1311297 Daikin Triple-Zone Mini Split System with with 47000 BTU Cooling Capacity, 48500 BTU Heating Capacity and 3x Wall Mounted Indoor Units

User Manual - Page 236

For 1311297.

PDF File Manual, 299 pages, Read Online | Download pdf file

1311297 photo
Loading ...
Loading ...
Loading ...
Troubleshooting for Outdoor Unit SiUS121827E
230 Part 6 Service Diagnosis
Reference
Troubleshooting
Check No.15 Refer to P.238
(R22566)
Caution
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
YES
NO
An output overcurrent may result from wrong internal wiring. If the system is interrupted by an output overcurrent
after the wires have been disconnected and reconnected for part replacement, check the wiring again.
Check No. 22
Check the power module.
Check No. 17
Check the installation condition.
Check No.15
Check with the inverter analyzer.
Turn off the power and disconnect
the harnesses U, V, and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and start operation.
Turn off the power. Then, turn on
the power to restart the system.
See if the same error occurs.
Check the power supply voltage.
Monitor the power supply voltage,
discharge and suction pressures,
and other factors for a long term.
Possible causes
Momentary drop of power supply
voltage
Compressor overload
Short circuit
Not a malfunction.
Keep observing.
Check the connectors and
other components.
Fully open the stop valve.
Correct the power supply.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB (main PCB).
Replace the outdoor unit
PCB (main PCB).
Error again?
Stop valve fully
open?
Any LED off?
Normal?
Inverter analyzer:
RSUK0917C
Short circuit
or wire breakage
between compressor's coil
phases?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the discharge
pressure.
Go to Check No. 18.
Is the voltage
fluctuation within ±10%
from the rated value?