the
circuit breaker/fuse box.
1
Take the tab on the air lter
and remove (slide) it from
the top facing air intake duct
adaptor.
2
To clean the lter, use a
vacuum with a hose
aachment to remove any
dust or debris.
3
Slide the new or cleaned
lter into the air intake duct
adaptor.
4
Turn ON power to the water
heater at the circuit breaker/
fuse box.
NOTICE: The water heater may
conduct a system diagnosc prior to
operaon.