79
8. Specications
Model S3M25K S3M30K S3M50K S3M60K S3M80K S3M100K
OVERVIEW
Capacity 25 kVA/25 kW 30 kVA/30 kW 50 kVA/50 kW 60 kVA/60 kW 80 kVA/80 kW 100 kVA/100 kW
Topology True On-Line Double Conversion; Voltage- and Frequency-Independent (VFI)
INPUT
Voltage and Phase 208/220V (Ph-Ph); 120/127V (Ph-N); 3-Phase, Neutral and Ground
Voltage Range -20%, +25% (Ph-Ph 166–260V or 176–275V) at 100% Load; -40%, +25% (Ph-Ph 125–260V or 132–275V) at <50% Load
Frequency (Range) 50/60 Hz, Selectable (40 – 70 Hz)
Power Factor ≥ 0.99 (100% Linear Load); ≥ 0.98 (50% Linear Load)
Harmonic Distortion < 3% THDi (100% Load)
Dual AC Input Yes
Backfeed Protection Yes
OUTPUT
Voltage and Phase 208/220V (Ph-Ph); 120/127V (Ph-N); 3-Phase, Neutral and Ground
AC Voltage Regulation ±1% of Nominal (Double-Conversion Mode, Converter Mode or Battery Mode); ±10% of Nominal (ECO Mode)
Power Factor 1.0 (Unity Output Power Factor)
Frequency Selectable ±1%, ±2%, ±4%, ±5%, ±10% of Input (Default: ±5%)
Frequency Regulation ±0.1 Hz (Converter Mode or Battery Mode)
Overload (AC Mode) Load ≤ 110%=1 hour; Load ≤ 125%=10 min.; Load ≤ 150%=1min.; Load >150%=Bypass
Crest Factor 3:1 Maximum
Harmonic Distortion ≤ 2% THD (100% Linear Load); ≤ 5% THD (100% Non-Linear Load)
Waveform Pure Sine Wave
Transfer Time 0 ms (Line ‹–› Battery and Inverter ‹–› Bypass); <8 ms (Battery ‹–› ECO)
Parallel Capability Parallel up to 5N+1 Units for Increased Capacity or up to 6 for Redundancy
BYPASS
Bypass Voltage Range Upper Limit: +10%, +15%, +20% or +25% (Default: +20%); Lower Limit: -10%, -20%, -30% or -40% (Default: -30%)
Bypass Frequency Range ±10% (Adjustable)
EFFICIENCY
Online Mode up to 94%
ECO Mode up to 98%
BATTERY AND CHARGER
DC Acceptance Voltage ±120V DC (Nominal)
Battery Conguration External Only* External Only* External Only* External Only* External Only* External Only*
Internal Battery Quantity None None None None None None
Run time (100% Load)
UPS runtime depends on the connected loads and the battery pack/cabinet model. Refer to the model page at Tripplite.Eaton.com
for runtimes.
Run time (50% Load)
External Battery Pack (Cabinet)
Models
*Refer to section 3.9 UPS to Cabinet Model Compatibility
Charging Current (Default) 1 – 20A (0.15C) 2 – 20A (0.15C) 4 – 40A (0.15C) 4 – 40A (0.15C) 6 – 60A (0.15C) 8 – 80A (0.15C)
ENVIRONMENT
Operating Temperature 0 – 40˚ C
Storage Temperature -15 – 60˚ C
Operating Humidity 0 – 95% (Non-Condensing)
Operating Altitude < 1000 m (Derate output power by 1% per 100 m above 1000 m.)
Audible Noise at 1 m < 65.4 dBA < 67.8 dBA < 72 dBA < 72 dBA < 74 dBA < 75.6 dBA
Heat Dissipation (100% Load) 6339 BTU/h 7679 BTU/h 12628 BTU/h 15154 BTU/h 19932 BTU/h 24915 BTU/h
MANAGEMENT
Display Panel Large 12.7 cm (5-inch) Multi-language Touchscreen Display with Supplemental LEDs
Communications
Optional SNMP Network Management Card (WEBCARDLXMINI) and three integrated MODBUS Ports: RS-232, RS-485 (RJ45), USB.
The Relay I/O card is optional.
STANDARDS
Safety UL1778:2014 (5th Edition); CAN/CSA-C22.2 No. 107.3-14 (3rd Edition)
EMC/EMI FCC Part 15B Class A
Additional ENERGY STAR 2.0, RETIE, IP20 Ingress Protection Rating; RoHS, ISTA 3B/Vibration, Shock and Tip tested.
PHYSICAL
Unit Dimensions (H x W x D)
39.4 x 11.8 x 31.5 inches/
1000 x 300 x 800 mm
47.2 x 17.4 x 33.46 inches/
1200 x 442 x 850 mm
62.99 x 23.62 x 33.46 inches/
1600 x 600 x 850 mm
Unit Weight 209 lb. / 95 kg 212 lb. / 96 kg 353 lb. / 160 kg 364 lb. / 165 kg 624 lb. / 283 kg 708 lb. / 321 kg