Troubleshooting for Outdoor Unit SiUS121827E
206 Part 6 Service Diagnosis
Note
Reference
Reference
Troubleshooting
OL (Q1L) activating temperature: 125°C (257°F)
OL (Q1L) recovery temperature: 110°C (230°F)
Check No.01 Refer to P.232
Check No.12 Refer to P.236
(R22970)
Caution
YES
NG
NO
OK
OK
NG
NG
OK
YES
NO
NG
OK
Refrigerant shortage
Water mixed
Stop valve
Disconnect the connector S40
from the PCB.
Disconnect the 2 terminals of
the OL (Q1L).
Resistance
Resistance
Nearly 0 Ω
Nearly 0 Ω
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB (main PCB).
Discharge pipe
thermistor disconnected?
Check No. 01
Check the discharge pipe
thermistor.
Check No. 13
Check the four way valve.
Check No. 14
Check the refrigerant line.
Check No. 12
Check the electronic
expansion valve.
Replace the OL (Q1L).
Replace the OL harness.
Connect the connector S40
properly.
Is the connector S40
properly connected?
Check the
resistance between
the 2 terminals on connector
S40.
Check the
resistance between the 2
terminals of the OL
(Q1L).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.