Installation and MaintenanceInstallation and Maintenance
17
Model
( Btu/h)
The range of
ESP
Function code set
9K
0-30Pa
0-30, function code value equals
static pressure value
[default: 10 (10Pa)]
24K
0-40Pa
0-40, function code value equals
static pressure value
[default: 40 (40Pa)]
If you still have any trouble, please contact local technical service center of our company for further information.
The ESP can be freely adjusted by using specific wired remote controller.
Note: The pressure loss of filter is not included in the ESP data above.
6.2 Change of ESP (External Static Pressure)
ESP setting (C-Series wired controller):
Press and hold “MODE” button and “ADD.FUNC.” button for 3 seconds, symbol and parameter code
starts blinking at the same time.
Press“ / ”button to adjust parameter number until “17” is displayed, and press “ENTER” button to enter
system parameter adaption state, symbol stops blinking.
Select desired parameter code 10 by pressing “ / ” button, and press "ENTER" button to confirm.
Select desired function code to rewrite the parameter values by pressing “ / ”button, and press
"ENTER" button to confirm.
Press “ON/OFF” button or “CANCEL”button to quit.
ESP setting (E-Series wired controller):
Parameter
Code
LCD
Function Code
Error Indicator
1
2
3
4
5
Fig 6.2
C-Series wired controller E-Series wired controller