Eaton 5P1000 1000VA 770W 120V Line-Interactive UPS

Eaton 5P UPS Installation and User Manual - Page 12

For 5P1000. Also, The document are for others Eaton models: 5P 750, 5P 1000, 5P 1500, 5P 850G, 5P 1550G, 5P 550 R, 5P 750 R, 5P 1000 R, 5P 1500 R, 5P 850G R, 5P 1550G R

PDF File Manual, 28 pages, Read Online | Download pdf file

5P1000 photo
Loading ...
Loading ...
Loading ...
Page 12
620-00082-01-us (en)
2.6 Display functions
Press the Enter ( ) button to activate the menu options. Use the two middle buttons ( and ) to scroll
through the menu structure. Press the Enter ( ) button to select an option. Press the button to cancel
or return to the previous menu.
Menu map for Display Functions.
Main menu Submenu Display information or Menu function
Measurements Load W VA / Load A pf / Output V Hz / Input V Hz /
Battery V min / Efficiency / Power usage
Control Load Segments Group 1: ON / OFF
Group 2: ON / OFF
These commands overrule user settings for load segments.
Start battery test Starts a manual battery test
Reset fault state Clears active faults (UPS restart required)
Restore factory settings Returns all settings to original values
Reset power usage Clears power usage measurements
Settings Local settings Sets product general parameters
Input / output settings Sets Input and output parameters
ON / OFF settings Sets ON / OFF conditions
Battery settings Sets battery configuration
Fault log Displays event log or alarms
Identification UPS Type / Part Number / Serial Number / Firmware release /
Com card address
2.7 User settings
The following table displays the options that can be changed by the user.
Description Available settings Default settings
Local settings
Language
[English] [Français] [Deutsch]
[Italiano] [Português] [Español]
[Русский]
Menus, status, notices and alarms,
UPS fault, Event Log data and
settings are in all supported
languages.
English
User selectable when UPS is
powered for the first time.
LCD settings Modify LCD screen brightness and
contrast to adapt to room light
conditions.
Audible alarm [Enabled] [Disabled on battery]
[Always disabled]
Enable or disable the buzzer if an
alarm occurs.
Enabled
In/Out settings
Output voltage [100 V] [120 V] [125 V]
On G model: [200 V] [208 V] [220 V]
[230 V] [240 V]
User selectable when UPS is
powered for the first time.
Input thresholds [Normal mode] [Extended mode]
Extended mode reduces lower input
voltage to 70 V before UPS transfers
to battery.
This can be used if the load can
withstand low voltage supply.
Normal mode
Sensitivity [High] [Low]
High: for sensitive equipment,
UPS will easily transfer to battery
when utility conditions are becoming
bad.
Low: for equipment that can
withstand bad utility conditions,
in that case, the UPS will not transfer
to battery.
High
Load segments -
Auto start delay
[No Delay] [1 s] [2 s]…[65354 s]
The connected load is powered after
the specified delay.
Group 1: 3 s
Group 2: 6 s
2. Presentation