Tripp Lite SMART1524ET 120VAC 24VDC 1500VA 1200W Extreme Temperature Network UPS

Owner's Manual - Page 7

For SMART1524ET. Series: AG-88E6
Also, The document are for others Tripp Lite models: SMART1548ET

PDF File Manual, 169 pages, Read Online | Download pdf file

SMART1524ET photo
Loading ...
Loading ...
Loading ...
7
The UPS includes built-in USB and DB9 monitoring ports, six sets of output dry-
contacts and one set of input contacts. A slot for an optional SNMP/Web network
interface is included. The interactive front-panel LCD screen and set of three function
keys enable local monitoring of UPS and site power status, as well as allow for setting
a variety of UPS setup and control options.
UPS Front Panel
1
AC Input Breaker (30A)
The AC input breaker serves as both input overcurrent protection and an on/off
switch to allow AC line power into the UPS. It must be switched ON for proper
UPS operation.
2
AC Input Terminal Block (120V, 3 wires: L, N, G)
This terminal block is the UPS AC line power input.
• Wiring Gauge: 12 AWG recommended
• Torque Specifications: 13 in•lb (1.47 N•m)
3
AC Output Breaker (30A)
The AC output breaker serves as both output overcurrent protection and an on/off
switch to allow UPS AC output to pass through to connected equipment. It must
be switched ON for proper UPS operation.
4
AC Output Terminal Block (120V, 3 Wires: L, N, G)
This terminal block is the UPS AC line power output.
• Wiring Gauge: 12 AWG recommended
• Torque Specifications: 13 in•lb (1.47 N•m)
5
Input Contact (2 wires: Program Input 1 & 2)
To activate a programmable contact-closure input alarm to the UPS, short pins
1 & 2. Refer to LCD MENU TREE / SETTINGS / INPUT CONTACT section for more
information.
Wiring Gauge: Up to 12 AWG recommended
Torque Specifications: 4.5 in•lb (.51 N•m)