Eaton 5P1000 1000VA 770W 120V Line-Interactive UPS

Eaton 5P UPS Installation and User Manual - Page 26

For 5P1000. Also, The document are for others Eaton models: 5P 750, 5P 1000, 5P 1500, 5P 850G, 5P 1550G, 5P 550 R, 5P 750 R, 5P 1000 R, 5P 1500 R, 5P 850G R, 5P 1550G R

PDF File Manual, 28 pages, Read Online | Download pdf file

5P1000 photo
Loading ...
Loading ...
Loading ...
Page 26
620-00082-01-us (en)
6. Appendices
6.1 Technical specications
Tower 5P 850G 5P 1550G
Rack 5P 850G R 5P 1550G R
Output Power @ 230 V 850 VA
600 W
1550 VA
1100 W
Output Power capacity
@ 208 V
765 VA
540 W
1395 VA
990 W
Output Power @ 200 V 765 VA
540 W
1395 VA
990 W
AC Input power
• Rated input voltage
• Input voltage range
• Input frequency range
Single phase 200-240 V
160 to 294 V
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
•Voltage
•Frequency
200/208/220/230/240 V (-10/+6 %)
(3)
50/60 Hz ±0.1 Hz
Battery
(sealed lead acid,
maintenance free)
•Standard
Tower
2 x 12 V
7 Ah
3 x 12 V
9 Ah
Rack
4 x 6 V
9 Ah
6 x 6 V
9 Ah
Environment
• Operating
temperature range
• Storage
temperature range
• Relative humidity
•Noise level
0 to 35 °C 0 to 40 °C
-15 to +50 °C
20 to 90 % (without condensation)
< 40 dBA
(1) The high and low thresholds can be adjusted using UPS settings.
(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3) Adjustable to 200/208/220/230/240 V, must be set to the identical AC power source value.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.