FLUKE 1664FC US Installation Multifunction Tester, 500 V, insulation pre-test

User Manual for the Fluke 1664FC US Installation Multifunction Tester, 500 V, insulation pre-test - Page 89

For 1664FC US.

PDF File Manual, 95 pages, Read Online | Download pdf file

1664FC US photo
Loading ...
Loading ...
Loading ...
Electrical Installation Tester
Specifications
83
Prospective Earth Fault Current (PEFC)
Prospective Short Circuit Current (PSC)
Computation
Prospective Earth Fault Current (PEFC/I
K
) or Prospective Short Circuit
Current (PSC/I
K
) determined by dividing measured mains voltage by
measured loop (L-PE) resistance or line (L-N) resistance, respectively.
Range 0 kA to 50 kA
Resolution
and Units
Resolution Units
I
K
<1000 A 1 A
I
K
>1000 A 0.1 kA
Accuracy
Determined by accuracy of loop resistance and mains voltage
measurements.
RCD Testing
RCD Types Tested
Limit on consecutive tests: Automatic shutdown for RCD tests when the temperature of
internal components is too hot.
RCD Type
[6]
Model 1662 Model 1663 Model 1664
AC
[1]
G
[2]
AC S
[3]
A
[4]
G
A S
B
[5]
G
B S
[1] AC – Responds to ac
[2] G – General, no delay
[3] S – Time delay
[4] A – Responds to pulsed signal
[5] B – Responds to smooth dc
[6] RCD test inhibited for V >265 ac
RCD tests permitted only if the selected current, multiplied by earthing resistance, is <50 V.