Cooper&Hunter CHV6-144URB - Cooling and Heating Solutions

Installation Manual - Page 10

For CHV6-144URB. Also, The document are for others Cooper&Hunter models: CHV6-072URB, CHV6-096URB, CHV6-120URB, CHV6-168URB, CHV6-192URB

PDF File Manual, 44 pages, Read Online | Download pdf file

CHV6-144URB photo
Loading ...
Loading ...
Loading ...
2
Capacity
kBtu/h(RT)
96(8RT)
120(10RT)
144(12RT)
168(14RT)
Model
192(16RT)
CHV6-072URB
CHV6-096URB CHV6-120URB
CHV6-144URB
CHV6-168URB
CHV6-192URB
(6RT)
Measuring Instrument
and Tool
R407C
R410A
Reason of Non-Interchangeability
and Attention (
: Strictly Required)
Application
Pipe Cutter
Chamfering
Reamer
——
Cutting Pipe
Removing Burrs
Flaring Tool
○■
Flaring for Tubes
Extrusion
Adjustment
Gauge
*
R410A requires high pressure resistance piping and larger
flaring. In case of material 1/2H, flaring is not
available.(The flaring tools for R410A are applicable to
R407C)
Dimensional Control
of Tube after Flaring
Pipe Bender
*
In case of material 1/2H, bending is not available. Use elbow
for bend and braze.
Bending
Expanding
Tool
*
In case of material 1/2H, expanding of tube is not available.
Use joint for connecting tube.
Expanding Tubes
Torque
Wrench
*
For Φ1/2in., Φ5/8in. of R410A, spanner size is up to 5/64in.
Connection of Flare Nut
Brazing Tool
*
Perform brazing work properly (adjustable flame and heating
method, filler applicable)
Nitrogen Gas
*
Strict control against contamination (Blow nitrogen during
brazing.)
Prevention from Oxidation
during Brazing Air-tight test
Refrige-
rant
Pipe
Lubrication Oil
(for Flare
Surface)
* Use a synthetic oil which is equivalent to the oil used in the
refrigerant cycle.
* Synthetic oil absorbs moisture quickly.
Applying Oil to the Flared
Surface
Refrigerant
Cylinder
*
Check the cylinder for the corresponding refrigerant.
Liquid refrigerant charging is required regarding zeotropic
refrigerant.
Refrigerant Charging
Vacuum Pump
The current pumps are applicable. However, it is required to
mount a vacuum pump adapter which can
prevent reverse flow
when a vacuum pump stops, resulting in no reverse oil flow.
Vacuum Pumping
Vacuum Pumping, Vacuum
Holding, Refrigerant Charg-
ing and Check of Pressures
Control Valve
Charging
Hose
Charging
Cylinder
×
*
Use the weight scale when charging
Refrigerant Charging
Weight Scale
——
Measure refrigerant quantity
Adapter for
Vacuum
Pump Reverse
Flow prevention
Refrige-
rant
Charge
Vacuum
Drying
Interchangeable
with R410A
*
The current gas leakage detector (R22) is not applicable due
to different detecting method.
Refrigerant Charging Gas
Leakage Check
For Φ1/4in.Φ3/8.Φ3/4in., spanner size is the same.
*
No interchangeability is available due to higher pressures
when compared with R22. Connection diameter is different:
R410A: UNFl/2, R407C: UNF7/16
Do not use old ones to the different refrigerant. Otherwise,
mineral oil will flow into the cycle and cause sludges, resulting
in clogging or compressor failure.
interchangeable with R407C
Interchangeable
with R410A
*
■: only for Refrigerant R410A (not interchangeable with R22)
: interchangeable with current R22
× : Prohibited
: only for Refrigerant R407C (not interchangeable with R22)
Brazing for Tubes
Refrigerant
Gas Leakage
Detector
Interchangeability
with
R22
2.Before Installation
Line-Up of Outdoor Unit
Basic Unit
Capacity
kBtu/h(RT)
Model
×
-
Loading ...
Loading ...
Loading ...