Loading ...
Loading ...
Loading ...
Service panel
Lock nut
Conduit cover
Conduit
plate
Conduit
pipe
<SUZ-KA09, KA12NAHZ>
5. Electrical work
5.1. Connecting wires for outdoor unit
1) Remove the service panel.
2) Remove the conduit cover.
3) Attach the conduit connector to conduit plate with lock nut then secure it against
unit with screws.
4) Connect ground wires of indoor/outdoor unit connecting wire (A) and power sup-
ply cord (K) to the TB support.
5) Loosen the terminal screw, and attach indoor/outdoor unit connecting wire (A)
from the indoor unit correctly on the terminal block. Attach the wire to the terminal
block securely so that its core cannot be seen, and no external force affects the
connecting section of the terminal block.
6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly
fastened.
7) Connect power supply cord (K).
8) Install the conduit cover.
9) Install the service panel securely.
Connect the cable from the indoor unit correctly on the terminal-block.
Use the same terminal block and polarity as is used with the indoor unit.
For aftercare maintenance, give extra length to connecting cable.
Both ends of connecting cable (extension wire) are peeled off. When too long,
or connected by cutting off the middle, peel off power supply cable to the size
given in the gure.
Be careful not to contact connecting cable with piping.
Caution:
Use care not to make miswiring.
Firmly tighten the terminal screws to prevent them from loosening.
After tightening, pull the wires lightly to conrm that they do not move.
Warning:
Be sure to attach the service panel of the indoor unit securely. If it is not
attached correctly, it could result in a re or an electric shock due to dust,
water, etc.
Tighten terminal screws securely.
Wiring should be done so that the power lines are not subject to tension.
Otherwise, heat may be generated or re may occur.
L1
L2
Lead wire
Power supply cord (K)
SUZ-KA09, KA12, KA15, KA18NAHZ
Grounding
terminal**
Disconnect
switch*
Grounding terminal**Ground
Power supply 208/230
V AC, 1 phase 2 wires.
60 Hz
INDOOR UNIT
OUTDOOR UNIT
208/230 V AC
1 phase, 60 Hz
Terminal block
Terminal block 2
Terminal
block 1
Remark:
* A disconnect switch is required.
Check the local code.
** Use a ring tongue terminal in order to
connect a ground wire to terminal.
1-3/8 in.
(35 mm)
19/32 in.
(15 mm)
Terminal block
to conduit cover
Power supply cord (K)
Indoor/outdoor unit
connecting wire (A)
TB support
Grounding
terminal
Grounding
terminal
Make ground wire a little longer than others. (More than 3-7/8 in.
[100 mm])
For future servicing, leave some slack in the connecting wires.
Be sure to attach each screw to its correspondent terminal when
securing the cord and/or the wire to the terminal block.
Make ground wire a little longer than others. (More than 3-7/8 in.
[100 mm])
For future servicing, leave some slack in the connecting wires.
Terminal block
to conduit cover
Power supply cord (K)
Indoor/outdoor unit
connecting wire (A)
TB support
<SUZ-KA15, KA18NAHZ>
en
5
A_VG79Y103H02_EN.indd 5 2019/10/03 10:56:55
006
Loading ...
Loading ...
Loading ...