5.3 Power Cables
The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical
codes.
WARNING!
UPONSTARTING,PLEASEENSUREYOUAREAWAREOFTHELOCATIONANDOPERATIONOFTHE
EXTERNALISOLATORSCONNECTEDTOTHEUPSINPUT/BYPASSSUPPLYOFTHEUTILITYDISTRIBUTION
PANEL.
CHECKTOSEEIFTHESESUPPLIESAREELECTRICALLYISOLATEDANDPOSTANYNECESSARYWARNING
SIGNS TO PREVENT ANY INADVERTENT OPERATION
5.3.1 Cable Sizes
5.4 Battery Cabinet Connections:
Models BP240V65, BP240V65-NIB,
BP240V100 and BP240V100-NIB
Each battery cabinet design includes built-in internal battery
connection cables, breaker, fuses and terminals. The
standard cabinet can hold 20 pieces of 12V 65Ah 12V 100Ah
batteries. The DC voltage system for all cabinets is 240VDC
with ±120V internal battery strings.
Figures 6-1 and 6-2 show the overall chassis design
and exploded views for the BP240V65, BP240V65-NIB,
BP240V100 and BP240V100-NIB models. The corresponding
views for the BP240V65L, BP240V65L-NIB, BP240V100L and
BP240V100L-NIB models are shown in section 6.5 Battery
Cabinet Connections: Models BP240V65L,
BP240V65L-NIB, BP240V100L and BP240V100L-NIB.
6. Installation
UPS
MODEL
BP240V65 / BP240V100
BP240V65-NIB / BP240V100-NIB
BP240V65L / BP240V100L
BP240V65L-NIB / BP240V100L-NIB
Recommended
Torque
CABLE SIZES (THHW wiring at 167°F / 75°C)
DC INPUT GROUNDING DC INPUT GROUNDING
10kVA 6 AWG 6 AWG 6 AWG 6 AWG Anderson Connector
(No Torque Parameter)
0kgf.com / 0N•m
15kVA 6 AWG x 2 6 AWG x 2 6 AWG x 2 6 AWG x 2
20kVA 6 AWG x 2 6 AWG x 2 6 AWG x 2 6 AWG x 2
25kVA 1/0 AWG 2 AWG 1/0 AWG 2 AWG 450kgf.cm/
44N•m
30kVA 1/0 AWG 1/0 AWG 1/0 AWG 1/0 AWG
50kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
60kVA 2/0 AWG 2/0 AWG 2/0 AWG 2/0 AWG
80kVA 2/0 AWG x 2 2/0 AWG x 2
100kVA 2/0 AWG x 2 2/0 AWG x 2
Figure 5-1: BP240V65, BP240V65-NIB, BP240V100,
& BP240V100-NIB Battery Cabinet Chassis
* S3M10-30K UPS systems do not support BP240V100L/100L-NIB battery cabinet models.