Tripp Lite PDUMH20HVNET 3.7kW Single-Phase 208/230V Switched PDU - LX Platform, 8 C13 Outlets, C20 Input

Owner's Manual - Page 4

For PDUMH20HVNET.

PDF File Manual, 36 pages, Read Online | Download pdf file

PDUMH20HVNET photo
Loading ...
Loading ...
Loading ...
4
A
B
C
D
1-5
1-5
Reduced-Depth Mounting: Use 3 screws
A
to attach each of the 2 shorter
mounting brackets
B
to the PDU as
shown. Mount the PDU to a stable surface
with the outlets facing upward by inserting
2 or more user-supplied screws
C
through
the mounting brackets
D
and into secure
mounting points.
Installation
15
Connecting the PDU
2-1
Input Power Cord Connection: Attach the
cable clamp to the PDU by inserting the
tabs into available slots on the top and
bottom of the power inlet
A
. Secure the
clamp by sliding it to the right. Attach the
included power cord to the PDU by
inserting the IEC C19 connector
B
of the
power cord into the cable clamp and IEC
C20 power inlet
C
. Install the included
screw
D
on the cable clamp to secure the
power cord connection. Connect the other
end of the input power cord to a
compatible source of AC power, such as a
UPS system, PDU or utility outlet.
Note: The AC power source should not share a circuit with a heavy electrical load.
Note: When connecting the PDU, it should be provided with over-current protection and a maximum 20A branch-rated over-
current protection device.
2-2
NEMA Adapter Connection: This product
includes a plug adapter that adds a NEMA
L6-20P plug to the input power cord. Use
this adapter only if you will be connecting
the PDU to a NEMA L6-20R outlet. Insert
the IEC C19 connector
A
of the adapter
into the IEC C20 connector
B
of the input
power cord. Secure the connection with the
retention bracket
C
by using the included
bolts to fasten the two halves of the
bracket around the connection as shown.
Connect the NEMA L6-20P plug to a
compatible source of AC power
D
, such as
a UPS system, PDU or utility outlet.
CAUTION: To avoid the risk of electric
shock, ensure that the Neutral (L2)
conductor has been identified before
connecting the PDU.
Note: Do not attempt to attach a user-supplied power
cord unless it is certified to be compatible with the input
power source that will be used by the PDU.
B
D
A
C
2-1
2-2
A
C
B
D