201156 - 3650W WIRELESS REMOTE START GENERATOR
TROUBLESHOOTING
37
Problem Cause Solution
Both CO Shield
®
LEDs not blinking 10
times upon start up.
Starting the generator within 1 minute
after being manually shutoff, not a CO
shutoff event.
Wait 1 minute before trying to restart the
generator. The LEDs should then blink ten (10)
times.
Generator cannot supply enough power
or overheating.
Generator is overloaded.
Review load and adjust. See “Connecting
Electrical Loads.
Dirty air filter. Clean or replace air filter.
Choke lever in wrong position.
Move choke lever until it stops under RUN position
or push in completely.
Engine is running but no AC output.
Poor cord connection. Check all connections.
Circuit breaker is open. Reset circuit breaker. Check all circuit breakers.
Faulty brush assembly. Replace brush assembly (Service Center).
Faulty AVR (auto voltage regulator). Replace AVR (Service Center).
Loose wiring. Inspect and tighten wiring connections.
Other. Contact the help line.
Engine hunts or falters.
Engine governor defective. Contact the help line.
Dirty fuel valve. Clean the fuel valve.
Carburetor is dirty and running lean. Contact the help line.
Choke lever in wrong position.
Move choke lever until it stops under RUN position
or push in completely.
Repeated circuit breaker tripping.
Overload.
Review load and adjust. See “Connecting
Electrical Loads.
Faulty power cords or device.
Check for damaged, bare or frayed wires. Replace
defective device.
Circuit breaker still too hot. Let unit sit for 5 mins.