Tripp Lite SU5KRT3UHW TAA 200–240V 5000VA 5000W On-Line Double-Conversion UPS, Unity Power Factor

Owner's Manual SmartOnline Single-Phase Rack-Mount Online UPS with Built-in LCD Monitoring & Control Screen - Page 22

For SU5KRT3UHW TAA.

PDF File Manual, 136 pages, Read Online | Download pdf file

SU5KRT3UHW TAA photo
Loading ...
Loading ...
Loading ...
22
Operations
MAIN MENU / SUBMENU DISPLAY / SETTING OPTIONS DISPLAY / SETTING DESCRIPTION
SETTINGS
Basic setup
(continued)
Power strategy:
• Auto-Adaptive
• Max Efficiency
• Max Quality
• Freq. Regulation
Freq. Conversion to 60 Hz
• Freq. Conversion to 50 Hz
Use the SETTINGS / BASIC / POWER STRATEGY option to display or
set the UPS Power strategy.
See Power Strategy Selection Options section under the
Operations section for more info on the available power strategy
options.
Battery:
• Battery configuration
• External Batt
• Battery Age Alert
Use the Settings/Basic/Battery option to view external battery
installed and its expiration dates, along with replacement battery
cartridge information.
See Operations/Configuring External Battery Packs for
information on how to configure external battery packs.
Battery Age Alert enables setting the duration for the battery
replacement reminder. The factory default setting is Disabled.
Advanced setup
System:
• Display brightness
o
High
o
Medium (factory setting)
o
Low
• Backlight dim: Enter 10-120 seconds
(factory setting is 60 seconds)
• Password: Set your 4 digit password
(factory setting is 0000)
• Factory reset (resets all UPS preferences
to factory settings, including battery
configurations)
Note: When executed, the card will reboot.
Use the SETTINGS / ADVANCED / SYSTEM option to set the display
brightness, the display backlight dim time-out, password or factory
reset options.
In/Out:
Overload Alert Lvl: Enter a value 5-105%
(factory setting is 105%)
Use SETTINGS / ADVANCED / IN-OUT for these options:
Sets the UPS output load percentage before an overload alert
is sent.
• Conf. Fault Action
(UPS response to fault)
o
Go to Bypass (factory default)
o Go to Standby
Sets the UPS response to fault conditions that require the UPS to
exit double-conversion mode. GO TO BYPASS option maintains AC
output (so long as input voltage is within bypass high/low limits).
GO TO STANDBY option causes the UPS to turn off output AC in
response to fault conditions.
• Bypass Low Limit: Enter a value -5% to
-20% (factory setting is -15%)
Specifies the lowest acceptable input voltage for bypass operation.
• Bypass High Limit: Enter a value +5% to
+20% (factory setting is +15%)
Specifies the highest acceptable input voltage for bypass
operation.
On/Off:
• Cold Start
o
Enable (factory setting)
o
Disable
Use SETTINGS / ADVANCED / ON-OFF for these options:
Enabling Cold-start allows the UPS to be manually turned on into
battery mode during a power failure.
• Auto Restart
o
Enable (factory setting)
o
Disable
Enabling Auto-restart allows the UPS to automatically turn back on
into a protected operating mode when power is restored.
• Auto Restart Delay
o
Enter: 0 to 60 seconds
(factory setting is 0 seconds)
Auto-restart delay forces the UPS to wait 0-60 seconds after
power is restored before automatically restarting.
Requires that Auto-restart when power is restored be enabled.
• Energy Saving
o
Enter: 0-100%
o
Disable (factory setting)
Energy saving enables the UPS to automatically shutdown when
the output load is less than the selected percentage continuously
for 5 minutes.
• Off Mode
o
Standby
o
Bypass (factory setting)
Off mode setting of BYPASS allows the UPS to provide unregulated
line power within configured bypass low / high limits to be available
at the output of the UPS when it is turned off.
• Min. Batt to Restart
o
Enter: 10-90%
o
Disable (factory setting)
Minimum battery charge level to restart forces the UPS to wait
until batteries have recharged to the selected percentage before
automatically restarting.
Note: UPS can be manually started using the power button if battery is
below the minimum battery restart threshold.
Requires that Auto-restart when power is restored be enabled.
Loading ...
Loading ...
Loading ...