•TheremainingairintheRefrigerationcycle,whichcontainsmoisture,maycausemalfunctiononthecompressor.
•Alwayscontacttheservicecenteroraprofessionalinstallationagencyforproductinstallation.
Adding Refrigerant
Add refrigerant charge according to table below:
If you use a pipe longer than 7.5m,
‘15’ g of refrigerant R-410A must be added for each extra meter.
If you use a pipe shorter than 7.5m,
The evacuate time is normal.
Refer to the Service Manual for further details.
R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from
the refrigerant cylinder to the equipment, follow the instructions below.
1. Before recharging, check whether the cylinder has a siphon or not.
There are two ways to recharge the refrigerant.
Charging the refrigerant under conditions of liquid by using a liquid pipe
Cylinder with siphon
Siphon
f
Charge the refrigerant standing the
cylinder upright.
Cylinder without siphon
f
Charge the refrigerant turning the cylinder
upside down.
•IfR-410Arefrigerantischargedwithgas,thecompositionofthechargedrefrigerantchangesandthe
characteristics of the equipment vary.
•Duringthemeasuringoperationofrefrigerantquantityaddeduseelectronicscales.
If cylinder doesn’t have syphon, upset it.
English-49
INSTALLATION07
AR5000 ED CO_IB&IM_DB68-05069A_EN.indd 49 2015/3/20 16:15:04