6
Features
A
B
AC Input Power Inlet: The IEC 60320 C20 inlet connects to the
detachable AC Input Power Cord.
AC Input Power Cord: The detachable cord has an IEC 60320
C19 connector
A
and an IEC 60320 C20 connector
B
.
AC Input Adapter: The adapter converts the AC input power cord
to a NEMA L6-20P plug. The included retention bracket (not
shown) secures the connection.
IEC 60320 C13 Output Receptacles: During normal operation,
the output receptacles distribute AC power to connected
equipment. When an outlet is live, the associated LED illuminates.
Digital Load Meter (Ammeter): The total electrical current drawn
by connected equipment is displayed on the meter in amperes.
Longer Mounting Brackets: Use these brackets to mount the
PDU horizontally in a standard rack or rack enclosure. The
mounting depth can be adjusted by attaching the brackets to
different positions on the PDU.
Shorter Mounting Brackets: Use these brackets to mount the
PDU in a 0U rack, wall or under-counter configuration.
Factory Port: The port is reserved for configuration by factory
authorized personnel only. Do not connect anything to the port.
WEBCARDLX: Allows you to operate this PDU as a managed
network device, accessible via SNMP network management
platform, web browser, SSH or Telnet.