3. Installation and Setup
27) Use the Battery Fuse PCB to connect batteries and refer to the Figures 3.5, 3.6 and 3.7. Refer to Table 3.1 for a complete battery
wiring listing.
BAT +1 cable to positive pole of #40 battery. BAT -1 cable to negative pole of #1 battery.
BAT +2 cable to positive pole of #80 battery. BAT -2 cable to negative pole of #41 battery.*
BAT N1 cable to positive pole of #20 battery. BAT N2 cable to negative pole of #21 battery.
BAT N3 cable to positive pole of #60 battery. BAT N4 cable to negative pole of #61 battery.
Figure 3.5 Figure 3.6
Figure 3.7
Notes:
• The blue numbers in above figures are “Battery Numbers” from 1 to 80, which are used for battery position identification.
• There are 2 red wires, 2 black wires and 4 blue wires, which connect the battery fuse board and batteries.
• S3M30KX/NIB battery Fuse board part number: 71-303365-XXG.
• S3M40KX/NIB Battery Fuse board part number: 71-303366-XXG.
Left Side
S3M30KX/S3M40KX
Right Side
S3M30KX/S3M40KX
Battery Fuse PCB
Input BAT-1 Input BAT +1
BAT +1 BAT +2
BAT N4
BAT N3
BAT -2*
BAT -1
BAT -2
BAT +2
BAT N1
BAT N3 BAT N4
BAT N2
* Only the BAT -2 cable and connector is routed through the cable grommet.