Clearance Requirements (continued):
Example of Multiple Units with Horizontal Airflow
CAUTION
Failure to observe clearance and air flow requirements will result in poor system
performance and premature equipment failure!
MISE EN GARDE
Le non-respect des exigences de dégagement et de circulation d’air aura
pour résultat un rendement médiocre du système et une défaillance
prématurée de l’équipement!
Locating and Mounting Evaporator Coil
General Guidelines:
Do not place the evaporator above or close to door openings. This will help
prevent potential icing problems.
Allow a minimum clearance equal to or greater than the coil height on all sides of
the coil for proper air flow and service access.
Use the evaporator coil for a template to locate and drill the mounting holes (1/2”
diameter).
Place a 1” and a 1-5/8” washer on each nylon bolt and insert through the drilled
mounting holes in the ceiling from the exterior of the walk-in ceiling panel.
BUILDING WALL
(VIEWED FROM ABOVE)
AIR
FLOW
AIR
FLOW
MINIMUM
DISTANCE
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”
INTAKE AIR
MINIMUM DISTANCE 24”
24”