Tripp Lite S3M80KX SmartOnline S3MX Series 3-Phase 380/400/415V 80kVA 72kW On-Line Double-Conversion UPS

Owner's Manual - Page 50

For S3M80KX.

PDF File Manual, 260 pages, Read Online | Download pdf file

S3M80KX photo
Loading ...
Loading ...
Loading ...
50
8. Specifications
MODELS S3M30KX S3M40KX S3M60KX S3M80KX
EXTERNAL BATTERIES (S3M60KX, S3M80KX require external batteries for backup. S3M30KX-NIB, S3M40KX-NIB [without
internal batteries installed], require external batteries for backup).
Type 12V Non-Spillable VRLA AGM/GEL
DC Nominal Acceptance Voltage ± 240 VDC
Quantity 40N (N 1 x Strings of 20 + 20)
Maximum Charging Current
Adjustable up to 4A ± 10%
(Max 12A with 2 x CBKIT30-40.)
Adjustable up to 8A ± 10%
(Max 24A with 2 x CBKIT30-80.)
Float Voltage 13,65V/Battery; 2,27V/Cell
Boost Charging 14,1V/Battery; 2,35V/Cell
End of Discharge 10V/Battery; 1,67V/Cell
Charger Temperature Compensation N/A
PHYSICAL
Dimensions (H x W x D) 1000 x 300 x 815 mm 1010 x 360 x 790 mm
Unit Weight (With Internal Batteries) 265 kg 316 kg N/A N/A
Unit Weight (Without Internal Batteries) 60 kg 61 kg 108 kg 113 kg
ENVIRONMENT
Operating Temperature 0 to 40˚ C ( 25˚ C for optimal battery lifespan.)
Storage Temperature 0 to 35˚ C (UPS with Batteries), -15 to 60˚ C (UPS without Batteries)
Operating Humidity 0 to 95% (Non-Condensing)
Operating Altitude < 1000 m (Derate output power by 1% per 100 m above 1000 m.)
Audible Noise < 60 dBA at 1 m < 70 dBA at 1 m < 75 dBA at 1 m
Heat Dissipation (100% Load) 5527 BTU/h 7362 BTU/h 11054 BTU/h 14738 BTU/h
Heat Dissipation (50% Load) 2994 BTU/h 3992 BTU/h 5998 BTU/h 7984 BTU/h
MANAGEMENT
Network Management Interface
Requires optional WEBCARDLX. (Monitor, control and reboot the UPS using HTML5 web,
SSH/telnet and SNMP interfaces. Supports centralised management through integration
with a wide range of Network Management Systems and DCIM platforms.)
Control Panel 62 mm LCD with supplemental LEDs.
Contact Closure Interface Requires Optional RELAYCARDSV Programmable Relay I/O Card
Remote Emergency Power Off (REPO) Feature Included (Default: Normally Closed)
RS-232 Included (Service Only)
STANDARDS
Safety IEC 62040-1:2008+A1:2013 (TUV Approval)
EMC/EMI EN 62040-2:2006 (Category C3) (TUV Approval)
Ingress Protection Rating IP20
CE Marking Yes
RoHS Compliant Yes
Quality Management System ISO 9001
OTHER INFORMATION
Colour RAL 9005 Jet Black
Mobility Casters
ACCESSORIES (Sold Separately)
Scalable Battery Cabinets
Support 5 min to 3 h runtime at 100% load. Available models include BP480V100-NIB,
BP480V100, BP480V65-NIB, BP480V65, BP480V40-NIB, BP480V40, BP480V10-NIB,
BP480V10, BP480V09. (NIB=No internal batteries.)
Network Management Card
WEBCARDLX (Monitor, control and reboot the UPS using HTML5 web, SSH/telnet and
SNMP interfaces. Supports centralised management through integration with a wide range
of Network Management Systems and DCIM platforms.)
Remote Environmental Sensors
(Require WEBCARDLX.)
E2MT (Temperature Sensor); E2MTDO (Temperature Sensor with Digital Outputs); E2MTDI
(Temperature Sensor with Digital Inputs); E2MTHDI (Temperature/Humidity Sensor with
Digital Inputs)
Contact Closure Card RELAYCARDSV
External Bypass Panel Contact your local sales representative or distributor for more information.
Scalable Charger Board Kits CBKIT30-40 (Adds 4A; Max 2) CBKIT30-80 (Adds 8A; Max 2)
Parallel Cable Kit P3080KIT
Battery Temperature Compensation
Thermostat Kit
N/A