5. Installation
5. Use a forklift to lift the battery cabinet from the pallet.
5.2 Selecting Installation Position
Select a proper environment to install the unit, in order to minimize the possibility of damage to the battery system and
maximize the life of the batteries.
1. Do not block air ow to the ventilation openings of the unit.
2. Ensure environmental conditions of the installation site are in accordance with the unit specications to avoid
overheat
and excessive moisture. Refer to section 4.2 Physical Requirements.
3. Do not place the unit in a dusty or corrosive environment or near any ammable objects.
4. The unit is not designed for outdoor use.
Notes:
• Placethebatterycabinetinaclean,stableenvironment.Avoidvibration,dust,humidity,ammablegases,liquidsandcorrosives.
To help prevent high temperatures in the room where the UPS is installed, extractor fans and/or cooling systems are recommended.
• Batteriesshouldbemountedinanenvironmentwherethetemperatureiswithintherequiredspecications.Temperatureisakey
factor in determining battery life and capacity. Battery temperature should be maintained between 59°F to 77°F (20°C to 25°C).
Keep batteries away from heat sources, main air ventilation areas, etc.
WARNING!
Typical battery performance data reects an operating temperature between 59°F to 77°F (20°C to 25°C).
Operating the UPS above this range will reduce the battery life, while operating the UPS below this range will
reduce battery capacity.