TP-6880 2/21 69Section 5 Troubleshooting
Problem Possible Cause Corrective Action
Generator set
stops suddenly.
Low oil pressure shutdown. Check for oil leaks. Check the oil level and add oil if
necessary.
Out of fuel. Check fuel supply.
Overcrank shutdown. Reset the controller. If the overcrank fault occurs again,
contact an authorized Kohler distributor/dealer.
Auxiliary winding circuit breaker tripped. Reset the circuit breaker (located in junction box.)
Contact an authorized Kohler distributor/dealer for
service if breaker trips repeatedly.
Emergency stop switch activated. Verify that it is safe to start the engine and apply load.
Then reset the stop switch or engine shutdown switch.
Fault shutdown. Check the controller display for fault messages. See
Section 2.5. Correct the fault condition and reset the
controller.
Generator set in the OFF mode. Press the RUN button to start the engine or press AUTO
to allow remote starting.
Remote stop command received from a remote
switch, ATS, or OnCue Plus.
Check the remote switch position. Check OnCue Plus.
Engine malfunction. Contact an authorized Kohler distributor/dealer.
Figure 5-1 General Troubleshooting Chart