Air Evacuation
Note on Adding Refrigerant
Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations. For example, in North America, the standard pipe length is 25’ (7.5m). In
other areas, the standard pipe length is 16‘ (5m). The refrigerant should be charged from the service
port
on the outdoor unit’s low pressure valve.
The additional refrigerant to be charged can be
calculated using the following formula:
CAUTION
DO NOT mix refrigerant types.
ADDITIONAL REFRIGERANT PER PIPE LENGTH
Connective Pipe
Length in (m)
Air Purging
Method
Additional Refrigerant
< Standard pipe length Vacuum Pump N/A
> Standard pipe
length
Vacuum Pump
R410A:
(Pipe length – standard length) x 0.16oZ/ft
(Pipe length – standard length) x 15g/m
R410A:
(Pipe length – standard length) x 0.32oZ/
(Pipe length – standard length) x 30g/m