28 Eaton Tripp Lite Series SmartPro User Guide 614-40194—Rev 04
66..55 RReeppllaacciinngg tthhee UUPPSS EEqquuiippppeedd wwiitthh aa HHoottSSwwaapp MMBBPP
The HotSwap MBP module makes it possible to service or even replace the UPS
without affecting the connected loads (HotSwap function).
Maintenance
1. Set switch (45) to Bypass position. The red LED on the HotSwap MBP module
goes ON, indicating that the load is supplied directly with AC input source
power.
2. Stop the UPS by pressing the
button on the UPS control panel. LED (43)
"UPS ON - OK to switch" goes OFF, the UPS can now be disconnected and
replaced.
Return to normal operation
1. Check that the UPS is correctly connected to the HotSwap MBP module.
2. Start the UPS by pressing the
button on the UPS control panel. LED (43)
"UPS ON - OK to switch" on the HotSwap MBP module goes ON (otherwise,
there is a connection error between the HotSwap MBP module and the UPS).
3. Set switch (45) to Normal position. The red LED on the HotSwap MBP module
goes OFF.
Replacing the UPS Equipped with a HotSwap MBP