Operations
Front Panel LCD Selection and Configuration Options
MAIN MENU / SUBMENU DISPLAY / SETTING OPTIONS DISPLAY / SETTING DESCRIPTION
STATUS
Load Status • Load level (%, kW, kVA, A, PF)
• Available capacity (%, kW, kVA)
UPS load percent (%), kilowatt (kW), kilovoltamp
(kVA), amp (A) & power factor (PF).
UPS capacity available in percent (%), kilowatts (kW)
& kilovoltamps (kVA).
In/Out Status • Input voltage & frequency (Vac, Hz)
• Output voltage & frequency (Vac, Hz)
• Load Group 1 (On, Off)
• Load Group 2 (On, Off)
• Load Group 3 (On, Off)
Displays UPS input and output status information for input / output
voltage (Vac), frequency (Hz) and outlet group power status (On/
Off) information.
Energy Status • Efficiency (%)
• Avg. Power (kw/hr.)
• Configured power strategy
Displays UPS efficiency percentage (%), connected equipment
kilowatt hour consumption (kw/hr.) and configured power strategy.
Battery Status • Battery model & serial number
• Installed (mm/dd/yyyy)
• Expires (mm/dd/yyyy)
Displays Battery Pack model number & serial number (Tripp Lite
SMART BATTERY PACKS) only, installation date and user configured
expiration date.
Power Flow Chart • View UPS operational flow chart Displays UPS operating mode in a graphical flow chart.
CONTROL
Start Batt. Test • Initiates a manual battery test Initiates a momentary UPS battery self-test with immediate Pass/
Fail results.
Reset Fault State • Resets any fault state messages Use this option to clear UPS fault messages.
Auto Batt. Testing • Set regular battery self-test interval
o
Disable
o
4 weeks (factory setting)
o
13 weeks
o
26 weeks
Use this option to initiate automatic UPS battery testing at regular
intervals.
EVENT LOG
On Batt. Events • Event counter
(UPS On-battery events only)
• Total minutes (total minutes of
on-battery mode operation)
• Most recent power failure (date)
• Months until battery replacement alert
(months)
• Event details (date, time &
description for the last 20 logged events)
Displays a summary of all ON-BATTERY events where the UPS
switched to battery mode in response to a protected condition.
Event details lists the last 20 battery events. As additional alerts
occur, the oldest records will be automatically removed.
All Events • Event counter (all events)
• Most recent event (date)
• Date time log
Displays a summary of all Recorded events. Event details lists the
last 20 events. As additional alerts occur, the oldest records will
be automatically removed.
SETTINGS
Basic setup
System
• Current date (display, set date)
• Current time (display, set time)
• Audible alarm (enable, disable)
• Language (select)
Displays, sets and resets date, time, audible alarm status and
language settings.
Note: Audible Alarm DISABLE setting prevents power fail and
operating fault alarms only, the UPS will always “beep” to confirm
the UPS is accepting user input from the front-panel LCD
navigation buttons.
Note: The current date and current local time are reported directly
from the remote management card.
Output voltage
• 200
• 208
• 220
• 230
• 240
Use the SETTINGS / BASIC / OUTPUT VOLTAGE option to display or
set the nominal UPS output voltage (changes take effect on next
restart).