Page 24
620-00082-01-us (en)
5. Maintenance
Battery tray removal on rack models
This operation must be performed when the UPS is switched OFF.
A
B
A - Remove the middle panel.
B - Remove the left-hand side of the
front panel by pushing the button
and then by sliding the part.
C
C - Disconnect the battery-module by
separating the town connectors
(never pull on the wires).
D
D - Remove the metal protection cover
in front of the battery (two screws).
E
E - Pull the plastic tab to remove
the battery block and replace it.
Mounting the new battery module
Carry out the above instructions in reverse order.
• To ensure safety and high performance, use only batteries supplied by EATON.
• Take care to firmly press together the two parts of the connector during remounting.