30 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 04
Table 16. Alarm Conditions (Continued)
Conditions Possible cause Action
The UPS does not start
The input source is not connected
correctly.
Check the input and battery connections.
The Remote Power Off (RPO) switch is
active or the RPO connector is missing.
If the UPS Status menu displays the "Remote
Power Off" notice, deactivate the RPO input.
77..22 DDeettaaiill AAllaarrmm oorr FFaauulltt CCooddee
Table 17. Alarm Codes
Alarm Code Message Description
#004
UPS TEMP. ALARM Ambient or NTC temperature is high
#110
BUILDING ALARM Building alarm
#604
BATTERY LOW Battery level is below Remaining
Capacity Limit threshold or Run Time
to Empty is below Remaining Time
Limit threshold.
#802
IMMINENT SHUTOFF Shut down imminent
#806
EMERGENCY OFF Emergency stop was proceed
#808
OVLD PREALARM The load percent is > the overload
level setting(default 105%)
Table 18. Alarm Fault Codes
Fault Code Message Description
#007 FAN FAULT Ventilator fault
#60D NO BATTERY Battery not present
#607 BATTERY FAULT Battery need replacement OR is
faulty
#004
UPS TEMP. FAULT UPS internal temperature is high,
over fault point
#808
POWER OVERLOAD Overload counter time reach,
transfer to Fault mode
#805
OUTPUT SHORTED Short circuit on output
#107
INPUT BAD WIRING Site wiring fault that can come of
Phase neutral inversion on single
phase UPS
#809
INDU OVERLOAD Inductive overload occurred, transfer
to Fault mode
#80A CAPA OVERLOAD Capacitive overload occurred,
transfer to Fault mode
#804
IMBALANCE LOAD Load is unbalance
Detail Alarm or Fault Code