Tripp Lite SMART1524ET 120VAC 24VDC 1500VA 1200W Extreme Temperature Network UPS

Owner's Manual - Page 35

For SMART1524ET. Series: AG-88E6
Also, The document are for others Tripp Lite models: SMART1548ET

PDF File Manual, 169 pages, Read Online | Download pdf file

SMART1524ET photo
Loading ...
Loading ...
Loading ...
35
Operation
Charging Current (#42) - Selecting this option enables configuration of CHARGER
CURRENT. To configure, navigate to the CHARGER screen and select the desired
maximum charging current. Selection options are: 2 AMP, 4 AMP, 6 AMP, 8 AMP
and 10 AMP (default = 2A).
[0-MAIN MENU]
[4-SYSTEM SETTING]
[42-Charging Current]
Current setting is [## amps]
0) Set to 2 amps
1) Set to 4 amps
2) Set to 6 amps
3) Set to 8 amps
4) Set to 10 amps
>
Battery Capacity (#43) - Selecting this option enables configuration of UPS BATTERY
Capacity to match the AH of the individual batteries used in the user-supplied external
battery bank. To configure, navigate to the BAT CAP screen and select the desired AH
rating value to match the ratings of the individual batteries used.
[0-MAIN MENU]
[4-SYSTEM SETTING]
[43-BATCAP]
Current setting is [009 AH]
0) Set to 7 AH
1) Set to 9 AH
2) Set to 10 AH
3) Set to 12 AH
4) Set to 17 AH
5) Set to 26 AH
6) Set to 40 AH
7) Set to 65 AH
8) Set to 100 AH
>
Battery Coefficient (#44) - Selecting this option enables adjustment of battery
coefficient as battery system ages to provide a better estimation of runtime
remaining. To configure, navigate to the Battery Coef screen and select a
coefficient value from 0.5->2.0 (default value = 1.0).
[0-MAIN MENU]
[4-SYSTEM SETTING]
[44-Battery Coef]
Current setting is [1.0]
Enter new value. (0.5->2.0)
>
Loading ...
Loading ...
Loading ...