INSTALLATIONINSTRUCTIONS-ELECTRICDRYER
Power Supply Cord Method = U.S. Only
1. Disconnect power.
2. Remove hold-down screw and the terminal block cover.
Fire Hazard
Use a new UL listed 30 amp power supply cord.
Use a UL listed strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center
terminal (silver).
Ground wire (green or bare wire) must be connected to
green ground connector.
Connect remaining 2 supply wires to remaining
2 terminals (gold),
Securely tighten all electrical connections.
Failure to do so can result in death, fire, or
electrical shock.
3=
A. External ground conductor screw
B. Tab
C. Terminal block cover
D. Hold-down screw
Assemble ,_A"(19 mm) UL-listed strain relief (UL marking on
strain relief) into the hole below the terminal block opening.
Tighten strain relief screws just enough to hold the two clamp
sections together. Install power supply cord through the
strain relief.
A. Strain relief clamp sections
B. Dryer cabinet
C. Strain relief screws
This dryer is manufactured with the neutral ground wire
connected to the neutral (center) of the wiring harness at the
terminal block. If local codes do not permit this type of
connection, use "Four-wire connection" instructions.
Use a UL-listed power supply cord rated 240 volt min.,
30-amp and marked for use with a clothes dryer.
4=
Complete installation following instructions for your type of
electrical connection:
* Four-wire (recommended method)
Three-wire (if four-wire is not available)
14