62
6. Operation and Conguration of
S3M UPS Models and Battery Cabinets
6.3.4 Conguring the S3M25-100K UPS and Optimizing
Charging of
the BP240V65/V65L and BP240V100/V100L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For
example, UPS model S3M100K UPS has no internal batteries and is Battery Group 1 by default. However, to connect a
BP240V100L cabinet with 40 internal batteries to the S3M100K, the S3M100K UPS must be congured to Battery
Group 2. To connect a second BP240V100L cabinet to the S3M100K UPS, the Battery Group must be set to 4 (four
sets of 20 batteries). Obtain the Battery Group number based on the specic S3M UPS and Battery Cabinet models
combination from the chart under Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to external battery cabinets
designed for the S3M-Series UPS Series.
Step 3: Setting Single Battery (Ah) Capability
Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specic
battery cabinet model:
• BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40
• BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65
• BP240V100/BP240V100L: the Single Battery (Ah) Capacity is 100
The Single Battery (Ah) values can be 7~2000.
Scroll to the next display screen by pressing the down arrow.